The drive and the chopper will withstand this continuous braking power. The braking is considered continuous if the
brcont
braking time exceeds 30 s.
Note: Check that the braking energy transmitted to the specified resistor(s) in 400 seconds does not exceed
E
.
R
R
Resistance value for the listed resistor assembly. Note: This is also the minimum allowed resistance for the brake
resistor.
E
Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor
R
element from 40 °C (104 °F) to the maximum allowable temperature.
P
Continuous power (heat) dissipation of the resistor when placed correctly. Energy E
Rcont
1)
22 kW with standard 22 ohm resistor and 33 kW with 32...37 ohm resistor
All braking resistors must be installed outside the converter module. The SACE brake resistors are built in an IP 21 metal
housing. The SAFUR brake resistors are built in an IP 00 metal frame. Note: The SACE and SAFUR resistors are not UL
listed
Resistor braking
Braking power
Brake resistor(s)
of the chopper
and the drive
P
Type
brcont
(kW)
8
SACE08RE44
11
SACE08RE44
16
SACE08RE44
22
SACE08RE44
28
SACE15RE22
1)
22/33
SACE15RE22
45
SACE15RE13
56
SACE15RE13
68
SAFUR90F575
83
SAFUR90F575
113
SAFUR80F500
160
SAFUR80F500
160
SAFUR80F500
160
SAFUR80F500
R
E
P
R
(ohm)
(kJ)
(kW)
44
210
1
44
210
1
44
210
1
44
210
1
22
420
2
22
420
2
13
435
2
13
435
2
8
1800
4.5
8
1800
4.5
6
2400
6
6
2400
6
6
2400
6
6
2400
6
PDM code 00096931-J
dissipates in 400 seconds.