2.2 SPECIFICATIONS
ETHERNET SWITCH (HIGH VOLTAGE, TYPE 2S)
Nominal DC voltage:
Minimum DC voltage:
Maximum DC voltage:
Input Current:
Nominal AC voltage:
2
Minimum AC voltage:
Maximum AC voltage:
Internal fuse:
GPM-F MODULE CONTACT INPUTS
Internal wetting:
Input comparator threshold: 6 V DC
External contact:
Current when energized: < 10 mA
Debounce time:
GPM-F MODULE CRITICAL FAILURE RELAY
Make and carry:
Continuous carry:
Break (DC inductive, L/R = 40 ms): 1 A at 24 V, 0.5 A at 48 V,
Operate time:
Contact material:
GPM-F MODULE POWER SUPPLY
GPM-F-L:
GPM-F-HM:
2-20
110 to 240 V DC
88 V DC
300 V DC
0.9 A DC maximum
100 to 240 V AC, 0.26 to 0.16 A/26 to 39
VA at 50/60 Hz
85 V AC, 0.31 A/22 VA at 50/60 Hz
265 V AC, 0.16 A/42 VA at 50/60 Hz
3 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 003
24 V DC
dry
10 ms
30 A for 0.2 s as per ANSI C37.90
8 A
0.3 A at 125 V, 0.2 A at 250 V
< 8 ms
silver alloy
100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
G60 Generator Protection System
2 PRODUCT DESCRIPTION
ETHERNET SWITCH (LOW VOLTAGE, TYPE 2T)
Nominal voltage:
48 V DC, 0.31 A/15 W
Minimum voltage:
30 V DC, 0.43 A/16 W
Maximum voltage:
60 V DC
Internal fuse:
5 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 005

2.2.8 FIELD AND STATOR GROUND MODULES

GPM-S-G MODULE
Power supply:
100 to 240 V AC at 50/60 Hz and 110VA
125 to 250 V DC at 110W
Output ratings:
26 V rectangular at 20 Hz, load capabil-
ity 80 VA
GPM-S-B MODULE
Power rating:
80VA
Input ratings:
maximum 30 V rectangular at 20 Hz
GPM-F-R MODULE
Current limiting resistor: 12.5 Ω × 4
Voltage divider resistor: 5 Ω × 3
STATOR GROUND PROTECTION CT
Part number:
204-SD-43737
Turns ratio:
400:5A
Rating factor (RF):
3.0
Frequency:
20 Hz
Voltage insulation:
600 V
Basic impulse level (BIL): 10 kV