Safety warnings This instructions manual is an essential and complementary part of the product and it is supplied to- gether with the boiler . Carefully read the manual, achieving all important information for a safe installation, use and servicing . f Carefully keep the manual, together with the documentation of all the accessories of the boiler and of the system, for any further consultation you may need.
Safety warnings symbols legend Generic safety Electrical danger Physical danger warning (fulguration) (personal damage) Thermal danger General warning or advice to avoid material damage (burns) or to achieve improvements References to Laws and Norms All the references to norms and national laws mentioned in this handbook are indicative as laws and norms are subject to issues and integrations by the authorities in charge.
The first starting up and the maintenance of the boiler must be performed by a professionally qualified staff (for example the installer or the Service Centres authorized by ITALTHERM) Gas conversion from a gas of a specific family to a gas of another family (from natural gas to LPG or vice versa) to another gas, can be made also when the gas boiler is already installed, but only by a qualified technician.
f Do not put any object on the gas boiler and don't leave any flammable liquid or solid materials, (e.g. paper, clothes, plastic, polystirene) in its proximity. f This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervi- sion or instruction concerning use of the appliance by a person responsible for their safety.
User guide The front control panel Electrical Supply Indicator Light green Off - boiler not electrically supplied. Blinking - boiler electrically supplied, but not active because the knob 12 is on . On - boler active. Knob 12 on , or on ...
On trade are available programmable room thermostats: most of them allow to make a weekly programming of various temperature levels, besides special programs for various purposes. We suggest to choose original ITALTHERM accessories Green Heating Technology...
Typical use Preliminary operations f Firstly, the knob 12 should be on the position 8 . f Make sure, by the gauge 17 that the cold-system temperature is al- service ways within 0.5 and 1.5 Bar (opti- mal: 1÷1.5 Bar). When the pressure drops below 0.5 Bar, the boiler stops working.
"User Guide" section and expressly allowed to the User. Always address yourselves to qualified personnel. Boilers must be always equipped with original accessories only. ITALTHERM Srl is not responsible for damages caused by the incorrect, wrong or unreasonable use of not original materials. The burner doesn’t turn on f if the room thermostat (or programmable room thermostat, or similar) is installed, check that it is really requiring the room heating;...
Boiler inactivity The effects of the periods of inactivity can be relevant in particular situations such as in flats used only for some months per year, most of all in cold places. The user will have to decide to put the boiler in the SAFETY SHUT OFF state disconnecting all the sup- plies, or to leave it in stand-by and use the Anti Frost Function.
ATTENTION: the anti-frost protections cannot intervene in the absence of electricity. If you an- ticipate this possibility, we recommend you add a good brand of anti-freeze to the heating sys- tem, following the producer’s instructions. We recommend to ask directly the installer/technician about the type of antifreeze product put in the heating system during installation.
Dimensions and connections 23÷43 23÷43 left side view - front view - front view - hydraulic connec- hydraulic connections hydraulic connections tions on the boiler on the wall on the boiler (with optional fitting kit) TA / L 52 52 88 39 52 52 88 39 Legend: upper view...
ITALTHERM S.r.l. will not be held responsible for consequent damages. Instruct the User about the antifreeze function of the boiler and about the antifreeze product added in the heating system.
Positioning and fastening If necessary, the open hooks can be positioned at any point along the edge B 32.5 32.5 of the boiler's frame bracket, provided that they are 2 and that they support the device in a correct and safe way . 45 35 Remark: A re-usable metal jig ( D in the figure) can be ordered separately, so as to facilitate connec- tions and fixing points positioning (when the original connection kit is used).
(consider that 1 mm of limestone incrustations reduces of 18% the thermal exchange of the heating element on which it has been formed). ITALTHERM guarantees its products only if the characteristics of the water comply with UNI 8065, re- ported also in laws on energy saving .
f Check the correct functioning of automatic venting de- vices, eventually installed; f Close the radiators venting devices as soon as water flows out of them; f Make sure, by reading the pressure gauge 2, that the pres- sure reaches the optimal value of 1.0 bar (max 1.5 bar); f Close the water supply valve 1 and bleed each radiator again;...
ITALTHERM S.r.l. declines any responsibility for damages to persons, animals or things caused by the faulty or missing connection of the boiler earthing and by failure to comply with the rules.
Eventual coaxial inlet Condensate collec on device 2% ÷ 5% Flue duct or chimney Horizontal flue outlet Ver cal flue outlet Carefully follow the prescriptions by the National and Local Regulation in force. Respect the minimum and maximum flue system length (refer to "Flue system types" on page 21). In case of flue outlet on wall, the positions and the distances prescribed by the regulation mist be re- spected (see "Flue terminals positioning"...
Flue terminals positioning Posizionamento dei terminali di scarico (nella parete stessa di cui si sta valutando la zona di rispetto) per apparecchi muniti di ventilatore in funzione della loro portata termica (per informazioni dettagliate, vedere la norma UNI 7129-3:2008 e successive modifiche o integrazioni) Distanze minime (mm) Apparecchi Apparecchi...
