Pressurized boiler head output: 635 - 1900 kw (12 pages)
Summary of Contents for REMEHA Avanta Plus 35c
Page 1
Installation and service manual Remeha Avanta Plus • Remeha Avanta Plus 28c • Remeha Avanta Plus 35c • Remeha Avanta Plus 39c • Remeha Avanta Plus 24s...
2.1 Scope of delivery 2.2 Mounting the boiler 2.2.1 Clearance requirements 2.2.2 Dimensions and connection points. 2.2.3 Mounting the Remeha Avanta Plus 2.3 Water-side connections 2.3.1 Water fl ow 2.3.2 Circulation pumps 2.3.3 Additional guidelines for the domestic and CH water 2.3.4...
Page 3
Error read outs 4.4.2 Deleting errors SERVICE PARTS 5.1 General EC DECLARATION REGULATIONS 7.1 EC regulations 7.2 Remeha factory test TECHNICAL SPECIFICATIONS AND WORKING PRINCIPLE 8.1 Technical data 8.2 The boiler components 8.3 Working principle 8.3.1 Regulating 8.3.2 Advanced boiler control (‘abc ®...
Remeha Avanta Plus INTRODUCTION The Remeha Avanta Plus is a series of high-efficiency fully condensing central heating boilers, for wall mounting, available in the following types: • Remeha Avanta Plus 28c, 35c and 39c - with integrated domestic hot water system (Combi-type) •...
1.3 Safety during installation, inspection and maintenance Under the current Gas Safety (Installation & Use) Regulations, the Remeha Avanta Plus, in common with all gas appliances, must be installed by a competent person in accordance with that regulation. Statutory regulations in any country, cannot be overridden by any of the notes or instructions from the manufacturer.
Page 6
Remeha Avanta Plus The Remeha Avanta Plus (combi and system) is a WRAS (Water regulations) approved product. Remeha Avanta Plus (combi and system) - PIN: 0063BQ3009 Gas Council numbers: Remeha Avanta Plus 28c: 47-673-02 Remeha Avanta Plus 35c : 47-673-03 Remeha Avanta Plus 39c: 47-673-04 LT.AL.W7H.000.074...
Assembly Instructions supplied with these accessories. 2.2 Mounting the boiler Packed in the box with the Remeha Avanta Plus box is this Installation and Service manual. Read instructions and remarks carefully. This section includes the guidelines and instructions for the connection of gas, water, electricity, safety devices, the regulator, control unit, flue discharge and air supply.
Remeha Avanta Plus 2.2.2 Dimensions and connection points. System-type Return connection Ø 22 mm Flow connection Ø 22 mm Gas connection Ø 22 mm Combustion air inlet Ø 100 mm (concentric) Flue duct Ø 60 mm (concentric) Condensate drain connection ¾”...
Page 9
(standard overflow pipe size) Connection safety valve Ø 15 mm • Based on the guidelines and the required installation space, determine where to mount the Remeha Avanta Plus. • In determining the boiler position, consider carefully the flue outlet position and any pluming consequences.
Remeha Avanta Plus 2.2.3 Mounting the Remeha Avanta Plus • Remove the mounting plate and template from the box. • Using the template determine and mark the position of the three mounting holes and center line of flue, making sure the plate is absolutely level.
2.3.2 Circulation pumps The Remeha Avanta Plus 24s and 28c are fitted with the Grundfos UPR 15-60 and the Avanta Plus 35c and 39c with the UPR 15-70, two-speed circulation pumps. The control unit ensures that when the hot-water function is active, the pump runs at ‘high’.
Remeha Avanta Plus Please ensure that the new boiler plant is not in circuit when the flushing takes place, especially if cleansing chemicals are used to assist the process. It is important to check the inhibitor concentration after installa- tion, system modifications, filling the system and every service in accordance with these instructions.
2.3.6 Expansion vessel An 8 litre expansion vessel (with the vessel charge set to 1.0 bar) is fitted as standard within the boiler case and is suitable for use in a heating system with a water content up to 100 litres, operating at a flow temperature of 80°C, a maximum pressure of 3 bar and a maximum system static head of 5 metres above the boiler.
• Fit the inlet pipe for CH water to the ‘CH return’ 22 mm Ø connection. The Remeha Avanta Plus has a drain cock built into the return isolating valve It is considered good practice to install an air separator / dirt removal device in the return to the boiler.
LT.AL.W7H.000.018 with current regulations. 2.3.11 Connecting under floor heating The Remeha Avanta Plus can be connected directly to an under floor heating system. If plastic pipes have been used they must be made oxygen dif- fusion proof in compliance with DIN 4726/4729.
2 m above the ground, balcony, or flat roof where access by persons is possible a suitable guard must be employed. The boiler will produce a water vapour plume during normal operation. Positions for the Remeha Avanta Plus are shown in the figure and table 02.
Page 17
Dimen- Terminal location Minimum sions distance (in mm) 600 mm No flue must penetrate to terminal area within dotted lines 600 mm round roof light (room 2000 mm sealed) Directly below an opening, air brick, opening window, etc. Above an opening, air brick, opening window, etc.
Page 18
Remeha Avanta Plus For flue installations not covered by this booklet, please contact our technical help line 0118 978 3434. 2.5.3 Connecting the flue terminal and air supply • Check the depth of the wall and cut the terminal to suit –...
• 230 V supply cable connection. LT.AL.W7H.000.022 2.6.1 The control unit The Remeha Avanta Plus has an electronic regulation and control unit with an integrated ionisation flame detector. The heart of the boiler control unit is a microprocessor, the ‘abc ®’...
Any loads other than those specified above are only allowed if an isolating transformer is used. The output of the Remeha Avanta Plus can be controlled in the following ways: On/off control – volt free switching - The boilers internal control will modulate the output to achieve the flow tempera- ture set point of the boiler.
Page 21
Terminal Block X6 230v - 3 Amp Power Supply Terminal Block X7 Common Alarm (Closes on alarm) Boiler Run (Closes on run) Terminal Block X5 Neutral For external DHW priority diverting valve on System boiler Open valve to DHW (230v) when used in conjunction with "Open Therm"...
Remeha Avanta Plus 2.7.1 On/off control – room temperature (volt free switching) The Remeha Avanta Plus can be connected to a 2-wire on/off thermostat, such as the Remeha Celcia 10. Mount the thermostat in a reference room (usually the living room).
OpenTherm room controls ® Block X9 (e.g. the Remeha Celcia 15 or 20) to be connected without any further modifications. • Mount the control in a reference room (usually the living room). • Connect the two-wire interface cables to connectors 7 and...
Remeha Avanta Plus If the DHW water temperature on the OpenTherm control can ® be adjusted, then the Remeha Avanta Plus will supply water at the temperature determined at the OpenTherm with the maxi- ® mum being set in the boiler.
2.7.6 Connecting the DHW sensor/thermostat Terminal • If an external DHW calorifier is being used with the Avanta Block X9 Plus system boiler a volt-free DHW control sensor or ther- mostat can be connected to connectors 3 and 4 of the X9 terminal strip after removing the existing link.
Remeha Avanta Plus 2.7.8 Connecting an external interlock The Remeha Avanta Plus is supplied with an external interlock function. A volt free switching device (i.e. external gas pres- sure switch, safety thermostat for under floor heating) can be connected to connectors 5 and 6 of the X9 terminal strip after removing the existing link.
Remeha Avanta Plus 2.9 Commissioning 2.9.1 Control Panel The control panel of the Remeha Avanta Plus has 4 function keys and a LED display. The function keys are used to read or change the settings and temperatures. 1 = display...
Page 29
1. Isolating the power supply and opening the front cover • Switch off the boiler at the fused spur and remove the fuse; 230 V • Remove the front panel (release the two screws at the bot- tom of the front panel, pull the bottom of the panel; forward and lift off the two pins on the top of the main casing).
Page 30
Remeha Avanta Plus • Check the integral boiler pump – remove chrome centre screw to vent pump and spin the shaft to check that the impellor can move freely; • Check that all boiler connections are watertight; • Open the boiler gas valve and check the static pressure to the boiler at the measurement point (C) on the gas block.
Page 31
4. Checking/setting the gas/air ratio at full load The Avanta Plus boilers are suitable for both natural gas and propane firing. For the Avanta Plus 39c an optional propane- set is needed. The boilers are supplied as standard set for natural gas (H), therefore the following procedure must be carried out BEFORE the boilers are fired and commissioned for the first time on propane:...
Page 32
Remeha Avanta Plus Ensure that the analysing probe has a gas tight seal in the sampling point with the probe end in the centre of the flue duct. 5. Checking/setting the gas/air ratio at part load Setting values O for natural gas H / L...
• Fill in commissioning sheet and log book data. The boiler is now ready for operation. The Remeha Avanta Plus is delivered pre-tested and operating parameters set up with standard factory settings to suit the most common systems. These setting can be adjusted to suit specific site conditions but must not be changed without reference to Broag or one of our approved contractors.
