Technical Data; General Specifications - Panasonic Network Adaptor Specification Sheet

Programmable controller
Hide thumbs Also See for Network Adaptor:
Table of Contents

Advertisement

FP-e Series

Technical data

General specifications

Item
Rated voltage
24 V DC
Operating voltage range
21.6 to 26.4 V DC
Allowed momentary power off time
10 ms
Ambient temperature
0 to +55°C
Storage temperature
–20 to +70°C
Ambient humidity
30 to 85%RH (non-condensing)
Storage humidity
30 to 85%RH (non-condensing)
Input terminals (COM, X0 to Xn)
Output terminals (Y0 to Y4)
Breakdown voltage
Output terminal (Y5)
Input terminals (COM, X0 to Xn)
Input terminals (COM, X0 to Xn)
Output terminals (Y0 to Y5)
Insulation resistance
Input terminals (COM, X0 to Xn)
10 to 55 Hz, 1 cycle/min.
Vibration resistance
Double amplitude: 0.75 mm, 10 min. on X, Y, and Z axes
Shock resistance
98 m/s
Noise resistance
1000V (p-p) with pulse widths 50 ns and 1 µs (based on in-house measurements)
Operating condition
Free from corrosive gases and excessive dust
Current consumption
200 mA or less (24 V DC)
Protection
IP66-compliant front section (Only when a rubber packing is used.)
Mass
Approx. 130 g
DC input specifications (X0 to X7)
Item
Number of input
8 points (6 points for thermocouple input type)
Insulation method
Optical coupler
Rated input voltage
24 V DC
Operating voltage range
21.6 to 26.4 V DC
Rated input current
Approx. 4.3 mA
8 points/common (6 points/common for
Input points
thermocouple input type)
per common
Either the positive or negative of the input power
supply can be connected to common terminal.
ON voltage/ON current
19.2 V or less/4 mA or less
OFF voltage/OFF current
2.4 V or more/1 mA or more
Approx. 5.1 k (X0, X1)
Input impedance
Approx. 5.6 k (X2 to X7)
50 µs or less (X0, X1)
OFF to ON
100 µs or less (X2 to X5)
2 ms or less (X6, X7)
Response
time
50 µs or less (X0, X1)
ON to OFF
100 µs or less (X2 to X5)
2 ms or less (X6, X7)
Operating mode indicator
LCD display (I/O monitor mode)
Note 1)
X0 through X5 are inputs for the high-speed counter and have a fast response
time. If used as normal inputs, you should insert a timer in the program as
chattering and noise may be interpreted as an input signal.
Also, the above specifications apply when the rated input voltage is 24V DC
and the temperature is 25°C.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
2
or more, 4 times on X, Y, and Z axes
Thermocouple input specifications
Description
Number of input
Temperature sensor type
Input range
Accuracy
Resolution
Conversion time
Insulation method
Detection function of
wire disconnection
∗1)
Temperature can be measured up to 330°C (626°F). When the measured temperature
exceeds 330°C (626°F) or the thermocouple wiring is disconnected, "K20000" is written
Note 1)
to the register.
∗2)
Temperature conversion for thermocouple input is performed every 250 ms. The
Note 1)
conversion data is updated on the internal data register after the scan is completed.
∗3)
The internal circuit and thermocouple input circuit are not insulated. Therefore, use the
nongrounding type thermocouples and sheath tubes.
Note 1)
Note 1)
Description
Power supply terminal, Function earth
Input terminal (A0, A1)
500 V AC for 1 minute
COM. (RS232C) terminal
Power supply terminal, Function earth
Input terminal (COM, X0 to Xn, A0, A1)
1500 V AC for 1 minute
COM. (RS232C) terminal
Output terminals (Y0 to Y4)
500 V AC for 1 minute
Power supply terminal, Function earth
Input terminal (A0, A1)
Min. 100 M
COM. (RS232C) terminal
(measured with 500 V DC)
Output terminals (Y0 to Y5)
Item
Description
2 points (CH0: WX1, CH1: WX2)
Thermocouple type K
∗1)
–30.0 to 300.0°C
(–22 to
±0.5%FS±1.5°C (FS = –30 to 300°C)
0.1°C
∗2)
250 ms/2CH
Between internal circuit and thermocouple input
∗3)
circuit: noninsulated
Between CH0 and CH1 of thermocouple input:
PhotoMOS insulation
Available
572°F)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp-e seriesAfpe224300Afpe224302Afpe224305Afpe214325Afpe214322

Table of Contents