CHAPTER 3: IEC 61850 COMMUNICATION

3.5.2 Protection (Prot) logical device

The Prot logical device contains logical nodes that model protection and protection related functions.
The Prot logical device is available when the Advanced IEC 61850 option is purchased with the UR device.
3.5.2.1 Logical node zero (LLN0)
LLN0 is instantiated in all UR series devices implementing the Prot logical device.
Table 3-18: Logical node zero data objects for protection
LNName: LLN0
data obj. data attribute
Type
NamPlt
LPL
vendor
VISIBLE
STRING255
swRev
VISIBLE
STRING255
configRev
VISIBLE
STRING255
ldNs
VISIBLE
STRING255
GrRef
ORG
setSrcRef
ObjectReference

3.5.2.2 Auxiliary overvoltage element (AuxOv)

This element is instantiated in the following products: B30, C60, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
Table 3-19: Auxiliary overvoltage data objects
AuxOvPTOV#
LNName:
data attribute
data obj.
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference
3.5.2.3 Auxiliary undervoltage (AuxUv) element
This element is instantiated in the following products: C60, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
UR SERIES – COMMUNICATIONS GUIDE
LDevice inst: Prot
FC UR Name
DC
DC
DC Prot configRev
EX
SP
Prot
LDevice inst:
FC UR Name
ST AUX OV# PKP
ST
ST AUX OV# OP
ST AUX OV# DPO
SP AUX OV# BLK for group γ
SP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Logical node Prot configuration
information
Mapped to LPHD1/PhyNam.vendor
Mapped to LPHD1/PhyNam.swRev
The factory default value is the empty
string
IEC 61850-7-4:2007B
Reference to the next higher-level
logical device (LD)
In communications, the Master ldName
setting if not empty, otherwise the
concatenation of the IED name and
"Master".
In SCL, the concatenation of the IED
name and "Master".
Auxiliary Overvoltage element # functions
UR element:
Description
AUX OV# PKP operands (including individual
three phases)
0, the code for unknown. It is unknown as
the element is non-directional
AUX OV# OP operand
AUX OV# DPO operand, which is the inverse
of AUX OV PKP
AUX OV# BLK setting for setting group γ
Reference to the data attribute to input
Source GoCB of input if via GOOSE
R/W/C
R
3
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
3-37