Remeha Avanta Plus 2.9.5 Error during the start-up procedure • If the display is blank (should show dots or letters), check: - 230 V main supply available to switch spur - switch spur fuse - cable and connections between the switched spur and the...
Page 35
• If the boiler is set to the economy setting (see par. 2.9.8), it will not supply a boost to DHW after CH is satisfied. The display then shows; [1 ; pre-purge stage [6 ; pump run on after CH [0 ; stand-by mode. •...
The operating parameters of the Remeha Avanta Plus have been factory set to suit most systems. However it is possible to adjust some of the parameters to enable the Remeha Avan- ta Plus to operate more efficiently to match specific system designs and site conditions.
Page 37
Setting range and notes Factory settings Codes in display Description where applicable 10 – 70 Maximum fan speed CH X 100 rpm Maximum fan speed DHW Do not change Minimum fan speed Do not change (CH and DHW) Starting fan speed Do not change 0 = low Pump setting CH...
Remeha Avanta Plus Changing the factory settings could result in the boiler not working properly. The parameters can be changed from the stand-by status as follows: • Press the [enter]-key and briefly the [reset]- key until codes c and 0 appear alternately in the display.
Page 39
LT.AL.W7H.000.049 LT.AL.W7H.000.050 SPEED RATIO 35C LT.AL.W7H.000.051...
Remeha Avanta Plus 2.9.10 Restore factory settings The factory settings can be restored in the service level as fol- lows: 1. After parameter p31 has shown, press the [+]-key; d f and xx appear alternately; 2. Press -key; xx appears;...
Engineer with the relevant training and certification (i.e. CORGI - ACS - IEE registrations etc). 3.1 Inspection The annual inspection of the Remeha Avanta Plus can be lim- ited to the following checks: - check the water pressure, see par. 3.1.1;...
Remeha Avanta Plus 3.1.1 Checking the water pressure The water pressure should be checked against the commis- Min. 1 bar sioning entry in the Boiler Log Book (min 1 bar) • If necessary, re-fill system to design pressure and re-set red pointer to match fill pressure 2 bar.
3.1.3 Checking the condensate siphon • Check the condensate siphon. Remove any dirt resi- dues and refill with clean water to the mark. LT.AL.W7H.000.0233 3.1.4 Checking the ignition electrode • Check the ionisation /ignition electrode for: - deposits (remove any white deposits with abrasive cloth); - the adjustment of the ignition electrode (between 3 and 4 mm);...
Remeha Avanta Plus Checking values O for natural gas H / L Fan speed (rpm) Boilertype Full load h3 Part load L3 ca. 4300 ca. 1300 ± 0.2 ± 0.3 ca. 5500 ca. 1300 ± 0.2 ± 0.3 ca. 6300 ca.
Page 45
1. Open the boiler • Isolate the 230 V supply at the switched spur and remove 230 V the fuse • Isolate the gas supply at the boiler gas valve • Remove the front panel (release the two screws at the bot- tom of the front panel, pull the bottom of the panel forward and lift off the two pins on the top of the main casing).
Page 46
Remeha Avanta Plus 3. Dismantling the front plate of the heat exchanger • Release the ignition transformer mounting plate and remove it completely. • Disconnect the electrical connection on the gas block. • Release the union nut from the gas pipe on the outlet to the gas block.
Page 47
5. Maintenance to the heat exchanger (CH) • Check the seal between the front plate and the heat exchanger and the insulation section. Replace sealing. • Handle the fragile front-plate insulation and the back-plate insulation of the heat exchanger with great care and do not let them get wet.
Page 48
Remeha Avanta Plus If a cleaning operation becomes necessary, please proceed as follows: • Turn off the mains cold water supply and drain off the resid- ual DHW; • Release two socket head screws and remove plate heat exchanger; • Clean plate heat exchanger with scale solvent (e.g. citric acid, pH 3);...
Page 49
7. Re-Assembling the boiler and checking the combustion • Re-assemble all the components in reverse order. • Remember to connect the fan plug again before it is com- pletely home on the front of the heat exchanger. • Check that the packing between the front plate and the heat exchanger has been fitted correctly.
Remeha Avanta Plus 4 ERRORS 4.1 General The Remeha Avanta Plus has an advanced control unit. The heart of this control unit is a microprocessor, the abc -con- ® trol which both controls and protects the boiler. If an error is detected anywhere in the boiler, it will lock-out and an error code will appear in the display.
Page 51
Error Description Possible cause Check / solution code Mains supply not correctly Control unit or Check that the power supply from the switch spur is properly earthed. é3 earth fault. earthed, if that is the case the control unit is faulty. Control unit faulty.
Page 52
Remeha Avanta Plus Error Description Possible cause Check / solution code Insufficient water. Check the minimum water pressure, read off the gauge and check for leaks. No through flow. Check that the pump is working; turn the spindle with a screwdriver,...
4.4 Error memory The Remeha Avanta Plus control unit has an error memory, in which the last 16 errors are stored. In addition to the error code (é and a number xx). The following data is also stored: • the number of times the error occurred (n and a number •...
5.1 General If, following the annual inspection or maintenance any part of the boiler is found to need replacing, use Remeha spare parts only or spare parts and materials recommended by Remeha. If the component to be replaced is covered by the Remeha...
Page 56
Remeha Avanta Plus Break down parts kit Part No Description Position S62743 Electrode ignition/ionisation 2004 S62728 Vent auto air bleed device 2010 S62746 Pump for 24s and 28c 2011 S62747 Pump for 35c and 39c 2011 S58733 Sensor temperature (2 pcs.)
Address : Kanaal Zuid 110 Town, Country : Postbus 32, NL-7300 AA Apeldoorn - hereby declares that the appliance(s) : Remeha Avanta Plus comply / complies with the specifications of the following EEC directives: EEG Directive: 90/396/EEG applied standards: (pr)EN 297...
- 97/23/EEC Pressure equipment directive (art. 3, sub. 3) Classification type for evacuation of the combustion products; according EN 483 7.2 Remeha factory test Before it leaves the factory, each Remeha Avanta Plus boiler is optimally adjusted and tested for: - electrical safety; - CO2- adjustment;...
8 TECHNICAL SPECIFICATIONS AND WORKING PRINCIPLE 8.1 Technical data Appliance type Remeha Avanta Plus system combi combi combi General modulating or on/off Boiler control Nominal output Pn (80/60°C) (CH) 21.6 21.6 29.4 33.3 Nominal output Pn (50/30°C) (CH) 23.0 23.0 31.3...
8.3 Working principle LT.AL.W7H.000.202 The Remeha Avanta Plus casing serves as a sealed air box, with air drawn in by the fan. On the outlet side of the fan is a venturi, into which a measured quantity of gas is injected based on the volume of air available.
DHW components (three way valve and plate heat exchanger). 8.3.1 Regulating The Remeha Avanta Plus is a fully modulating boiler and can be regulated using one or more of the following methods; 1. Open Therm – 2 wire interface compatible with the Remeha Celcia 15 room compensator and the Remeha Celcia 20 outside weather compensator or with any other proprietor’s...
’- control prevents unnecessary additional call outs. ® 8.3.3 Regulating the water temperature The Remeha Avanta Plus is fitted with an electronic tempera- ture regulator with flow and return temperature sensors. The flow temperature can be set to between 20 and 85°C, see 2.9.8 (factory setting 75°C).
9 EFFICIENCY DATA AND GAS EFFICIENCY LABELS 9.1 Annual efficiency Up to 110.5 % in relation to Hi at a load of 30% and a return temperature of 30°C. 9.2 Water-side efficiency Up to 98,3 % in relation to Hi at full load and an average water temperature of 70°C (80/60°C).
Page 65
Suggested Schematics with Control and Power Wiring details Outside Sensor Mount in a sheltered position on North facing wall Local temp control Under floor HTG 1020 230v Supply Local temp Mains cold water control Condensate 22mm Gas 22mm Under floor HTG High Temp Flow 22mm...
Page 66
Page AVANTA PLUS System Options ON / Off Control (Internal modulating) Typical “Y” plan - Heating and DHW using 230v controls Typical “W” plan - Heating and Priority DHW using 230v controls Typical “S” plan - Heating and DHW using 230v controls Internal time clock - Heating and Priority DHW using Celcia 10 and 3 way diverting valve kit Weather Compensation Control (Direct modulating using ‘OpenTherm®’) Simple weather compensated Heating with Priority DHW...
Page 67
AVANTA PLUS AVANTA 18v Controls for the Boilers AVANTA series are fully condensing boilers using gas / air ratio controls to provide full modula- tion and can be operated in the following modes: All boilers require a permanent 230v single phase 3 amp fused power supply plus controls as below: NOTE: The boiler is phase / neutral sensitive when used with external 230v controls ON / OFF Control - fixed flow temperature where the boiler modulates it’s output to match a fixed flow set point using simple 230v switching controls...
Page 68
AVANTA PLUS System Option 1 Typical “Y” plan Heating and DHW using 230v controls 2 Channel Time clock Room Stat Wiring Centre 230v Supply 22mm Return Condensate 22mm Gas 22mm Three way Mid position 'A' HTG valve - HTG and/or Flow high output Calorifier 'AB'...
