Brivis contour Service Manual

Brivis contour Service Manual

Evaporative cooler

Advertisement

Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5
Printed 2/13/2014 11:50:17 AM
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the contour and is the answer not in the manual?

Questions and answers

Summary of Contents for Brivis contour

  • Page 1 Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 2: Table Of Contents

    Servo Seal & Drain Valve Operation 71 - 76 Trident Water Management 77 - 90 DEALING WITH PROBLEM INSTALLATIONS 91 - 95 SERVICE MAINTENANCE 96 - 100 Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 3 Introduction In August 2003 Brivis introduced the new 3 series Contour cooler and also a lesser featured contour was also introduced called the Brivis Profiler. The Brivis Profiler cooler was introduced to offer a budget model Contour to meet market demand.
  • Page 4 Brivis Advance The Brivis Advance was introduced in 2005 and is designed to take the place of the AD range of units up to Model AD56. However, the AD76 and AD86 will remain in production. In essence the Advance is a square shaped Contour/Profile, which sits upon the same base frame as the Contour/Profiler.
  • Page 5: Servicing Instructions

    N-E5 into an older model Contour. These parameters are located in the cooler service parameter section, and can only be accessed by using a Networker.
  • Page 6 N-E5 Serial Numbers - 18764 020 2021 and Beyond will have the dump delay setting in lots of 10 minutes. N-E5 - Version 9, 9a & 10 will have the dump delay setting in lots of 10 minutes. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 7 The Version 9A controllers can be identified by the marking "9A" on the box. Action: Technicians, when attending any 3 series cooler (Brivis Profiler or Contour), need to complete these steps: Identify the version of controller in the cooler and replace all N-E5 controls (version 7, 8 or 9) with the new version "9A"...
  • Page 8 Action: Service technicians are required to perform this action when attending any 3 series Contour or Profiler. This action should only be performed on 1 or 2 series Contour coolers if they exhibit the above symptoms. The installation of a modified water sensor should be carried according to the installation instructions.
  • Page 9: Servicing Instructions

    5.5 litre solenoid by a blue label that has been placed on the side of the solenoid valve body. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 10 N-E5 Networker NC-3 BWC-1 (Electronic) BWC-2 (Manual) Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 11: Contour L 23

    N-E5 Networker N-C3 BWC-2 (Manual) BWC-1 (Electronic) Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 12: Contour L 33

    N-E5 Networker N-C3 BWC-2 (Manual) BWC-1 (Electronic) Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 13: Contour L 43

    N-E5 Networker N-C3 BWC-2 (Manual) BWC-1 (Electronic) Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 14: Contour L 53

    N-E5 Networker N-C3 BWC-2 (Manual) BWC-1 (Electronic) Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 15: Contour L 63

    N-E5 Networker N-C3 BWC-2 (Manual) BWC-1 (Electronic) Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 16: Profiler P 23

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 17: Profiler P 33

    N-E5 BWC-2 (Electronic) BWC-1 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 18: Profiler P 43

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 19: Profiler P 53

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 20: Profiler P 63

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 21: Advance F 13

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 22: Advance F 23

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 23: Advance F 33

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 24: Advance F 43

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 25: Advance F 53

    N-E5 BWC-1 (Electronic) BWC-2 (Manual) Networker N-C3 Water Connection Flexible Hose Connection with 1/2" BSP (Male) Thread Drain Connection 40 mm PVC Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 26: Motor Circuit Diagrams

    Motor Circuit Diagram MOTOR WIRING CIRCUIT DIAGRAM BETTS 855 BNVA - A12 MOTOR - 315 WATT DIRECT WIRED CAPACITOR 8 u/F Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 27: Motor Circuit Diagrams

