CHAPTER 6: SETPOINTS
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
RESTART INHIBIT
Range: OFF, 1 to 50000 s in steps of 1 s
Default: OFF
Sets the amount of time following a stop before a start control is permitted. OFF defeats
this feature.
Figure 46: Start Inhibit, Starts per Hour, Time Between Starts, and Restart Inhibit logic
diagram
MOTOR STATUS
Running
Starting
Clk
In
ACTUAL VALUE
Thermal Capacity Used
COMMA D
Clear Learned TCU
SETTI G
m = Thermal Inhibit
setting = OFF
setting = 0%
TC
in
Tc + m/100 x Tc
in
in
*saturates at 100%
I
I
avg
> Current Cutoff Level
avg
LOGIC OPERA D
THERMAL INHIBIT
STARTS/HR INHIBIT
TIME-BTWN-STARTS INHIBIT
OR
RESTART INHIBIT
FUSE FAIL INHIBIT
PH REVERSAL INHIBIT
Edge Triggered
Sample & Holds
(Non-Volatile)
-
Clk
Clk
Clk
In
In
In
+
Preset
Preset
Presets latches to 85%
TC
learned
85%
TCU
TC
SETTI G
Starts/Hour Limit
STARTS/HOUR COUNTER
setting = OFF
Counter setting
SETTI G
t = Time Between Starts
do
setting = OFF
0
t
do
SETTI G
t = Restart Inhibit
do
setting = OFF
0
t
do
LED: Start Inhibit
Operate Output Relay 3 (Start Inhibit)
S4 CONTROL
Clk
Clk
In
In
Preset
Preset
Preset
Select
Largest
Value
LOGIC OPERA D
THERMAL INHIBIT
AND
> 100% - TCU
learned
ACTUAL VALUE
Learned TCU
THERMAL INHIBIT
LOGIC OPERA D
AND
STARTS/HR INHIBIT
ACTUAL VALUE
STARTS/HR INHIBIT
LOGIC OPERA D
TIME-BTWN-STARTS INHIBIT
AND
ACTUAL VALUE
TIME-BTWN-STARTS INHIBIT
LOGIC OPERA D
AND
RESTART INHIBIT
ACTUAL VALUE
RESTART INHIBIT