Page 69
AVANTA PLUS System Option 2 Typical “W” plan Heating and Priority DHW using 230v controls 2 Channel Time clock Room Stat Wiring Centre 230v Supply 22mm Return Condensate 22mm Gas 22mm Three way Diverting 'A' HTG valve - HTG or DHW Flow high output Calorifier 'AB'...
Page 70
AVANTA PLUS System Option 3 Typical “S” plan Heating and DHW using 230v controls 2 Channel Time clock Room Stat Wiring Centre 230v Supply 22mm HTG Zone Valve Return Condensate c/w end switches 22mm Gas 22mm Flow DHW Zone Valve Cylinder Stat c/w end switches AVS0001...
Page 71
AVANTA PLUS System Option 4 Internal time clock - Heating and Priority DHW using Celcia 10 and 3 way diverting valve kit Room thermostat (Celcia 10) Mount in a reference room 1.5M above floor away from any heat scource 1020 230v Supply 22mm Return...
Page 72
AVANTA PLUS System Option 5 Simple weather compensated Heating with Priority DHW Two channel Outside Sensor time clock Mount in a sheltered position on North facing wall 230v Supply 22mm Return Condensate 22mm Gas 22mm Three way Diverting 'A' HTG Flow valve - HTG or DHW high output Calorifier...
Page 73
AVANTA PLUS System Option 6 Simple weather compensated Heating with room thermostat override (230v) and Priority DHW Outside Sensor Mount in a sheltered position on North facing wall Two channel time clock Room thermostat Mount in a reference room 1.5M above floor away from any heat scource 230v Supply 22mm...
Page 74
AVANTA PLUS System Option 7 Simple weather compensated Heating with room thermostat override (Celcia 10) and Priority DHW Outside Sensor Mount in a sheltered position on North facing wall Two channel time clock Room thermostat Mount in a reference room 1.5M above floor away from any heat scource 230v Supply...
Page 75
AVANTA PLUS System Option 8 Time / Weather compensated Heating with Priority DHW (Celcia 20 - Digital clock) Outside Sensor Mount in a sheltered position Time / Weather on North facing wall compensator (Celcia 20) Mount in a reference room 1.5M above floor away from any heat scource 230v Supply...
Page 76
AVANTA PLUS System Option 9 Simple room compensated Heating using the Celcia 15 and Priority DHW Modulating thermostat (Celcia 15) Two channel Mount in a reference room time clock 1.5M above floor away from any heat scource 230v Supply 22mm Return Condensate 22mm Gas...
Page 77
AVANTA PLUS System Option 10 Time / Room compensated Heating with Priority DHW (Celcia 20 - Digital clock) Time / Room compensator (Celcia 20) Mount in a reference room 1.5M above floor away from any heat scource 230v Supply 22mm Return Condensate 22mm Gas...
Page 78
AVANTA PLUS Combi Option 11 Timed heating with constant DHW using external time clock and room thermostat (230v) Room thermostat (230v) Two channel Mount in a reference room time clock 1.5M above floor away from any heat scource 230v Supply Mains cold water Condensate 22mm Gas...
Page 79
AVANTA PLUS Combi Option 12 Timed heating with constant DHW using internal time clock (230v) and room thermostat (Celcia 10) Room thermostat (Celcia 10) Mount in a reference room 1.5M above floor away from any heat scource 1020 230v Supply Mains cold water Condensate 22mm Gas...
Page 80
AVANTA PLUS Combi Option 13 External time clock with simple weather compensated Heating and constant DHW Two channel Outside Sensor time clock Mount in a sheltered position on North facing wall 230v Supply Mains cold water Condensate 22mm Gas 22mm Flow 22mm Return...
Page 81
AVANTA PLUS Combi Option 14 Internal time clock with simple weather compensated Heating and constant DHW Outside Sensor Mount in a sheltered position on North facing wall 1020 230v Supply Mains cold water Condensate 22mm Gas 22mm Flow 22mm Return AVS0019 Terminal 230v - 3 Amp...
Page 82
AVANTA PLUS Combi Option 15 Time / Room compensated Heating using the Celcia 20 (Digital clock) and constant DHW Outside Sensor Mount in a sheltered position on North facing wall Time / Weather compensator (Celcia 20) Mount in a reference room 1.5M above floor away from any heat scource 230v Supply...
Page 83
AVANTA PLUS Combi Option 16 External time clock with simple room compensated Heating using the Celcia 15 and constant DHW Modulating thermostat (Celcia 15) Two channel Mount in a reference room time clock 1.5M above floor away from any heat scource 230v Supply Mains cold water Condensate...