    Motor Circuit Diagram MOTOR - 750 WATT DIRECT WIRED BETTS MODEL - 808855BQVA - A22V CAPACITOR 25 u/F Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 28 Circuit Wiring Diagram Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 29 If these two pairs of terminals are mixed around the Networker will not function. Networker If the Cooler is integrated with a Brivis MPS or Auto EMS heater(s), then simply connect the wiring in parallel with the heater's circuit to the Networker.
  • Page 30 Networker, using the instructions on page 24. Networker Cooler No. 1 Cooler No. 2 Cooler No. 3 Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 31 Repeat the sequence for each Cooler, then follow the Networker Advanced • Programming instructions to allocate the Coolers to their respective Networker zones. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 32: Installing Dual Networkers

    Evap ID No. n01 ID34:0 Not Used n01 ID35:0 Not Used n01 ID30:0 Evap Zone B, Networker Temp Sense Networker ID No . Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 33: Installing Dual Networkers

    Using the rotary dial, change the parameter value to 2 (2=Slave). • Push the On/Off key to exit. • The unit should then be ready for zone configuration. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 34 If this has been done, the resetting procedure needs to be performed again to rectify this problem. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 35: Networker Installer Parameters

    Evap Zone D - Networker Temp Sense Heating OFF cycle Circulation Fan Operation 0 = OFF or 1 = ON n01 ID43:0 Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 36: Cooler Service Parameters

    Time increment of either; seconds, minutes or hours. • RPM. • Numerical number where 0 = OFF & 1 or above = ON. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 37 Contour 1 series = 60 sec Contour 2 series = 200 sec Contour 3 series = 200 sec Profiler series = 200 sec Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 38 Servoseal, then close the Servoseal and wait for the usual dump time to elapse before opening the Servoseal again and performing the normal start up procedure. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 39 Aquasave is wired directly into the N-E5 base connector. The parameter settings are 1=Aquasave present, 0=No Aquasave. Flush Time - The time the solenoid is open during a flush service operation. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 40: General Operation

    The automatic Pre-wetting time of the dried filter pads, will depend on how long the Cooler's pump has been OFF, as follows: Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 41: General Operation

    ServoSeal motor, which will drain the trough and close the dropper duct damper seal (Note: damper not present on Profiler coolers). Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 42 ServoSeal, water fill and Pre-wet operations. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 43 NOTE: Should the pump be turned ON whilst the fan is operating, then the fan will be forced OFF for the Pre-wet period, then come back ON again automatically. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 44 (new) operation can be performed i.e. Networker turned back ON again. The Cooler then remains idle until the Networker is turned ON again, and calls for cooling. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 45 ServoSeal Closes 15 seconds Delay = 45 seconds (WashWaitTime) Water Inlet Valve opens 30 seconds (WashTime) Delay = 45 seconds Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 46: Flush Service

    The action of the fresh water entering, mixing and overflowing out from the tank, dilutes the salt and sediment ratio back to the original supply water condition. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 47: Aquasave Operation

    There air then passes through a tube to the diffuser ball which should be submerged beneath the water. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 48 Networker sent on a 2 wire bus network. The N-E5 will communicate with the Networker about the status of the Cooler's operation, including malfunction errors. The N-E5 can be fitted to any 3 series Contour and Profiler Cooler models, but will require configuring to the model type, using the service parameters accessed through the Networker.
  • Page 49 ServoSeal / drain valve motor circuit. The N-E5 controller will maintain a minimum voltage on the output to the water inlet solenoid in the OFF cycle. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 50 Check the water inlet solenoid and wiring loom for short circuit. • Check the fan motor and wiring loom for short circuit. • Replace 8 Amp fuse and re test. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 51: Fan Operation

    Other service adjustments can be made within the Model No. range, and are discussed in the section regarding special adjustments using the Networker. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 52 Networker (where available). If the condition rectifies itself, and the speed sensor signal is restored, then the Cooler will resume normal fan operation. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 53 • Check the motor capacitor - replace and retest. • Check the N-E5 is not faulty - replace and re test. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 54 If the fan is operating in FAN_LIMP mode, then the DC brake will not be applied. Allow for the 4 minute delay period to register the error on the Networker, before the DC brake is disabled. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 55 Check the motor is not HOT and the thermal over load switch is not open circuit. • Check the incoming power supply is ON and is the correct polarity. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 56 (max fan speed selected). Replace capacitor and test again. • Replace fan motor. • VOLTS MOTOR/COMMON-BLUE 10 A MOTOR/START-BLACK 1000V- - - 750V FUSED Multimeter Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 57 Check that the ServoSeal has been driven open, indicating Networker signal • operating correctly. If ServoSeal not open Replace Networker and test again. • If motor doesn't run: Replace motor. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 58 Cooler Operation (cont.) Fan Operation (cont.) Fan Motor will not operate - Flowchart Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 59: Fan Operation

