Ethos IS100 Installation Instructions Manual

Wood fire with ezc-031135 zero clearance cabinet and exa-10042 econair flue system

Advertisement

Quick Links

Page 1 of 2
Specifications / Installation instructions
Page 1 of 6
Specifications / Installation Instructions
Freestanding Models: Genesis, Aquos, Phoenix
Insert model: Zero Clearance Cabinet for Ares Fire
( E ffective 1 Jan 2017 )
Effective 1st January 2017
IMPORTANT
It is the responsibility of the installer to ensure that the installation of this appliance complies with AS/NZS 2918:2001
Supplied:
Ethos freestanding fire
Flue kit:
Installation instructions for the Ethos IS100 wood
fire with EZC-031135 Zero Clearance Cabinet and
EXA-10042 EconAir flue system
Not included in kit:
Flue kit:
Ethos wood fires must be fitted with the Ethos factory flue kit as this has been specifically designed to
achieve optimum performance of the unit. It must be a minimum of 4.2 mtrs.
note: It is essential that the 130mm stainless steel flue is well sealed & riveted it must also be securely
fitted & sealed into the exhaust spigot of the fire using stainless steel rivets or screws.
Shielding:
The Ethos Genesis / Aquos / Phoenix wood fires do not require additional shielding, however reduced
clearances may be obtained using approved heat resistant material.
( r ef: AS/NZS 2918: 2001 )
Seismic restraint:
Use 2 x 6mm dynabolts or similar, two holes are provided in the rear of the firebox pedestal or feet
for this purpose.
Floor protector:
The floor protector must be a minimum of 12mm thick approved heat resistant material.
WARNING: THE APPLIANCE AND FLUE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH AS/NZS 2918: 2001
AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODE OR CODES.
WARNING: APPLIANCES INSTALLED IN ACCORDANCE WITH THIS STANDARD SHALL COMPLY WITH THE
REQUIREMENTS OF AS/NZS 4013 WHERE REQUIRED BY THE REGULATORY AUTHORITY, I.E. THE APPLIANCE
SHALL BE IDENTIFIABLE BY A COMPLIANCE PLATE WITH THE MARKING " TESTED TO AS/NZS 4013 "
ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING FROM THE TESTING
AUTHORITY IS CONSIDERED TO BE IN BREACH OF THE APPROVAL GRANTED FOR COMPLIANCE WITH AS/NZS
These instructions should be read in conjunction with the instruction
4013.
and install documents for the IS100 wood fire.
CAUTION: MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING
THE DIMENTIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS. WHERE SUCH
ACTION IS CONSIDERED, THE MANUFACTURER SHOULD BE CONSULTED
Retain these instructions for future reference
CAUTION: CRACKED AND BROKEN COMPONENTS, e.g. GLASS PANELS OR FIREBRICKS, MAY RENDER THE
INSTALLATION UNSAFE.
THE MANUFACTURER RESERVES THE RIGHT TO CHANGE SPECIFICATIONS OR DESIGNS WITHOUT PRIOR NOTICE
3 x 1200 130mm SS flue
1 x 600 130mm SS flue
2 x 200 x 1200 liners ( black )
1 x 200 x 1200 liner ( galv )
1 x Revolving cowl & cone
1 x Ceiling plate ( black )
Flashing
Hearth / Floor protector
Screws / Rivets
Dynabolts
Fire cement
Mounting rails
IN THE FIRST INSTANCE.

Advertisement

loading
Need help?

Need help?

Do you have a question about the IS100 and is the answer not in the manual?

Questions and answers

Summary of Contents for Ethos IS100

  • Page 1 Mounting rails Flue kit: Ethos wood fires must be fitted with the Ethos factory flue kit as this has been specifically designed to achieve optimum performance of the unit. It must be a minimum of 4.2 mtrs. note: It is essential that the 130mm stainless steel flue is well sealed & riveted it must also be securely fitted &...
  • Page 2: Important Installation Notes

    Effective 1st January 2017 Following these instructions allows for the Ethos IS100 wood Following these instructions allows for the Ethos IS100 Insert wood fire to be safely fire to be safely installed in a timber frame wall, without the need...
  • Page 3 Page 3 of 6 Specifications / Installation Instructions Insert model: Zero Clearance Cabinet for Ares Fire Effective 1st January 2017 Floor Insulation Detail The following table sets out the calculated floor protector projections required to ensure that temperatures on the exposed floor comply with the requirements of standard AS/NZS 2918:2001 for exposed floors constructed of medium heat resistant materials.
  • Page 4 Side vent panel, one mounted 25mm min clearance to each side of the cavity. Refer to page 6 for further information. No insulation required if mounted on concrete oor. If mounted on combustible materials, Ethos part EZC-031140 insulation base panel is required.
  • Page 5 Page 5 of 6 Specifications / Installation Instructions Insert model: Zero Clearance Cabinet for Ares Fire Effective 1st January 2017 Top View Example 1200(w) x 600(h) Supalux 9mm heat resistant board 585mm min depth 25mm min clearance Open air cavity running down from ceiling space, allows cooling air to be drawn from ceiling space to cool Zero Clearance Cabinet.
  • Page 6 Page 6 of 6 Specifications / Installation Instructions Insert model: Zero Clearance Cabinet for Ares Fire Effective 1st January 2017 Front 3/4 View Example with Air Cavity and Vent Plates Cavity to allow cool air 1200mm wide x 600mm high to be drawn from roof Supalux 9mm heat resistant space to ventilate the...