Page 1
TECHNICAL MANU ACNF, ADPF, AEPF, ARPF, ARUF, ASPF, ATUF, AWUF Air Handlers • Refer to Service Manual RS6100004 & RS6200006 for installation, operation & troubleshooting information. • All safety information must be followed as provided in the Service Manual. •...
Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Installation and repair of this unit Goodman will not be responsible WARNING WARNING WARNING...
Page 3
WARNING that is not design certified by damage, personal injury, or death, Goodman for use with this unit. do not store combustible materials or use gasoline or Serious property damage, personal injury, reduced unit other flammable liquids or vapors in the vicinity of this performance and/or hazardous conditions may result appliance.
PRODUCT DESIGN AIR HANDLERS WARNING *See Air Handler Specification Sheet for Proper Combinations. ALL AIR HANDLERS USE DIRECT DRIVE MO- When installing or servicing this equipment, safety TORS. POWER SUPPLY IS 220-240 V, 60 HZ, 1 clothing, including hand and eye protection, is PHASE strongly advised.
Page 5
PRODUCT DESIGN To prevent the horizontal drain pan from sweating in high *ARPF air handlers are multi-position, multi-speed with di- humidity applications, it is recommended that a DPIH rect drive motors. They are available in 1 1/2 to 5 ton sizes insulation accessory kit be used.
BLOWER PERFORMANCE DATA ACNF CFM delivered against External Static Pressure Model Speed 0.1” 0.2” 0.3” 0.4” 0.5” High ACNF18001 High ACNF18051 High ACNF18061 High ACNF18081 High ACNF24001 High ACNF24051 High ACNF24061 High ACNF24081 High ACNF24101 High 1,075 1,015 ACNF30001 High 1,075 1,015 ACNF30051 High...
Page 9
ACNF BLOWER PERFORMANCE DATA ACNF*****DA (with aluminum coils) CFM deliverd against External Static Pressure Model Speed 0.1" 0.2" 0.3" 0.4" 0.5" High ACNF180016 High ACNF180516 High ACNF180616 High ACNF180616 High ACNF240016 High ACNF240516 High ACNF240616 High ACNF240816 High ACNF241016 High 1,060 ACNF300016 High...
Page 14
BLOWER PERFORMANCE DATA AEPF The AEPF air handler blower motor is pre-programmed for operation at four distinct airflow levels when operating in the Cooling, Heat Pump heating, Backup heating (Electric Heating), and Backup + Heat Pump heating modes. Each modes has four levels to deliver different CFM. Simply flip the dipswitch for a different CFM combination. Setting the Motor Dipsw itch Function...
Page 20
BLOWER PERFORMANCE DATA ARUF CFM deliverd against External Static Pressure M odel Speed 0.1" 0.2" 0.3" 0.4" 0.5" High 1155 1090 1025 ARUF172916 M ed. High 1155 1090 1025 ARUF182416 M ed. High 1135 1085 1025 ARUF193116 M ed. High 1385 1315 1240...
Page 22
PRODUCT SPECIFICATIONS ASPF AS PF183016* ASPF303616* AS PF313716* ASPF426016* B lowe r D iam eter 9 1/2" 10 5/8" 10 5/8" 10 15/16" W idth 8" 10 5/8" 10 5/8" 10 11/16" C oil D rain C onnec tion FPT 3/4"...
Page 23
BLOWER PERFORMANCE DATA ASPF CFM deliverd against External Static Pressure M otor M odel Speed Tap 0.1" 0.2" 0.3" 0.4" 0.5" ASPF183016 1075 1055 1015 1130 1115 1085 1040 1000 1060 1105 ASPF303616 1165 1070 1020 1285 1240 1195 1140 1100 1435 1395...
Page 30
BLOWER PERFORMANCE DATA AWUF CFM deliverd against External Static Pressure Model Speed 0.1" 0.2" 0.3" 0.4" 0.5" High AWUF18XX1/16A* High AWUF18XX16B* High AWUF24XX1/16A* High AWUF24XX16B* 1250 1195 1135 1085 1010 High AWUF30XX1/16A* 1110 1055 1020 1255 1120 1100 1020 High AWUF30XX16B* 1115 1010...
WIRING DIAGRAMS ACNF HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 32
WIRING DIAGRAMS ADPF, ARPF, ARUF, ATUF HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. HTR1 HTR2 HTR1 HTR1 HTR2 HTR1 TL HTR2 HTR3...
Page 33
WIRING DIAGRAMS ADPF, ARPF, ARUF, ATUF HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. HTR1 HTR2 HTR1 HTR1 HTR2 HTR1 TL HTR2 HTR3...
Page 34
WIRING DIAGRAMS AEPF HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. HTR1 HTR2 HTR1 HTR1 TL HTR2 HTR1 TL HTR2 HTR3 HTR3 TL...
Page 35
WIRING DIAGRAMS AEPF******CA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. HTR 1 HTR 1 HTR 1 HTR 1 HTR 2 PL 1 HTR 2...
Page 36
WIRING DIAGRAMS ASPF******AA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 37
WIRING DIAGRAMS ASPF******BA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 38
WIRING DIAGRAMS ASPF******CA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. HTR1 HTR1 HTR1 HTR2 HTR1 HTR2 HTR2 HTR3 HTR3 HTR4 FOUR (4) ELEMENT ROWS...
Page 39
WIRING DIAGRAMS ASPF******C* HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 40
WIRING DIAGRAMS AWUF [18, 24, 30, 36]** HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 41
WIRING DIAGRAMS AWUF[31-32]** HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 42
WIRING DIAGRAMS AWUF37 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Need help?
Do you have a question about the RS6100004 and is the answer not in the manual?
Questions and answers