    Lower fan motor down and out of the mounting bracket. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 60: Pump Operation

    Slide the winding and lamination plate assembly up and off the pump housing • centre. Slide the winding coil out from the lamination plates. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 61 Check for 240 Volt output to the pump, at the PUMP-NEUTRAL and PUMP- • ACTIVE terminals on the pump. VOLTS PUMP - NEUTRAL 10 A 1000V- - - 750V FUSED PUMP - ACTIVE Multimeter Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 62 10 A 1000V- - - 750V FUSED PUMP - ACTIVE Multimeter If pump doesn't operate: Refer to mechanical checks. • Replace pump. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 63 10 A 1000V- - - 750V FUSED Multimeter PUMP - ACTIVE If pump doesn't operate: Refer to mechanical checks. • Replace pump. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 64 Check the pump impellor is not damaged, and can rotate within the upper pump • housing. Replace upper pump housing assembly, if impellor damaged or jammed. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 65: Pump Operation

    Replace upper pump internal 8 amp housing assembly if fuse is not open Replace the impellor is damaged circuit N-E5 and re-test Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 66: Water Inlet Solenoid Operation

    (cont.) Water Inlet Solenoid Operation The Contour Cooler has a 240 Volt water inlet solenoid on the under side of the base, at the high side of the roof. The water inlet solenoid has a flexible hose attached with a filter inserted in the hose connections at each end.
  • Page 67 SOLENOID-ACTIVE and INLET SOLENOID-NEUTRAL terminals, on the service compartment back wall. INLET VALVE - NEUTRAL VOLTS 10 A 1000V- - - 750V FUSED INLET VALVE - ACTIVE Multimeter Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 68 1000V- - - 750V FUSED Multimeter INLET VALVE - ACTIVE Check if the water inlet solenoid is blocked. • Replace water inlet solenoid. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 69 If water inlet solenoid doesn't operate: Check wiring terminals & loom. • Check water inlet solenoid is not blocked or jammed. • Replace water inlet solenoid. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 70: Water Inlet Solenoid Operation

    If no power: Check the water inlet solenoid has not blocked or jammed open. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 71: Servo Seal & Drain Valve Operation

    Cooler Operation (cont.) ServoSeal and Drain Valve Operation Contour and Profiler Coolers have a new and unique mechanism, to drain and empty the Cooler's tank and simultaneously close off the duct (Contours only), at the end of use. The ServoSeal is a set of adjustable louvers constructed in the Contour's base, which are driven closed and prevent heat loss from the building, when the unit is not in use.
  • Page 72 Manoeuvre the linkage arms through the service compartment back wall opening, • and remove assembly. Disconnect motor cam lever switch. • Disconnect linkage arm and cam shaft. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 73 Check the MOTOR/MICRO-SWITCH cam shaft is not damaged. • Replace the faulty motor micro switch. • MOTOR/MICRO-SWITCH VOLTS MAINS ACTIVE-IN 10 A 1000V- - - 750V FUSED Multimeter MOTOR-ACTIVE Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 74 Check linkages are free moving and not jammed. • Check gear linkage mechanism is not jammed. • Replace gear linkage mechanism. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 75 Replace N-E5 module and re test. • If ServoSeal / drain valve motor doesn't operate: Remove motor from gear linkage mechanism and re-test. • Replace motor. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 76: Servo Seal & Drain Valve Operation

    Follow check procedures as above for ServoSeal will not open / drain close, with • power test to Active Close terminal on ServoSeal motor and switch. Circuit Diagram: Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 77: Trident Water Management

