Representation Of Analog Values In Voltage Measuring Ranges - Siemens Simatic S7-1500 Manual

Hide thumbs Also See for Simatic S7-1500:
Table of Contents

Advertisement

Analog value processing
C.3 Representation of input ranges
C.3.1

Representation of analog values in voltage measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table C- 6
Voltage measuring ranges ±10 V, ±5 V
Values
dec.
hex.
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
-32768
8000
Table C- 7
Voltage measuring range 1 to 5 V, 0 to 10 V
Values
dec.
hex.
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-4864
ED00
-32768
8000
180
Voltage measuring range
±10 V
>11.759 V
11.759 V
10 V
7.5 V
361.7 µV
0 V
-7.5 V
-10 V
-11.759 V
<-11.759 V
Voltage measuring range
1 to 5 V
>5.704 V
5.704 V
5 V
4 V
1 V + 144.7 µV
1 V
0.296 V
< 0.296 V
Range
±5 V
>5.879 V
Overflow
5.879 V
Overrange
5 V
Nominal range
3.75 V
180.8 µV
0 V
-3.75 V
-5 V
Underrange
-5.879 V
<-5.879 V
Underflow
0 to 10 V
>11.759 V
11.759 V
10.0 V
7.5 V
361.7 μV
0 V
-1.759 V
< -1.759 V
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB
Range
Overflow
Overrange
Nominal range
Underrange
Underflow