LRM 8112 Movement Detector
Technical data
• Sensitivity
level
optimised for use in office (or industrial)
applications. Most arm/hand movements
will be detected within the sensitivity area
for radial movements.
pattern
nearly circular,
8 m diameter for tangential
movements
6 m diameter for radial movements
• Output
voltage
0 Vdc for active detector (open collector,
normally open.)
-0.5 - +15 Vdc maximum rating
current
maximum current sinking > 10 mA
Outputs can be "wired OR" up till at least
10 detectors.
One detector output can drive up to at
least 4 controller inputs.
• Inactive-state delay timer
0, 5, 10, 30 minutes ±20%, cumulative.
to be selected via 3 dipswitches.
• Indicator
Red LED, "on" when output is active. Can
be disabled via dipswitch.
• Power supply
12 Vdc ±10%, 10 mA (LED on), derived
from connected controller
• Electrical connections
modular socket ("Telejack") standard pinning:
1. 12 Vdc supply voltage
2. ground
3. 5 Vdc supply voltage (n.a.)
4. light sensor output signal (n.a.)
5. infrared receiver output signal (RC5)
(n.a.)
6. movement detector output signal
• Housing
colour
white RAL 9010
material
polycarbonate
flame rating
V0
850 °C ≤ 5 s extinction
glow wire test
visible surface texture
9-125 UN-D 249, suitable for lacquering
• Operating conditions
ambient temperature
+5 - +50 °C
relative humidity
20 - 85%, no condensation
• Storage conditions
ambient temperature
-25 - +85 °C
relative humidity
10 - 95%
• EMC
immunity
in accordance with EN 50082-1
radiated interference
in accordance with EN 50081-1
• Reliability
call rate
1% per year (estimated)
life time
10 years (estimated)
• Dimensions
sensor
116 mm x 30 mm
mounting plate
70 mm x 9 mm
mounting ring
113 mm x 60 mm
• Weight
sensor
90 g
mounting plate
10 g
mounting ring
70 g
• Mounting
fixation
plate with bayonet-catch for surface
mounting ring with springs and bayonet-
catch for recessed mounting minimum
recess clearance 60 mm. Ceiling tiles need
not be removed for mounting
Related equipment
• Stand-alone control
TRIOS
light controller
LRC 1010, LRC 1020
LRC 1015, LRC 1025
LRC 1620 DALI Room Controller
• General Purpose Components
cables
sensor cables
LCC 8011, LCC 8012, LCC 8013,
LCC 8014
branching connector
LCC 8024
sensors
multi-sensor
LRI 8133
Related documentation
• Installation Instructions
• Technical Application Manual TRIOS
Miscellaneous
• Sensitivity
The unit is based on the "passive infrared principle", i.e. it detects
infrared radiated by a moving object.Therefore the practical
sensitivity depends on the combination of characteristics of the
object. It increases with size and temperature (difference with
background), and changes with speed and direction of the moving
object. Sensitivity is maximum for tangential movements and minimal
for radial movements.