Setting
Screen Display
BACKWASH TIME
Backwash
10
Time
MINUTES
BRINE DRAW-RINSE
Brine
60
Draw-
Rinse
MINUTES
FAST RINSE-TIME
Fast Rinse-
10
Time
MINUTES
Fill Time
FILL TIME
377
SECONDS
2)MANUAL MODE
3)SET DATE/TIME
4)ACCESSORIES
>5)ADV. SETUP
Regeneration Triggers Setup
Default values are shown for each selection.
SOFTENING
JAN-01-10 12:01P
2)MANUAL MODE
3)SET DATE/TIME
4)ACCESSORIES
>5)ADV. SETUP
1)SYSTEM SETUP
2)REGEN SETUP
>3)CYCLE TIMES
4)REGENTRIGGER
26
Culligan® Smart Controller (GBE) for Softeners and Filters
Range
Use this setting to adjust the number of minutes for backwash.
0–150
The default setting is 10 minutes. You generally will not need
to change this setting. Press
The screen displays the brine draw-rinse setting. For com-
mercial softener applications this value should be 60 minutes.
0–150
Press
is not properly rinsing out within this duration.
This value is displayed as Fast Rinse-Time for five-cycle
valves and Fill Time for four-cycle valves. The value is calculat-
ed for household units based on input parameters.
0–150
For commercial units, press
10 minutes.
The screen displays the fill time setting if a 5-cycle valve is
0–9000
selected, based on the salt dosage. Find this value in the
unit's installation manual. For example, if you have a Hi-Flo 22
WS-90 water softener (3 ft³) and you want to set a capacity of
60,000 grains, the chart in Appendix A of the Hi-Flo 22 manual
shows a time setting of 12 minutes. For a 4-cycle valve, the
refill is controlled by AUX OUTPUT 2; set the refill time there.
See page 48.
For filters, Press
5.
The cycle times setup is complete. The screen displays the advanced setup menu.
Press
to display the home screen.
1.
From the HOME scrren, press
2.
The screen displays the main menu. Press
SETUP.
3.
The screen displays the advanced setup menu. The menu includes SYSTEM SET-
UP, REGEN SETUP, CYCLE TIMES, and REGENTRIGGER.
4.
Press
to select 4)REGENTRIGGER.
Changing the Setting
or
and then
to keep the default setting, one (1) minute.
NOTE
This time is displayed in seconds. For exam-
ple, If you entered 12 minutes during FTS, then
this will display 720 seconds.
to view the main menu.
26
to view the next setting.
to extend the time if the brine
to keep the default setting of
to select 5)ADV.
Cat. No. 01021161
Need help?
Do you have a question about the Smart Controller (GBE) and is the answer not in the manual?
Questions and answers