9.4
Testing the full-tank float switch (or pressure switch) circuit
Table 10:
Testing the full-tank float switch (or pressure switch) circuit
Test
Test Description
Notes
IF SWITCH IS NORMALLY OPEN (N.O.), cf. figure 26
10
POWER ON
voltage at terminals
3 and 4
chose one of
these two tests
10
resistance between
switch wires,
disconnected from
controller
IF SWITCH IS NORMALLY CLOSED (N.C.), cf. figure 26
11
POWER ON
voltage at terminals
4 and 5
chose one of
these two tests
11
resistance between
switch wires,
disconnected from
controller
page 36 | v100820
Meter Setting
+ Probe Input
V DC
V ...
Ω
Ω ...
V DC
V ...
Ω
Ω ...
Errors excepted and possible alterations without prior notice.
See schemes on previous page for illustration of testing
Normal Result
Interpretation
a) 0 – 2 V
if a) switch closed (or circuit shorted)
b) 5 V
if b) switch open (or circuit broken)
a) < 100 Ω
if a) switch closed (or circuit shorted)
b) > 10 kΩ
if b) switch open (or circuit broken)
a) 0 – 2 V
if a) switch closed (or circuit shorted)
b) 5 V
if b) switch open (or circuit broken)
a) < 100 Ω
if a) switch closed (or circuit shorted)
b) > 10 kΩ
if b) switch open (or circuit broken)
- pump off
- pump on
- pump off
- pump on
- pump on
- pump off
- pump on
- pump off
Manual | LORENTZ PS Pump Systems