ENERVISTA SOFTWARE INTERFACE
4
2.
Enter the serial number of the F60 device to lock to the settings file in the Serial Lock field.
3.
Click the OK button to apply the change.
The settings file and corresponding secure FlexLogic equations are now locked to the F60 device specified by the serial
number.

4.1.9 Settings file traceability

A traceability feature for settings files allows the user to quickly determine if the settings in a F60 device have been
changed since the time of installation from a settings file. When a settings file is transferred to a F60 device, the date, time,
and serial number of the F60 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This
information can be compared with the F60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the F60
device or obtained from the F60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.