Air-Tightness Test - Mitsubishi Electric PURY-(E)P-YLM-A (-BS) Installation Manual

Air-conditioners for building application
Table of Contents

Advertisement

Available languages

Available languages

9-5-3. Sealing the openings around the pipes
Seal all openings around pipes and wires to keep out small animals, rainwater, or snow.
- Failure to do so may result in current leakage, electric shock, or damage to the unit.

9-6. Air-tightness test

Do not use oxygen, flammable gas, or a refrigerant containing chlorine for air-tightness
testing.
- Doing so may result in an explosion. Chlorine will deteriorate the refrigerant oil.
After refrigerant pipe installation is completed, check the system for leaks by conducting an air-tightness test. If there
is a leak, the composition of the refrigerant will change and the performance will drop.
<Air-tightness test procedures>
① Make sure the service valves are closed.
② Add pressure to the refrigerant pipes through the service ports of the high- and low-pressure pipes.
* Pressurize to the design pressure (4.15 MPa) using nitrogen gas.
③ If the pressure holds for one day and does not decrease, the pipes have passed the test and there are no leaks.
If the pressure decreases, there is a leak. Look for the source of the leak by spraying a bubbling agent (e.g.,
Gupoflex) on the flared or brazed sections.
④ Wipe off the bubbling agent.
WT07282X01
Example of closure materials (not supplied)
Fill the openings
* The figure shows a unit on which an outdoor unit twinning kit
(low-pressure side) is not installed.
HI
LO
Nitrogen gas
To indoor unit
Gauge manifold
Low pressure knob
High pressure knob
Service valve
Low-pressure pipe
High-pressure pipe
Outdoor unit
Service port
GB-31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents