FC 300 Instruction Manual
The parameter shortcut
The parameter shortcut allows direct access to any parameter.
Quick Transfer of Parameter Settings
"
Once the setup of a drive is complete, we
recommend that you store the data in the LCP or
on a PC via MCT 10 Setup Software Tool.
Data storage in LCP:
Go to par. 0-50 LCP copy
1.
Press the [OK] key
2.
Select "All to LCP"
3.
Press the [OK] key
4.
All parameter settings are now stored in the LCP indicated by the progress bar.
When 100% is reached, press [OK].
NOTE
Stop the unit before performing this operation.
You can now connect the LCP to another adjustable frequency drive and copy the parameter
settings to this adjustable frequency drive as well.
Data transfer from LCP to drive:
Go to par. 0-50 LCP copy
1.
Press the [OK] key
2.
3.
Select "All from LCP"
Press the [OK] key
4.
The parameter settings stored in the LCP are now transferred to the drive indicated by
the progress bar. When 100% is reached, press [OK].
NOTE
Stop the unit before performing this operation.
Reset to Default Setting
"
To restore all parameter values to their default setting, go to par. 14-22 Operating Mode and
select Initialization. Power down the adjustable frequency drive. The adjustable frequency drive
will automatically restore to default settings during the next power-up.
How to Program
can be carried out by holding down the [Main Menu] key for 3 seconds.
MG.33.A2.22 - VLT is a registered Danfoss trademark
29
Need help?
Do you have a question about the FC 300 and is the answer not in the manual?
Questions and answers