Page 84
AVANTA PLUS Combi Option 17 Internal time clock with simple room compensated Heating using the Celcia 15 and constant DHW Room compensator (Celcia15) Mount in a reference room 1.5M above floor away from any heat scource 1020 230v Supply Mains cold water Condensate 22mm Gas 22mm...
Page 85
AVANTA PLUS Combi Option 18 Time / Room compensated Heating with Priority DHW (Celcia 20 - Digital clock) Time / Weather compensator (Celcia 20) Mount in a reference room 1.5M above floor away from any heat scource 230v Supply Mains cold water Condensate 22mm Gas 22mm...
Page 86
AVANTA PLUS System Option 19 System boiler - Internal time clock with simple weather compensated UF Heating and priority DHW Outside Sensor Mount in a sheltered position on North facing wall Local temp control 230v Supply High output Calorifier c/w DHW thermostat or Under floor HTG sensor 1020...
Page 87
AVANTA PLUS Combi Option 20 Combi boiler - Internal time clock with simple weather compensated UF Heating and constant DHW Outside Sensor Mount in a sheltered position on North facing wall Local temp control Under floor HTG 1020 230v Supply Local temp Mains cold water control...
Page 88
AVANTA 18v System Only - Option 1 Typical “Y” plan Heating and DHW using 230v controls 230v Supply Check valve may 2 Channel be necessary Time clock Wiring Centre DHW thermostat 'B' DHW Three way Mid position 'AB' valve - HTG and/or 22mm Flow Room Stat...
Page 89
AVANTA 18v System Only - Option 2 Typical “W” plan Heating and Priority DHW using 230v controls 230v Supply Check valve may 2 Channel be necessary Time clock Wiring Centre DHW thermostat 'B' DHW Three way Diverting 'AB' valve - HTG or DHW 22mm Flow Room Stat...
Page 90
AVANTA 18v System Only - Option 3 Typical “S” plan Heating and DHW using 230v controls DHW thermostat 230v Supply Check valve may 2 Channel be necessary Time clock Wiring Centre DHW Zone valve c/w end switches 22mm Flow Room Stat HTG Zone valve 22mm c/w end switches...
Page 91
AVANTA 18v System Only Option 4 Simple weather compensated Heating with Priority DHW Outside Sensor Mount in a sheltered position on North facing wall 230v Supply 2 Channel DHW thermostat Time clock 'B' DHW 'AB' Three way Diverting valve - HTG or DHW 22mm Flow 'A' HTG...
Page 92
AVANTA 18v System Only Option 5 Simple weather compensated Heating with 230v room thermostat override and Priority DHW Outside Sensor Room thermostat Mount in a sheltered Mount in a reference room position on North 1.5M above floor away from facing wall any heat scource 230v Supply 2 Channel...
Page 93
AVANTA 18v System Only Option 6 Simple weather compensated Heating with volt free room thermostat override and Priority DHW Outside Sensor Room thermostat (volt free) Mount in a sheltered Mount in a reference room position on North 1.5M above floor away from facing wall any heat scource 230v Supply...
Page 96
Wokingham Berkshire RG41 2QP Tel : 0118 978 3434 Fax : 0118 978 6977 e Mail : boilers@broag-remeha.com Web Site : www.avantaplus.com www.uk.remeha.com The schematics in this brochure are for guidance only and do not constitute a design Art No : 113046 The content in this brochure is based on the latest information available at date of publication and may be subject to revisions.
Page 97
AVANTA PLUS 28 Combi - Gas Council No 47-673-02 39 Combi - Gas Council No 47-673-04...
Page 98
Remeha Avanta plus Combi 1 Part No. Description Position S62748 Casing front panel 1001 S62708 Screw M5 x 20 (20 pcs.) 1002 S62724 Fixing strip heat exchanger 24/28kW 1003 S62723 Fixing strip heat exchanger 30/39kW 1003 S62709 Sealing for front casing (10 m.)
Page 101
Remeha Avanta plus Combi 3 Posi- Part No. Description tion S62745 Fan assembly 230V 3001 S58684 Fan assembly 24V 3001 S58683 Venturi 3002 S62767 Air supply silencer 3003 S62758 Piping set gas 24/28kW 3004 S62759 Piping set gas 30/39 kW...
Page 102
Remeha Avanta plus Combi 4 Part No. Description Position S62734 Control board 4001 S62739 Display print board 4002 S62750 Transformer ignition 4003 S62769 Cable set 4004 S62737 Control panel front 4005 S62735 Controlpanel back 4006 S62710 Self tapping screw 3.5 x 10 (50 pcs.)
