7-3-8. Error / Operation output

Outdoor unit
Outdoor unit
interface PCB
SW16
Operation
In-operation output: An in-operation indication signal is output as long as at least one indoor unit is in operation in
the line.
Failure output: A failure in dication signal is output if check code occurs in at least one indoor / outdoor unit in the line.
Note 1: Output Relay (K1, K2) Contact Specifications
Output terminals (OUTPUT1, 2) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to loads K1 and K2 insert a surge killer CR (for an AC power
supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
220-240 VAC, 10 mA or more, 1 A or less
24 VDC, 10 mA or more, 1 A or less (non-conductive load)
C1
Connector cable 1
CN511
Connector on Interface side (green)
K1,K2
Relays
L1
Failure indication Lamp
L2
Operation indication Lamp
OUTPUT1
Failure output
OUTPUT2
Operation output
PJ20
Connector on optional PCB side
PS
Power supply unit
TB1
Terminal block
Optional PCB
TB1
C1
K1
C
N
5
1
1
P
J
2
0
K2
45
61
Locally procured
(See "NOTE")
L1
OUTPUT1
L2
OUTPUT2
OUTPUT3
Shield
wire
PS
PS