Hitachi WJ200-001S Instruction Manual page 106

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Jog Frequency – The jog speed setting is used whenever the Jog command is active.
The jog speed setting range is arbitrarily limited to 10 Hz, to provide safety during
manual operation. The acceleration to the jog frequency is instantaneous, but you can
choose from three modes for the best method for stopping the jog operation.
Func.
Name
Code
Jog frequency

Jog stop mode

Note 1: For jogging operation, turn JG terminal ON at first and then turn FW or RV terminal
on.
Note 2: When jogging stop mode A039=02 or 05, DC braking data is needed.
Note 3: During jogging operation, frequency can be set with output frequency setting F001.
"A" Function
Description
Defines limited speed for jog,
range is from start frequency to
9.99 Hz
Define how end of jog stops the
motor; six options:
Free-run stop (invalid
during run)
Controlled deceleration
(invalid during run)
DC braking to stop(invalid
during run)
Free-run stop (valid during
run)
Controlled deceleration
(valid during run)
DC braking to stop(valid
during run)
Run
Defaults
Mode
Initial data
Units
Edit
6.00
Hz
04
321