Goodman GPH16 Installation Instructions Manual

Goodman GPH16 Installation Instructions Manual

15/16 seer “h” series self-contained package air conditioners and heat pump units with r-410a

Advertisement

I
NSTALLATION
GPC15 / GPH16 (15/16 SEER "H" SERIES)
S
-C
P
ELF
ONTAINED
ACKAGE
W
R-410A
ITH
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with
this Installation Manual. Observe all safety warnings. Dur-
ing installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to
educate the customer on its safe use.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
ENERGY STAR
ENERGY STAR
Agency.
ENERGY STAR
ENERGY STAR
the
ENERGY STAR
ENERGY STAR
Environmental Protection Agency.
IOG-3011B
04/2016
I
NSTRUCTIONS
A
C
IR
ONDITIONERS AND
®
and the
ENERGY STAR
ENERGY STAR
mark are registered trademarks owned by the U.S. Environmental Protection
products are third-party certified by an EPA-recognized Certification Body. Products that earn
prevent greenhouse gas emissions by meeting strict energy efficiency guidelines set by the U.S.
"IMPORTANT – This product has been designed and manufactured to meet ENERGY STAR
criteria for energy efficiency when matched with appropriate coil components. However,
proper refrigerant charge and proper air flow are critical to achieve rated capacity and
efficiency. Installation of this product should follow the manufacturer's refrigerant charging
and air flow instructions. Failure to confirm proper charge and airflow may reduce energy
efficiency and shorten equipment life."
Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com
© 2015-2016 Goodman Manufacturing Company, L.P.
All information contained herein is subject to change without notice.
H
P
U
EAT
UMP
NITS
These installation instructions cover the outdoor installa-
tion of self contained package air conditioner and heating
units. See the Specification Sheets applicable to your model
for information regarding accessories.
*NOTE: Please contact your distributor or our website for
the applicable Specifications Sheets referred to in this
manual.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GPH16 and is the answer not in the manual?

Questions and answers

Summary of Contents for Goodman GPH16

  • Page 1 NSTALLATION NSTRUCTIONS GPC15 / GPH16 (15/16 SEER “H” SERIES) ONTAINED ACKAGE ONDITIONERS AND NITS R-410A ATTENTION INSTALLING PERSONNEL These installation instructions cover the outdoor installa- Prior to installation, thoroughly familiarize yourself with tion of self contained package air conditioner and heating this Installation Manual.
  • Page 2: Table Of Contents

    AIR FLOW MEASUREMENT AND ADJUSTMENT ..10 TO THE INSTALLER ........... 2 ADJUSTING SPEED TAP FOR INDOOR SHIPPING INSPECTION ........2 BLOWER MOTOR ........... 10 Checking Product Received ......2 Message to the Homeowner ......3 EXPANSION VALVE (TXV) SYSTEM REPLACEMENT PARTS ........
  • Page 3: Shipping Inspection

    Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact: CONSUMER AFFAIRS GOODMAN MANUFACTURING COMPANY, L.P. 7401 SECURITY WAY HOUSTON, TEXAS 77040 877-254-4729...
  • Page 4: Codes And Regulations

    See outdoor unit specification sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found at www.goodmanmfg.com for Goodman brand products or www.amana-hac.com for Amana brand products.
  • Page 5: Rooftop Installation

    Location 36" Consider the affect of outdoor fan noise on conditioned space and any adjacent occupied space. It is recommended that the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away. The unit should be set on a solid, level foundation - preferably a concrete slab at least 4 inches thick.
  • Page 6: Plenum Application

    SQUARE TO ROUND DUCT CONVERTER PANEL OUTER FLANGE 1000 1500 2000 2500 3000 3500 STARTER FLANGE Airflow - SCFM FIGURE 3 FIGURE 4 flanges of the square duct openings. The flexible duct is then clamped on to the collars. Once the duct is affixed to the unit, seal the collars and flanges with a proper waterproof sealant (See Figure 3).
  • Page 7: High Voltage Wiring

    Fuses smaller than that recommended on the wiring diagrams could result in unnecessary fuse failure or service calls. The WARNING use of protective devices of larger size than indicated could HIGH VOLTAGE result in extensive damage to the equipment. The ISCONNECT POWER BEFORE SERVICING OR INSTALLING manufacturer bears no responsibility for damage caused to...
  • Page 8: Heat Pump Start-Up Procedure

