Real Time Event Monitoring:

All events listed below in figure 1.2 are real time and can be viewed in Modbus register 40002. Figure 1.2 depicts the 16 bit
breakdown and cross reference. This is not to be confused with the historical event log.
Description
Bit 0 'Switch In Auto'
Bit 1 'System Fault'
Bit 2 'Engine Running'
Bit 3 'Battery Fault'
Bit 4 'Charger Failure'
Bit 5 'Failed To Start'
Bit 6 'AC Power Failure'
Bit 7 'Low Oil Pressure'
Bit 8 'High Water Temperature'
Bit 9 'Low Fuel Level'
Bit 10 'Pump On Demand'
Bit 11 'Engine Overspeed'
Bit 12 'Engine Quit'
Bit 13 'Low Discharge Pressure'
Bit 14 'Engine Fuel Solenoid On'
Bit 15 'High Discharge Pressure'
Description
Bit 0 'Pressure Transducer Fault'
Bit 1 'Low Intake'
Bit 2 'Switch in Manual'
Bit 3 'Switch in Off'
Bit 4 'Battery 1 Failure'
Bit 5 'Battery 2 Failure'
Bit 6 'Charger 1 Failure'
Bit 7 'Charger 2 Failure'
Bit 8 'Pressure Drop'
Bit 9 'Engine Auto Available'
Bit 10 'Contactor Coil Failure'
Bit 11 'Test Running'
Bit 12 'Hi/Low Zone'
Bit 13 'Contactor Coil 1 Failure'
Bit 14 'Contactor Coil 2 Failure'
Bit 15 'Weekly Test Due'
Description
Bit 0 'Dump Valve'
Bit 1 'Engine Lockout'
Bit 2 'Stop Push button'
Bit 3 'SD Card Missing'
Bit 4 'Reset button'
Bit 5 'OID LED 13'
Bit 6 'OID LED 14'
Bit 7 'OID LED 15'
Bit 8 'OID LED 16'
Bit 9 'OID LED 17'
Bit 10 'OID LED 18'
Bit 11 'OID LED 19'
Bit 12 'OID LED 20'
Bit 13 'OID LED 21'
Bit 14 'OID LED 22'
Bit 15 'OID LED 23'
Description
Bit 0 'R1'
Bit 1 'R2'
Bit 2 'R3'
Bit 3 'R4'
Bit 4 'R5'
Bit 5 'R6'
Bit 6 'R7'
Bit 7 'R8'
Bit 8 'R9'
Bit 9 'R10'
Bit 10 'R11'
Bit 11 'R12'
Bit 12 'R13'
Bit 13 'R14'
Bit 14 'R15'
Bit 15 'R16'
Description
Bit 0 'R17'
Bit 1 'R18'
Bit 2 'R19'
Bit 3 'R20'
Bit 4 'R21'
Bit 5 'R22'
Bit 6 'R23'
Bit 7 'R24'
Bit 8 'Auto Test'
Bit 9 'Cranking'
Bit 10 'Start by remote'
Bit 11 'Remote Start Input'
Bit 12 'Remote Start'
Bit 13 'Shutdown in test'
Bit 14
Bit 15
Modbus Registers
040002:0
Bit 0 Of Modbus Register 040002 - Indicates the 'Switch In Auto' Event
040002:1
Bit 1 Of Modbus Register 040002 - Indicates The 'System Fault' Event
040002:2
Bit 2 Of Modbus Register 040002 - Indicates The 'Engine Running' Event
040002:3
Bit 3 Of Modbus Register 040002 - Indicates The 'Batter Fault' Event
040002:4
Bit 4 Of Modbus Register 040002 - Indicates The ''Charger Failure' Event
040002:5
Bit 5 Of Modbus Register 040002 - Indicates The 'Failed To Start' Event
040002:6
Bit 6 Of Modbus Register 040002 - Indicates The 'AC Power Failure' Event
040002:7
Bit 7 Of Modbus Register 040002 - Indicates the 'Low Oil Pressure' Event
040002:8
Bit 8 Of Modbus Register 040002 - Indicates The 'High Water Temperature' Event
040002:9
Bit 9 Of Modbus Register 040002 - Indicates The 'Low Fuel Level' Event
040002:10
Bit 10 Of Modbus Register 040002 - Indicates The 'Pump On Demand' Event
040002:11
Bit 11 Of Modbus Register 040002 - Indicates The 'Engine Overspeed' Event
040002:12
Bit 12 Of Modbus Register 040002 - Indicates The 'Engine Quit' Event
040002:13
Bit 13 Of Modbus Register 040002 - Indicates A 'Low Discharge Pressure' Event
040002:14
Bit 14 Of Modbus Register 040002 - Indicates A 'Engine Fuel Solenoid On' Event
040002:15
Bit 15 Of Modbus Register 040002 - Indicates A 'High Discharge Pressure' Event
**All Data In Modbus Register 40002 Is Real Time**
Modbus Registers
040003:0
Bit 0 Of Modbus Register 040003 - Indicates the 'Pressure Transducer Fault' Event
040003:1
Bit 1 Of Modbus Register 040003 - Indicates The 'Low Intake' Event
040003:2
Bit 2 Of Modbus Register 040003 - Indicates The 'Switch in Manual' Event
040003:3
Bit 3 Of Modbus Register 040003 - Indicates 'Switch in Off' Event
040003:4
Bit 4 Of Modbus Register 040003 - Indicates The 'Battery 1 Failure' Event
040003:5
Bit 5 Of Modbus Register 040003 - Indicates The 'Battery 2 Failure' Event
040003:6
Bit 6 Of Modbus Register 040003 - Indicates The 'Charger 1 Failure' Event
040003:7
Bit 7 Of Modbus Register 040003 - Indicates The 'Charger 2 Failure' Event
040003:8
Bit 8 Of Modbus Register 040003 - Indicates The 'Pressure Drop' Event
040003:9
Bit 9 Of Modbus Register 040003 - Indicates The 'Engine Auto Start Available' Event
040003:10
Bit 10 Of Modbus Register 040003 - Indicates The 'Common Contactor Coil Failure' Event
040003:11
Bit 11 Of Modbus Register 040003 - Indicates The 'Engine Running in Test Mode' Event
040003:12
Bit 12 Of Modbus Register 040003 - Indicates The 'High/Low Zone Event
040003:13
Bit 13 Of Modbus Register 040003 - Indicates A 'Contactor Coil 1 Failure' Event
040003:14
Bit 14 Of Modbus Register 040003 - Indicates A 'Contactor Coil 2 Failure' Event
040003:15
Bit 15 Of Modbus Register 040003 - Indicates A 'Weekly Test Due' Event
**All Data In Modbus Register 40003 Is Real Time**
Modbus Registers
040004:0
Bit 0 Of Modbus Register 040004 - Indicates 'Dump Valve On' Event
040004:1
Bit 1 Of Modbus Register 040004 - Indicates 'Engine Lockout' Input
040004:2
Bit 2 Of Modbus Register 040004 - Indicates 'Stop push button pressed' Event
040004:3
Bit 3 Of Modbus Register 040004 - Indicates ' SD Card Missing' Event
040004:4
Bit 4 Of Modbus Register 040004 - Indicates 'Reset push button pressed' Event
040004:5
Bit 5 Of Modbus Register 040004 - Indicates 'OID Lamp 13 on'
040004:6
Bit 6 Of Modbus Register 040004 - Indicates 'OID Lamp 14 on'
040004:7
Bit 7 Of Modbus Register 040004 - Indicates 'OID Lamp 15 on/ECM Failure'
040004:8
Bit 8 Of Modbus Register 040004 - Indicates 'OID Lamp 16 on/EMC Warning'
040004:9
Bit 9 Of Modbus Register 040004 - Indicates 'OID Lamp 17 on/ECM Switch in Alt.'
040004:10
Bit 10 Of Modbus Register 040004 - Indicates 'OID Lamp 18 on/Fuel Injection Fault'
040004:11
Bit 11 Of Modbus Register 040004 - Indicates 'OID Lamp 19 on/Fual Tank Leak'
040004:12
Bit 12 Of Modbus Register 040004 - Indicates 'OID Lamp 20 on/Clogged Water Strainer'
040004:13
Bit 13 Of Modbus Register 040004 - Indicates 'OID Lamp 21 on/High Cooling Water Temp.'