Page 103
Remeha Avanta plus Combi 5 Posi- Part No. Description tion S62776 Plate heat exchanger 30/39 5001 S62775 Plate heat exchanger 24/28 5001 S59132 Actuator three way valve 5002 S62773 Hydro block right C30/39 5003 S62774 Hydro block right C24/28 5003...
Page 105
Remeha Avanta plus Combi 9 Posi- Part No. Description tion S62784 Gas pipe for stand off frame 22mm 9001 S62785 Pipe HTG F/R connections 22mm 9002 S62787 Pipe DHW return connection 15mm 9003 S62790 Stand off frame (sparepart) 9004 S56157 Gasket 18.3 x 12.7 x 2 mm.
Page 106
Wall mounting plate and valve set KT397 Part No Description Position Qty in kit S56157 Gasket 18.3 X 12.7 X2 mm. (10 pcs.) 5022 S62730 Gasket 27.4x18.2x2 (20 pcs.) 5021 S62752 Gas cock 3015 S62760 Pipe and nut gas 3017 S62761 Connection tail HTG 22mm 5026...
Page 107
AVANTA PLUS 24 System - Gas Council No 41-288-05...
Page 108
Remeha Avanta plus System 1 Part No. Description Position S62748 Casing front panel 1001 S62708 Screw M5 x 20 (20 pcs.) 1002 S62724 Fixing strip heat exchanger 24/28kW 1003 S62709 Sealing for front casing (10 m.) 1004 S62711 Grommet 15mm id x 48mm od (5 pcs)
Page 109
Remeha Avanta plus System 2 Posi- Part No. Description tion S62777 Heat exchanger 24/28kW 2001 S62779 Heat exchanger front plate 24/28kW 2002 S62741 Burner 24/28kW 2003 S62743 Electrode ignition/ionisation 2004 S59118 Glass inspection set 2005 S62744 Insulation front plate heat exchanger...
Page 111
Remeha Avanta plus System 3 Part No. Description Position S58684 Fan assembly 24V 3001 S58683 Venturi 3002 S62767 Air supply silencer 3003 S62758 Piping set gas 24/28kW 3004 S58685 Gas combination block 3005 S45182 Gasket for flue fan (10 pcs.)
Page 112
Remeha Avanta plus System 4 Part No. Description Position S62734 Control board 4001 S62739 Display print board 4002 S62750 Transformer ignition 4003 S62769 Cable set 4004 S62737 Control panel front 4005 S62735 Controlpanel back 4006 S62710 Self tapping screw 3.5 x 10 (50 pcs.)
Page 113
Remeha Avanta plus System 5 Posi- Part No. Description tion S62771 Hydro block right system 5003 S62770 Hydro block left system 5004 S58730 O-ring 17Ø x 4 (10 pcs.) 5007 S62715 Gasket 14.5Ø x 8.5 x 2 (10 pcs.) 5010 S59141 Screw M5 x 18 (15 pcs.)
Page 114
Remeha Avanta plus System 9 Posi- Part No. Description tion S62784 Gas pipe for stand off frame 22mm 9001 S62785 Pipe HTG F/R connections 22mm 9002 S62790 Stand off frame (spare part) 9004 S56157 Gasket 18.3 x 12.7 x 2 mm. (10 pcs.)
Page 115
Inspection / Service and Breakdown Parts Inspection visit - No parts should be necessary Service visit - Maintenance Set (Gasket and seal kit) Part No S62782 Breakdown visit - Major components kit s Part No : KT398 covers all boilers Part No : S100034 covers 24s &...
Page 116
KT398 Breakdown Parts Kit for Avanta Plus - 24s / 28c and 39c Not illustrated Breakdown Parts Kit for Avanta Plus -- Broag Part No KT398 - Contents Part No Description Position S62743 Electrode ignition/ionisation 2004 S62728 Vent auto air bleed device 2010 S62746 Pump for 24/28 kW...
Page 117
Berkshire RG41 2QP Tel : 0118 978 3434 Fax : 0118 978 6977 e Mail : boilers@broag-remeha.com Web Site : www.uk.remeha.com The content in this brochure is based on the latest information available at date of publication and may be subject to revisions.
Remeha Avanta Plus 28c Remeha Avanta Plus 39c Remeha Avanta Plus 24s User guide Remeha Avanta Plus...