    Trident Water Management System The Contour Cooler's tank water level is regulated, by turning ON and OFF the water inlet solenoid as required, according to the operating conditions. After the initial filling, at which point the water inlet solenoid turns OFF, the Cooler looses tank water volume due to evaporation, in the normal course of the unit's operation.
  • Page 78 As the water level control probes will be constantly subjected to water and electrical power during normal operation, it is expected that a coating will eventuate, depending on the water quality. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 79 Error 50 is different and will cause a lockout, but provides the user the facility to reset the operation at the Networker. However, if the condition is still present after reset, the unit will lockout again. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 80 Water inlet solenoid is timed OFF for 90 seconds, then refills to High Water Level • Sensor again. To rectify this condition, refer to Service Checks on page 73. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 81 Water inlet solenoid timed to fill for 70 seconds, then closes again. • To rectify this condition, refer to Service Checks section. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 82 Even if the closed circuit on the water sensors has cleared by the next start up of • the cooler, this error remains current until it completes a successful shut down without this error condition. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 83 This condition will not harm the pump, but will result in poor and inadequate cooling performance. To rectify this condition, refer to Service Checks section. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 84 This condition will not harm the pump, but will result in poor and inadequate cooling performance. To rectify this condition, refer to Service Checks on page 73. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 85 Check the N-E5 8 Amp fuse is not open circuit. • Check for N-E5 PCB track fracture adjacent Trident plug connection (may be • intermittent). Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 86 Check for coating on the Water Sensor probes preventing circuit. • Check for high water quality (not able to make circuit - refer to Brivis). • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 87 NETWORKER CONNECTION POINT WATER LEVEL CONTROL LOOM High Water Level Common Sensor Low Water level High Water Sensor Pin Common Plastic Guide Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 88 NETWORKER CONNECTION POINT WATER LEVEL CONTROL LOOM High Water Level Common Sensor Low Water level Low Water Common Sensor Pin Plastic Guide Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 89 Check in the N-E5 is a 10 Volt output to the water inlet solenoid in the OFF cycle. • Check the water inlet pressure is within 300 - 1000 kPa. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 90: Trident Water Management

    Disconnect the water level sensor loom from the N-E5. • Remove the 2 retaining nuts at the top of the probe assembly and remove. • Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 91: Dealing With Problem Installations

    L 43 & P 43 2000 - 2750 L 53 & P 53 2400 - 3200 L 63 & P 63 2900 - 3600 Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 92 Cooler's maximum output (midway between the minimum and maximum Output Selection figure), then the duct and outlet sizes should be increased to meet this level. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 93 Check the duct and fittings are insulated. • Check the Cooler is not transferring excessive vibration onto the dropper duct of • the buildings structure. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 94 L 43 & L53 P 43 & P53 2.3 m 2 1.4 m 2 L63 & P63 2.8 m 2 1.7m 2 Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 95: Dealing With Problem Installations

    Check the route of any water discharge from the Cooler i.e. roof guttering and • water run off area down stream of Cooler. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 96: Service Maintenance

    Service Maintenance Pre Season Maintenance The service to a Contour Cooler requires access to the home to check the performance of the unit through the duct system and the function of the wall control. Service work performed without access cannot be responsible for the system operation, only the Coolers function.
  • Page 97 Check the fan motor varies through the entire range. Check the minimum and maximum RPM setting are appropriate for the duct installation. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 98 Check the Networker wall control is located in a suitable position for correct operation. Check the Coolers Pre Wet function is operating correctly. Check the unit operates in both Manual and Auto modes. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 99 Operate the pump for 5 minutes to rinse the pads and drain again. Refill the tank with clean water, operate the pump for 5 minutes to rinse the pads and drain again to complete. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...
  • Page 100: Service Maintenance

    Push the bushes out of the distribution tray. Separate the roof outer and the inner distribution tray. Clean the components and reassemble. Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM...

This manual is also suitable for:

AdvanceProfiler

Table of Contents

Save PDF