16 Technical data
16.5
Technical specifications
16.5.1
Technical specifications: Outdoor unit
Nominal capacity and nominal input
Outdoor units
Indoor units
Condition 1
(a)
Heating capacity
Cooling capacity
Heating PI
Cooling PI
COP
EER
Condition 2
(b)
Heating capacity
Cooling capacity
Heating PI
Cooling PI
COP
EER
(a)
In heating: Ambient temperature DB/WB 7°C/6°C – leaving water condenser 35°C (DT=5°C). In cooling: Ambient temperature
35°C – leaving water evaporator 18°C (DT=5°C)
(b)
In heating: Ambient temperature DB/WB 7°C/6°C – leaving water condenser 45°C (DT=5°C). In cooling: Ambient temperature
35°C – leaving water evaporator 7°C (DT=5°C)
Installer reference guide
102
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Nominal
Nominal
Nominal
Nominal
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Nominal
Nominal
Nominal
Nominal
Heating only type
RVLQ05CAV3
RVLQ08CAV3
RHYHBH05
RHYHBH08
1.80 kW
4.40 kW
5.12 kW
—
—
—
0.87 kW
—
5.04
—
1.80 kW
4.03 kW
4.90 kW
—
—
—
1.13 kW
—
3.58
—
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
Reversible type
RVLQ08CAV3
RHYHBX08
7.40 kW
10.02 kW
2.50 kW
6.86 kW
1.66 kW
2.01 kW
4.45
3.42
6.89 kW
9.53 kW
2.50 kW
5.36 kW
2.01 kW
2.34 kW
3.42
2.29
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1 – 2013.05
Need help?
Do you have a question about the RHYKOMB33AA and is the answer not in the manual?
Questions and answers