040004:14
Bit 14 Of Modbus Register 040004 - Indicates 'OID Lamp 22 on/Low Engine Temp.'
040004:15
Bit 15 Of Modbus Register 040004 - Indicates 'OID Lamp 23 on/Contactor Coil Failure'
**All Data In Modbus Register 40004 Is Real Time**
Modbus Registers
040005:0
Bit 0 Of Modbus Register 040005 - Indicates 'Relay 1 On'
040005:1
Bit 1 Of Modbus Register 040005 - Indicates 'Relay 2 On'
040005:2
Bit 2 Of Modbus Register 040005 - Indicates 'Relay 3 On'
040005:3
Bit 3 Of Modbus Register 040005 - Indicates 'Relay 4 On' - Horn
040005:4
Bit 4 Of Modbus Register 040005 - Indicates ' Relay 5 On' - Drain Solenoid
040005:5
Bit 5 Of Modbus Register 040005 - Indicates 'Relay 6 On' - Engine Fuel Solenoid
040005:6
Bit 6 Of Modbus Register 040005 - Indicates 'Relay 7 On' - Engine Stop Solenoid
040005:7
Bit 7 Of Modbus Register 040005 - Indicates 'Relay 8 On'
040005:8
Bit 8 Of Modbus Register 040005 - Indicates 'Relay 9 On' - System Fault (US mode)
040005:9
Bit 9 Of Modbus Register 040005 - Indicates 'Relay 10 On' - Engine Running (US mode)
040005:10
Bit 10 Of Modbus Register 040005 - Indicates 'Relay 11 On'
040005:11
Bit 11 Of Modbus Register 040005 - Indicates 'Relay 12 On' Auto mode on (EU Mode)
040005:12
Bit 12 Of Modbus Register 040005 - Indicates 'Relay 13 On'
040005:13
Bit 13 Of Modbus Register 040005 - Indicates 'Relay 14 On' Engine running (EU Mode)
040005:14
Bit 14 Of Modbus Register 040005 - Indicates 'Relay 15 On' Engine running (EU Mode)
040005:15
Bit 15 Of Modbus Register 040005 - Indicates 'Relay 16 On' Pump on demand (EU Mode)
**All Data In Modbus Register 040005 Is Real Time**
Modbus Registers
040006:0
Bit 0 Of Modbus Register 040006 - Indicates 'Relay 17 On' Failed to start (EU Mode)
040006:1
Bit 1 Of Modbus Register 040006 - Indicates 'Relay 18 On' System Fault (EU Mode)
040006:2
Bit 2 Of Modbus Register 040006 - Indicates 'Relay 19 On'
040006:3
Bit 3 Of Modbus Register 040006 - Indicates 'Relay 20 On'
040006:4
Bit 4 Of Modbus Register 040006 - Indicates ' Relay 21 On'
040006:5
Bit 5 Of Modbus Register 040006 - Indicates 'Relay 22 On'
040006:6
Bit 6 Of Modbus Register 040006 - Indicates 'Relay 23 On'
040006:7
Bit 7 Of Modbus Register 040006 - Indicates 'Relay 24 On'
040006:8
Bit 8 Of Modbus Register 040006 - Indicates 'Test mode initiated but not running'
040006:9
Bit 9 Of Modbus Register 040006 - Indicates 'Cranking engine'
040006:10
Bit 10 Of Modbus Register 040006 - Indicates 'Engine started running after remote start'
040006:11
Bit 11 Of Modbus Register 040006 - Indicates 'Remote start input present'
040006:12
Bit 12 Of Modbus Register 040006 - Indicates 'Remote start was received'
040006:13
Bit 13 Of Modbus Register 040006 - Indicates 'Engine stopped during test run due to alarm'
040006:14
Bit 14 Of Modbus Register 040006 - NOT USED
040006:15
Bit 15 Of Modbus Register 040006 - NOT USED
**All Data In Modbus Register 040006 Is Real Time**
Figure 1.2
Page 30 of 34
File Name: Doc#586p.docx
Usage Notes For Read Only Registers
Usage Notes For Read Only Registers
Usage Notes For Read Only Registers
Usage Notes For Read Only Registers
Usage Notes For Read Only Registers