    4. Turn the fan switch to the “ON” position. The blower should operate after a 10 second delay. WARNING HIGH VOLTAGE 5. Turn the fan switch to “Auto” position. The blower should ISCONNECT POWER BEFORE SERVICING OR INSTALLING stop after a 60 second delay. THIS UNIT.
  • Page 9: Final System Checks

    Final System Checks 16. Check to see if all supply and return air grilles are adjusted and the air distribution system is balanced for the best compromise between heating and cooling. 17. Check for air leaks in the ductwork. 18. See Sections on Air Flow Measurement and Adjustment and Checking Charge. 19.
  • Page 10: Defrost Control

    Figure 7 shows a schematic of a heat pump on the cooling cycle and the heating cycle. In addition to a reversing valve, a heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equipment for the outdoor coil.
  • Page 11: Adjusting Speed Tap For Indoor

    NOTE: If more than one lead is energized at the same time, the motor will use the higher speed setting. SATURATED SATURATED NOTE: GPC15 and GPH16 units are rated for a maximum SUCTION PRESSURE LIQUID PRESSURE E.S.P. of 0.8 except when using a 20kw electric heater. (The...
  • Page 12: Two Speed Application (Gph1648 / Gpc1560)

    4. Disconnect manifold set, installation is complete. ELECTRIC HEAT INSTALLATION & ADJUSTMENT This series of electric cooling and heat pump package GPC15/GPH16(24-60) Models (0 - 0.5 E.S.P.) equipment is designed to accept a field installed electric heat Electric Heat KW Unit Model Number kit.
  • Page 13: Service

    SERVICE WARNING THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY: OTHERS SHOULD NOT ATTEMPT TO HIGH VOLTAGE SERVICE THIS EQUIPMENT. ISCONNECT POWER BEFORE SERVICING OR INSTALLING THIS UNIT. ULTIPLE POWER SOURCES MAY BE PRESENT. FAILU Common Causes of Unsatisfactory Operation of Heat Pump TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY O on the Heating Cycle.
  • Page 14: Blower Performance Gp* 15/16 Seer

    *PC15/*PH16[24-36]H41 BLOWER PERFORMANCE GPC15 /GPH16[24-36]H41 BLOWER PERFORMANCE E.S.P. (In. of H Model Speed Volts Watts T2 / T3 Watts 1231 1179 1127 1074 1022 T4 / T5 Watts Watts T2 / T3 Watts 1231 1179 1127 1074 1022 T4 / T5...
  • Page 15 *PC15/*PH16[42-60]**H41 BLOWER PERFORMANCE GPC15 /GPH16[42-60]H41 BLOWER PERFORMANCE E.S.P. (In. of H Model Speed Volts 1181 1146 1112 1062 1022 Watts 1410 1366 1328 1286 1248 1195 1155 1115 T2 / T3 Watts 1637 1605 1561 1527 1484 1436 1390 1345...
  • Page 16: Troubleshooting Chart

    TROUBLESHOOTING CHART HIGH VOLTAGE! ISCONNECT POWER BEFORE SERVICING OR INSTALLING THIS UNIT ULTIPLE POWER WARNING SOURCES MAY BE PRESENT AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH POSSIBLE CAUSE REM EDY SYMPTOM High head - low suction a.
  • Page 17 PACKAGE UNITS - HEAT PUMP AND AC UNITS HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin. An alternate cleaning method is to use one of the products EPLACE OR LEAN ILTER...
  • Page 18: Start-Up Checklist

    Start-up Checklist *Store in job file Air Conditioning & Heating Date: ___________________________________ Location: __________________________________________ Model Number: ___________________________________ __________________________________________ Serial Number: ___________________________________ __________________________________________ Technician: ___________________________________ Unit #: __________________________________________ Pre Start-Up (Check each item as completed) Verify all packaging material has been removed. Remove all shipping brackets per installation instructions.
  • Page 19 Start-up Checklist Air Conditioning & Heating Start-Up (Insert the values as each item is completed.) ELECTRICAL Supply Voltage L1 - L2 L2 - L3 L3 - L1 Circuit 1 Compressor Amps Circuit 2 Compressor Amps Blower Amps Condenser Fan Amps Fan 1 Fan 2 Fan 3...
  • Page 20 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com © 2015-2016 Goodman Manufacturing Company, L.P .