1MRK504116-UUS C
3.6.7.3
Table 68:
ZSMGAPC Group settings (basic)
Name
Values (Range)
IBase
1 - 99999
VBase
0.05 - 2000.00
PilotMode
Disabled
Enabled
Zreach
0.1 - 3000.0
IMinOp
10 - 30
Table 69:
ZSMGAPC Group settings (advanced)
Name
Values (Range)
DeltaI
0 - 200
Delta3I0
0 - 200
DeltaV
0 - 100
Delta3V0
0 - 100
SIRLevel
5 - 15
3.6.8
Application manual
SIRLevel: The setting of the parameter SIRLevel is by default set to 10. This is a
suitable setting for applications with CVT to avoid transient overreach due to the CVT
dynamics. If magnetic voltage transformers are used, set SIRLevel to 15 the highest level.
IMinOp: The minimum operate current for the SIR measurement is by default set to
20% of IBase.
Setting parameters
Unit
Step
A
1
kV
0.05
-
-
ohm
0.1
%IB
1
Unit
Step
%IB
1
%IB
1
%VB
1
%VB
1
-
1
Faulty phase identification with load encroachment
FMPSPDIS (21)
Function description
Faulty phase identification with load
encroachment for mho
Default
Description
3000
Base value for current measurement
400.00
Base value for voltage measurement
Disabled
Pilot mode Disable / Enable
38.0
Line impedance
20
Minimum operating current for SIR
measurement
Default
Description
10
Current change level in %IB for fault inception
detection
10
Zero seq current change level in % of IB
5
Voltage change level in %VB for fault
inception detection
5
Zero seq voltage change level in % of VB
10
Settable level for source impedance ratio
IEC 61850
IEC 60617
identification
identification
FMPSPDIS
S00346 V1 EN
Section 3
IED application
ANSI/IEEE C37.2
device number
21
311