This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an RCD of Type B (time de- layed) shall be used on the supply side of this product. See also Danfoss Application Note on RCD, MN.90.GX.YY.
1 Quick Guide VLT 2800 Quick Guide 1.1.2 Safety Instructions • The frequency converter must be disconnected from the mains if repair work is to be carried out. Check that the mains supply has been disconnected and the prescribed time has passed before removing motor and mains plugs.
Page 4
1.2.2 Available Litterature This quick guide contains only the very basic information necessary for installing and running the drive. For more information please consult the VLT 2800 Design Guide, MG.27.EX.YY Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com...
1.3 Mechanical Installation VLT 2800 frequency converters allow side-by-side installation on a wall in any position as the units do not require ventilation on the side. Because of the need for cooling, there must be 10 cm free air passage above and below the frequency converter.
Page 6
VLT 2800 Quick Guide 1 Quick Guide With the IP 21 solution all units require a minimum of 100 mm air on each side. This means that side-by-side mounting is NOT allowed. Size mm øa øb øc VLT 2803 - 2815...
Page 7
1 Quick Guide VLT 2800 Quick Guide 1.3.2 Terminal cover The drawing below gives the dimensions for NEMA 1 terminal covers for VLT 2803-2875. Dimension 'a' depends on the unit type. 1.3.3 IP 21 solution Type Code number VLT 2803-2815 200-240 V,...
1 Quick Guide VLT 2800 Quick Guide 1.4 Electrical Installation 1.4.1 Electrical Installation in General All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required, (60-75° C) recommended. Details of terminal tightening torques.
Page 10
VLT 2800 Quick Guide 1 Quick Guide VLT 2880 - VLT 2882 Fit screened/armoured cable from the motor to the motor terminals of the frequency converter, i.e. U, V, W. The screen ends in a screen connector. 1.4.3 Mains connection...
Page 11
1 Quick Guide VLT 2800 Quick Guide 1.4.4 Motor connection Connect the motor to terminals 96, 97, 98. Connect earth to terminal 99. Technical data for correct dimensioning of cable cross-section. All types of three-phase asynchronous standard motors can be connected to a frequency con- verter.
100 nF capacitor between the screen and the chassis. See section entitled Earthing of screened/armoured control cables in the VLT 2800 Design Guide for the correct termination of control cables. Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com...
Page 13
1 Quick Guide VLT 2800 Quick Guide Function 01-03 Relay outputs 01-03 can be used for indicating status and alarms/warnings. 24 V DC voltage supply. 18-33 Digital inputs. 20, 55 Common frame for input and output terminals. Analog output for displaying frequency, reference, current or torque.
Page 14
VLT 2800 Quick Guide 1 Quick Guide Connect all earthing systems to ensure the lowest possible conductor impedance. The lowest possible conductor impedance is achieved by keeping the conductor as short as possible and by grounding with the greatest possible surface area. If multiple drives are installed in a cabinet, the cabinet backplate, which must be made of metal, should be used as a joint earth reference plate.
Page 15
1 Quick Guide VLT 2800 Quick Guide 1.4.11 Extra protection RCD relays/ELCBs, multiple protective earthing or earthing can be used as extra protection, pro- vided that local safety regulations are complied with. Three phase VLT frequency converters require an RCD type B. If an RFI filter is mounted in the drive and either the switch of the RCD or a manually operated switch is used to connect the drive to the mains voltage, a time delay of minimum 40 ms is required (RCD type B).
Page 16
Non UL compliance: If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/IEC61800-5-1: In case of malfunction, not following the fuse recommendation may result in damage to the fre- quency converter.
Page 17
1 Quick Guide VLT 2800 Quick Guide Alternative fuses 380-500 V drives Buss- Buss- Buss- Buss- Buss- Buss- SIBA Little Ferraz- Ferraz- 2800 mann mann mann mann mann mann E18027 Fuse Shaw- Shaw- E52273 E4273 E4273 E4273 E4273 E4273 E81895...
VLT 2800 Quick Guide 1 Quick Guide 1.5 Programming 1.5.1 Control Unit On the front of the frequency converter there is a control panel divided into four sections. Six-digit LED display. Keys for changing parameters and shifting display function. Indicator lamps.
Page 19
1 Quick Guide VLT 2800 Quick Guide If the [STOP/RESET] key is set at Not active [0] in parameter 014 Local stop/re- set, and there is no stop command via the digital inputs or serial communication, the motor can only be stopped by disconnecting the mains voltage to the frequency converter.
Page 20
VLT 2800 Quick Guide 1 Quick Guide 1.5.7 Hand Auto During normal operation the frequency converter is in Auto mode, where the reference signal is given externally, analog or digital via the control terminals. However, in Hand mode, it is possible to give the reference signal locally via the control panel.
Page 21
1 Quick Guide VLT 2800 Quick Guide VLT 2880-2882 do not have the AMT function. Set reference range Min. reference, Ref Parameter 204 Max. reference, Ref Parameter 205 Set ramp time Ramp-up time [s] Parameter 207 Ramp-down time [s] Parameter 208...
VLT 2800 Quick Guide 1 Quick Guide 1.7 Connection Examples More examples can be found in the Operating Instructions (MG.27.AX.YY). 1.7.1 Start/Stop Start/stop using terminal 18 and coasting stop using terminal 27. Digital input Start Par. 302 Digital input Coasting Par.
Page 27
1 Quick Guide VLT 2800 Quick Guide 1.9.1 Warnings/alarm messages Description W A T Cause of Problem Live zero error (LIVE ZERO X X X Voltage or current signal on terminals 53 or 60 ERROR) is below 50% of preset value.
Page 28
VLT 2800 Quick Guide 1 Quick Guide Description W A T Cause of Problem AMT not possible Either R value is outside permitted limits, or motor current is too low on at least one phase, or the motor is too small for AMA.
VLT 2800 Quick Guide 1 Quick Guide According to international Type 2840 2855 2875 2880 2881 2882 standards Output current 32.0 37.5 INV. (3 x 380-480V) (60s) [A] 14.5 19.2 25.6 38.4 51.2 60.0 Output power (400 [KVA] 11.1 16.6 22.2...
Page 31
1 Quick Guide VLT 2800 Quick Guide Control card, digital inputs: Number of programmable digital inputs Terminal number 18, 19, 27, 29, 33 Voltage level 0 - 24 V DC (PNP positive logic) Voltage level, logic '0' < 5 V DC Voltage level, logic '1' >...
Page 32
Terminal number 70 Common for terminals 67, 68 and 69 Full galvanic isolation. See section entitled Galvanic Isolation in the Operating Instructions. For CANopen/DeviceNet units, see VLT 2800 DeviceNet manual, MG.90.BX.YY. Relay outputs: Number of programmable relay outputs Terminal number, control card (resisitvie and inductive load) 1-3 (break), 1-2 (make) Max.
1 Quick Guide VLT 2800 Quick Guide Max. cross section to control wires, rigid wire 1.5 mm /16 AWG (2 x 0.75 mm Max. cross section to control cables, flexible cable 1 mm /18 AWG Max. cross section to control cables, cable with enclosed core 0.5 mm...
Page 34
1.12.3 Derating for Low Air Pressure Above 1000 m the ambient temperature or max. output current must be derated. For altitudes above 2000 m, please contact Danfoss regarding PELV. 1.12.4 Derating for Running at Low Speeds When a motor is connected to at frequency converter, it is necessary to check that the cooling of the motor is adequate.