Delta UPS - Amplon Family
N Series, Single Phase
6/ 10 kVA Maintenance Bypass Box
for Single UPS & Parallel UPSs
Installation & Operation Quick Guide
ENGLISH
1

Product Introduction

The Maintenance Bypass Box is designed to operate in conjunction with your Delta N
series 6kVA/ 10kVA UPS. It ensures that your connected critical load continues to be
powered from the input supply during UPS maintenance or during the unlikely event of a
UPS failure.
2

Important Safety Instructions

y y
Only qualified service personnel can perform installation and maintenance of the Main-
tenance Bypass Box.
y y
The Maintenance Bypass Box must operate in conjunction with Delta N series 6kVA/
10kVA UPS. Please refer to the following table.
Maintenance
PDB1511A530035
Bypass Box Model
(for single UPS application)
UPS103N2002N009
UPS103N2004N0B0
UPS103N2004N0BA
Applicable Delta
UPS103N2004N035
N series UPS Model
UPS602N2002N009
UPS602N2004N0B0
UPS602N2004N0BA
UPS602N2004N035
y y
Before installation of the Maintenance Bypass Box, please completely turn off the UPS
and cut off the input power and battery power (if applicable).
y y
Failure to properly install the Maintenance Bypass Box may result in severe damage to
your UPS or load equipment.
y y
Please install the Maintenance Bypass Box in an indoor temperature controlled environ-
ment that is free of conductive contaminants.
y y
Do not operate the unit in extremely dusty and/ or unclean areas, locations near heating
devices, water or excessive humidity, or where the unit is exposed to direct sunlight.
y y
Select a location where provides good air circulation for the unit at all times.
y y
Properly route power cords so they cannot be walked on or damaged.
y y
The Maintenance Bypass Box must be well grounded due to a possible risk of current
leakage.
y y
The Maintenance Bypass Box is not intended for use in direct patient care or in life sup-
port applications.
www.deltapowersolutions.com
3
Package List
y y
Model PDB1511A530035_ Maintenance Bypass Box for Single UPS Application
1
No.
1
2
3
4
5
6
7
8
9
10
y y
Model PDB1512A510035_ Maintenance Bypass Box for Parallel UPSs Application
1
PDB1512A510035
(for parallel UPSs application)
UPS103N2004N0B0
UPS103N2004N0BA
UPS103N2004N035
UPS602N2004N0B0
UPS602N2004N0BA
UPS602N2004N035
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
NOTE:
1. If there is any damage or anything missing, please immediately contact the
dealer from whom you purchased the unit.
2. If the Maintenance Bypass Box needs to be returned, carefully repack the
Maintenance Bypass Box and all of the accessories using the original packing
material that came with the unit.
5013246101
2
3
4
6
8
9
7
Item
CU Terminal (Type A)
CU Terminal (Type B)
Terminal Holder
Screw for Fastener
Fastener (Type A)
Wire 1
Wire 2
Cable Tie
Screw for Terminal Holder
RS-232 Cable
2
3
4
5
6
8
10
11
12
9
Item
Heat Shrink Tube
CU Terminal (Type B)
CU Terminal (Type C)
Terminal Holder
Screw for Fastener
Fastener (Type A)
Fastener (Type B)
Wire 1
Wire 2
Cable Tie
Cable Gland
Screw for Terminal Holder
Parallel Cable
1 / 4
4
Standard Compliance
y y
IEC
y y
EN62040-1
5
5
How to Remove the Front Panel
10
PDB1511A530035
Remove the Front Panel
Q'ty
旁路
开关
BYP
ASS
SW
ITC
H
:
W
A R
O
P E
N I
,严
,会
4 PCS
A U
C A
U S
N I
G
N
N
G
:
C A
N
E
T H
O
I N
V E
T H
I S
.
O
P E
R I
Z E
D
C O
E R
R T
V E
OU
输出
N
A N
S E
D
S H
R V
R
P L
.非
TPU
断路
T
P E
O
E
I C
U
T D
A T
E
O
BRE
AKE
A T
R
E
P E
R S
W
W
N .
L
I L
R
I T
.
N
O
O
N E
N
L Y
L
ON
OFF
4 PCS
2 PCS
Pull
8 PCS
4 PCS
6
1 PCS
Front View after Front Panel Removal
1 PCS
y y
6 PCS
PDB1511A530035
2 PCS
1 PCS
1
2
7
No.
13
1
Latch (for fastening the front panel)
2
Latch (for fastening the front panel)
Bypass Switch (please remove the cover's screw shown in the
3
figure above to see the bypass switch)
Output Breaker
4
Q'ty
5
Latch (for fastening the front panel)
12 PCS
4 PCS
y y
PDB1512A510035
6 PCS
3
4 PCS
12 PCS
1
4 PCS
ON
1 PCS
OFF
2
2 PCS
U P S 2
输 出 断 路 器
U P S 2
O U T P U T B R E A K E R
2 PCS
6 PCS
No.
2 PCS
1
Latch (for fastening the front panel)
4 PCS
2
Latch (for fastening the front panel)
1 PCS
UPS2 Output Breaker
3
Continue to the Next Page
PDB1512A510035
Remove the Front Panel
B Y
旁路
PA
S S
BRE
AKE
R
ON
OFF
:
W
A R
P E
O
C A
N I
,严
,会
U S
C A
T H
A U
N
N I
E
N
G
G
T H
:
.
N
O
R I
O
P E
Z E
I N
V E
R T
I S
C O
N
D
S E
A N
V E
S H
E R
R
.非
UP
S 2
UP
D
O
R V
P E
I C
E
U
P L
A T
T D
E
S 2
O
U T
输出
R
A T
O
P E
E
N .
W
R S
W
I L
L
P U
T
断路
.
I T
O
N E
N
O
N
L Y
B R
E A
K E
L
R
ON
OFF
UP
S 1
UPS
O
U T
1
输出
P U
T
断路
B R
E A
K E
R
Pull
B Y P A S S S W I T C H
旁 路 开 关
3
输 出 断 路 器
警 告 :
O U T P U T B R E A K E R
开 起 此 盖 板 时 , 会 即 刻 关 闭 逆 变 器 输 出 . 非 授
权 合 格 人 员 , 严 禁 开 起 .
4
W A R N I N G :
O P E N I N G T H I S C O V E R P L A T E W I L L
C A U S E I N V E R T E R S H U T D O W N . O N L Y
A U T H O R I Z E D S E R V I C E P E R S O N N E L
C A N O P E N A N D O P E R A T E I T .
ON
5
OFF
Item
4
5
6
旁 路 断 路 器
B Y PA S S BREAKER
警 告 :
开 起 此 盖 板 时 , 会 即 刻 关 闭 逆 变 器 输 出 . 非
ON
授 权 合 格 人 员 , 严 禁 开 起 .
W A R N I N G :
OFF
O P E N I N G T H I S C O V E R P L A T E W I L L
C A U S E I N V E R T E R S H U T D O W N . O N L Y
A U T H O R I Z E D S E R V I C E P E R S O N N E L
C A N O P E N A N D O P E R A T E I T .
U P S 1
输 出 断 路 器
U P S 1
O U T P U T B R E A K E R
Item