Flue system types Split pipe system (C * and B Split pipe system Ø80mm Reducer AS+SC Model min÷max for length of Ø mm AS+SC (m) (AS = 0 m) up to 8 46 (R) 24 F 2 ÷ 28 more than 8 45 mm up to 8 48 (R)
Adjustment and Maintenance ATTENTION: the operations described below must be carried out only by qualified personnel [authorized by ITALTHERM] . When regulation/measuring is over, remember to tighten pressure tapping point screws and ALWAYS check for gas leaks! Before boiler ignition, verify that pump is not blocked due to its inactivity: unscrew the plug located in the middle of the cap to gain access to the rotor shaft, and turn it manually using a screwdriver or another suitable tool.
Inlet gas check Remark: The pressure should be measured at nomi- nal input, so this test must be performed with the burner ignited. Loosen (2-3 turns) the screw of pressure tapping point for gas inlet 2 of the gas valve and insert the manometer sensor;...
wait at least 10 seconds and verify that the meas- ured pressure corresponds to the MAX value indi- cated in the Burner Pressure table (see page 26), with regard to the boiler model and gas type; extract one of the connectors 4 that supply the modulation coil;...
Page 25
00 corresponds to the minimum setting of the gas valve and the value 99 corresponds to the maximum; • wait (approximately five seconds) that the display shows “PO” (POwer) flashing (moreover, both the GREEN and RED indicators flash to short “pulses”). •...
Burner pressure tables HEAT OUTPUT NATURAL GAS G20 BUTANE G30 PROPANE G31 Display value kcal/h mbar mm H mbar mm H mbar mm H MIN . 9 .1 7826 2 .1 4 .7 4 .7 8600 2 .5 5 .4 5 .4 9460 3 .0...
The factory setting depends on the gas type arranged in factory for the boiler. To change the type of gas supply, it is necessary to follow the complete instructions described in the paragraph "Gas conversion" on page 28. OFF In City Plus Boilers it must be OFF . Factory setting . Green Heating Technology...
OFF delay ON (for normal radiators systems). Factory setting . delay OFF (for fan coil systems). OFF In City Plus Boilers it must be OFF . Factory setting . Pump functioning mode during heating working. intermittent for normal applications (with or without delay, see SW3).
Check and if necessary adjust the gas valve maximum and minimum pressure (see page 23) and the heating maximum power (see page 24). 10. Check that there are no gas leaks. 11. Apply the sticker indicating the type of gas (supplied with the kit) on the suitable area on “WARN- ING”...
Draining the heating system When it is necessary to drain the heating system, pro- ceed as described here below: f Connect a rubber pipe to the draining tap termi- nal 1 ; f put the other end of the pipe in a suitable drain or sink;...
Page 31
Signal Probable causes Suggested solutions Check that the Inlet/Outlet Ducts and the respective terminals are Incorrect com- clean and in good condition, and that there are no leaks in them. bustion / flame de- During the installation, respect the regulation prescriptions, the tachment from the slopes and the lengths (see "Flue systems"...
Page 32
Signal Probable causes Suggested solutions Memory-stored User: Disconnect the electrical supply to the boiler by operating the data not coherent . suitable external bipolar switch, then connect it again after a few minutes. If the lockout persists or reappears, call the Service Centre. Redo all the boiler settings ("Max heating power adjustment"...
Clean casing with soapy water only. Do not clean casing, other painted or plastic surfaces with thin- ner . f In any case of parts replacement, it is mandatory to use ITALTHERM original spare parts. ITALTHERM declines any responsibility in case of non-original spare parts utilization.
Technical data TECHNICAL DATA City Plus 24 F City Plus 30 F U.M. Gas type G30 / G31 G30 / G31 CE certification 0694 CM 3400 Class 2H3+ 2H3+ Type B22 - C12 - C32 - C42 - C52 - C62 - C82 - C92 Working temperature range °C...
Page 35
TECHNICAL DATA (cont'd) City Plus 24 F City Plus 30 F U.M. Gas type G30 / G31 G30 / G31 HOT WATER Flow rate at 25°C temp. rise l/min 13 .7 17 .2 Flow rate at 30°C temp. rise l/min 11 .4...
Hydraulic diagram This diagram is for information only. To make boiler hydraulic connection either see "Dimen- sions and connections" on page 13 and eventually "Positioning and fastening" on page 15. Flue pressure switch 19 Loss of water pressure switch 20 Heating circuit temperature sensor Safety thermostat for 21 Burner max.
Remote Control Kit This remote control is more than a simple room thermostat . Thanks to this, it is possible to manage the boiler in all its set- tings like DHW and CH temperature adjustment, boiler reset in case of boiler block, and of course it works as a room thermo- stat both in manual and weekly program mode.
Page 40
ITALTHERM Srl Via S. D’Acquisto, snc • 29010 Pontenure (PC) - IT Tel. +39.0523.575611 • Fax +39.0523.575600 www.italtherm.it • e-mail: info@italtherm.it UNI EN ISO 9001:2008...