1. CHARACTERISTICS
4 different programs for each day of the week (28 different ranges and
temperatures altogether). Time programming with 10 minutes accuracy.
Designed to operate in heating or air conditioning systems.
Temperature measurement range: 0-50 °C, resolution of 0.1 °C.
Temperature control range: 5-45 °C, resolution 0.2 °C.
Hysteresis selectable from 0.5 / 1.0 / 2.0 / 4.0 °C.
PI - system for heating curve optimization.
Sensor calibration: from -4.0 °C to 4.0 °C, step 0.2 °C.
Program copy function.
Large, clear backlit display.
Temporary temperature change - the controller instantaneously maintains the
preset temperature until the next program starts.
Holiday mode - the controller maintains the preset temperature for a selected
time up to 99 days.
Settings lock - the option to change parameters is blocked. This mode is intended
for offices where only 1 person is entitled to change the settings.
No heating, i.e. the Anti-freeze mode - the mode of heating in which the
controller maintains the lowest possible and safe temperature (5 °C); in air
conditioning mode the cooling device is disabled.
Operating time counter of the heating / air conditioning device - maximum
indication 999 hours, with a resolution of 1 minute.
Ant-freeze protection - the controller turns heating on when the temperature
drops below 5 °C. This function is always active.
Power supply: 2 AA alkaline batteries.
Output load: 16 A 230 V AC, 1-pole changeover relay.
External temperature sensor - NTC 10kΩ at 25 °C.
Automatic switch between summer and winter time.
Anti-stop system - the relay is switched on for 1 minute once a week.
Dimensions (L / H / W.): 132.5 x 85 x 27.6 mm.
CE declaration of conformity is available on the website
EUROSTER 2026/2026TX
http://www.euroster.com.pl
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the 2026 and is the answer not in the manual?

Questions and answers

Summary of Contents for EUROSTER 2026

  • Page 1 EUROSTER 2026/2026TX - User Manual EUROSTER 2026/2026TX 1. CHARACTERISTICS • 4 different programs for each day of the week (28 different ranges and temperatures altogether). Time programming with 10 minutes accuracy. • Designed to operate in heating or air conditioning systems.
  • Page 2 EUROSTER 2026/2026TX - User Manual 2. PROPER PLACE FOR INSTALLATION To ensure fully efficient controller operation, please observe the following recommendations regarding the placement of the device. 1. The controller is designed for indoor wall mounting at a height of about 1.5 m above the floor.
  • Page 3 EUROSTER 2026/2026TX - User Manual Note: Upon changing any value the corresponding item on the display starts blinking. This should be understood as a request for confirmation. If the users approves the change with the confirmation button, it will be stored. If not confirmed within 15 seconds, the controller cancels the changes and returns to normal operation.
  • Page 4 To avoid negative surprises, it is recommended to replace the batteries each year before the heating season begins. 5. CONTROLLER MODE SELECTION Euroster 2026 is equipped with 4 configuration jumpers. Factory settings are indicated in italics: Installation Type: Air Condition / Heating Jumper used to select the type of installation, in which the regulator is used.
  • Page 5: Controller Wiring Diagram

    EUROSTER 2026/2026TX - User Manual 6. CONTROLLER WIRING DIAGRAM In a system with a gas boiler In an underfloor heating system NOTE. If you use a floor sensor, connect it to the terminals 4 and 5. The SENSOR jumper should also be put in the Ext position (batteries should be taken out during this procedure).
  • Page 6 The idea behind the regulator’s operation with hysteresis is presented below: Algorithm optimizing the heating curve (PI) The controller 2026 can operate using an algorithm optimizing the heating curve. This algorithm is intended for installations with water underfloor heating. Its aim is to minimize room temperature fluctuations.
  • Page 7 15 seconds to cancel the change. 8. CONTROLLER’S OPERATION Euroster 2026 is a programmable regulator. The user can set up 4 different temperatures for 4 different intervals of time, for each day of the week separately. Setting up programs for the entire week can be laborious;...
  • Page 8 EUROSTER 2026/2026TX - User Manual Programming the controller Note: The order of weekdays is irrelevant during programming. Set the knob at PN position. Set the desired temperature for P1 with the keys . Confirm with the Set the required start time for P1 with the keys .Confirm with the key...
  • Page 9 EUROSTER 2026/2026TX - User Manual Press to copy the program. Digit 4 stops flashing. Similarly, set knob at Friday and then press ; program will be copied. Set the knob in the START position. The controller will begin to operate normally.
  • Page 10 EUROSTER 2026/2026TX - User Manual Designation of hours / days If specified time is expressed in hours, the letter "h" is displayed after the number; if in days - the display shows "d" and word "Date" appears above the number on the right.
  • Page 11 EUROSTER 2026/2026TX - User Manual Checking the operating time The controller has a function for counting of operating time of the regulated device. It is intended to determine the date of maintenance or for cost estimation. The maximum counted value is 999:59. The counter stops after reaching this value.
  • Page 12: General Description

    With the EUROSTER TXRX controller the signal is transmitted wirelessly by radio, eliminating the need for wiring between the controller EUROSTER TX, and the device controlled by the receiver EUROSTER RX. The effective range of operation depends to a large extent on the materials of which the building is made.
  • Page 13: Operation

    EUROSTER TX sends every minute a short coded message confirming the status of the relay of the EUROSTER RX receiver. It is indicated by lighting of the green LED for about 1 second. For this reason, the indicator of the controller can light up earlier than the control device is turned on.
  • Page 14 EUROSTER 2026/2026TX - User Manual buildings, this is not significant to the economy of regulation and has no effect on the cost of heating. An electrical, oil or gas appliance, consuming more power than the maximum load of contacts, can be connected only through an external relay with appropriate characteristics.
  • Page 15 EUROSTER 2026/2026TX - User Manual With a gas boiler 1. Electrical connector cube Output wire, contacts used COM - NO - (normally open) 3. Antenna 4. Euroster RX (receiver) Euroster TX placed in any room With a CH pump 7. EUROSTER TX (transmitter) Central heating boiler 8.
  • Page 16 TXRX series products meet the EU directives: R & TTE CE declaration of conformity is published and available on the website: www.euroster.com.pl In case of a complaint the complete EUROSTER TXRX must be supplied to the point of sale with the warranty card. 9. SET CONTENTS...