Advertisement

loading
Need help?

Need help?

Do you have a question about the PDB1511A530035 and is the answer not in the manual?

Questions and answers

Summary of Contents for Delta PDB1511A530035

  • Page 1: Product Introduction

    输出 断路 器 CU Terminal (Type B) 4 PCS The Maintenance Bypass Box is designed to operate in conjunction with your Delta N 输出 断路 器 series 6kVA/ 10kVA UPS. It ensures that your connected critical load continues to be...
  • Page 2: Rear Panel

    (Right Side) on the Maintenance Bypass Box UPS2 UPS1 Bypass Breaker (please remove the cover’s screw shown in the figure above to see the bypass breaker) UPS1 UPS2 PDB1511A530035 UPS1 Output Breaker 192V dc.58 RS-2 192V dc.58 ALLE Remove the bottom of the UPS’s four screws shown in Figure 1.
  • Page 3 PDB1511A530035: PDB1512A510035 Turn on the UPS1’s INPUT BREAKER. The fans will turn on, and the UPS1 will run in bypass mode. Temperature Rating 6kVA 10kVA UPS 1 : Wire 1 x 1 & Terminal Holder x 1 & Screw x 1 Turn on the UPS2’s INPUT BREAKER.
  • Page 4: Technical Specifications

    NOTE: Under the cover plate, there is a manual bypass detector (see Figure 16) that Copyright © 2017 by Delta Electronics Inc. will be automatically activated to send the UPS a message of transferring in to All Rights Reserved. This Quick Guide is bypass mode once the cover plate is removed.