Overload Circuit Protector Adjustment and Setting

The trip threshold of the OCP is set to the lowest setting when the product ships from the factory. The
OCP setting should allow for the high inrush current of startup and the short-time overload current of
high-inertia loads and not be set so high as to provide inadequate overcurrent protection. The OCP
should be set to a level that is just above the maximum level of the application's normal operating
requirements.
A motor starter is recommended for larger motors.
Overload settings are application-specific and should be set and/or adjusted by Qualified Personnel
ONLY (see
Figure 4. Motor OCP Adjustment and OCP Contactor.
Set to minimum at the factory.
Application-specific
adjustment is required.
Q9 FlowSaver Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Qualified Personnel on pg.
The Normally Open (NO) and the Normally Closed (NC) contacts remain
in their normal states during normal operation. Both contacts change
states during an overload trip.
The contacts may be used with ancillary circuitry to annunciate an
overload trip or to control other system features.
3).