Page 119
TIPS FOR MAINTAINING THE BOILER AND CENTRAL HEATING SYSTEM ENERGY SAVINGS AND ENVIRONMENTAL PROTECTION 9.1 Tips on saving energy 9.2 Room thermostats and settings 10 EXPANDING THE CENTRAL HEATING SYSTEM TECHNICAL DATA 12 APPENDICES 12.1 Remeha factory test 12.2 EC regulations...
Page 120
INTRODUCTION The Remeha Avanta Plus range are a series of fully condens- ing high-efficiency central heating boilers, available in the fol- lowing types: • Remeha Avanta Plus 28c and 39c - with integrated domestic hot water system (combi-type) • Remeha Avanta Plus 24s...
Page 121
Remeha Avanta Plus SAFETY This User Guide uses specific terms and pictograms to draw particular attention to instructions. Broag does this to enhance the user’s safety, to prevent problems and ensure the technical reliability of the boiler. General safety The following pictograms are used in this Installation and User manual to specifically draw certain points to your attention: ...
Page 122
Service once a year The boiler must be inspected once a year by a qualified engi- neer to ensure optimum, safe operation. Repairs Repairs to the Avanta Plus must only be carried out by a quali- fied engineer and in accordance with the applicable regula- tions and (safety) requirements.
Remeha Avanta Plus Controls The Remeha Avanta Plus is a fully modulating boiler and can be controlled using one or more of the following methods; Open Therm – 2 wire interface compatible with the Remeha Celcia 15 room compensator and the Remeha Celcia 20 outside weather compensator or with any other OpenTherm control.
Page 124
Normal start-up procedure Activate the switch on the spur unit for mains supply; the boiler will run the start-up program. - A display test will briefly appear showing all segments of the display. f[ xx software version; LT.NL.W6H.000.066 p[ xx parameter version; LTNLW6H000066A - A venting cycle of 2 minutes now follows, the version numbers will be displayed alternately;...
Page 125
Remeha Avanta Plus • Press the [+] key again until t4 appears and, for exam- ple, 18 (18°C), the current outside temperature; • Press [+] key again until fl appears and e.g. ^0 (6uA), the present ionisation current; • Press [+] key again until ñf appears and e.g. 30 (3000 rpm), the present fan speed;...
Page 126
Changing P3 setting: boiler regulation (domestic hot water and central heating mode) DHW use only If the Remeha Avanta Plus is, for example, only being used to provide domestic hot water, switch the boiler regulation system LT.NL.W6H.000.071 for the central heating system off.
Page 127
Remeha Avanta Plus In the comfort mode the boiler will be seen to run occasionally even if time clocks are in the off position. 0 = Comfort mode 1 = Eco mode 2 = regulated by controller (= factory setting) Change the mode as follows: •...
Page 128
P6 setting: display on/off Display off Operating codes on display change constantly as a result of different operating modes. If boiler is in visible location, this can be annoying. Display is therefore set to ‘Automatically off’. Display goes off after 3 minutes, i.e. one or two dots remain visible to indicate that boiler is operational (two dots) or non- operational (one dot).
Page 129
Remeha Avanta Plus PROBLEMS WITH BOILER AND/OR CENTRAL HEATING SYSTEM See par. 4.1 for problems with the boiler and/or central heat- ing system which the user can resolve himself. See par.4.2 for error codes which have to be remedied by the installer. Other problems are listed in the error table in par.
Other problems Problem or error Possible cause Solution/points to check A. No hot water when tap is Check whether the boiler is switched on Boiler is not running turned on check whether a fuse has blown; check whether the gas tap is properly open. Water pressure is too low (less than 1 Check mains cold water pressure bar)
Page 131
230 V Topping up the central heating system The Remeha Avanta Plus runs best with a water pressure of between 1.5 and 2 bar (see the water-pressure meter at the bottom of the boiler). If the water pressure falls below 1 bar, the system has to be topped up with water.
Page 132
• When topping up, use a filling loop, a cloth and a bleed key. LTALW7H000229a LT.AL.W7H.000.229 Top the Avanta Plus up as follows: • Attach the filling loop between mains cold water inlet and CH return. LT.AL.W7H.000.235 LTALW7H000235b • Turn the filling loop valve open by a quarter turn. ...
Page 133
Remeha Avanta Plus • Turn the filling loop valve off again once the water-pres- sure meter shows 2 bar. • Remove the filling loop after topping up the system. 2 bar LT.AL.W7H.000.237 LTALW7H000237b Air gets into the central heating system when topping up with water.
Page 134
Bleeding the central heating system A gurgling noise in pipes and/or radiators which only partially heat up indicate(s) air in pipes and radiators. The central heat- ing system has to be bled. Before bleeding, the following preparations have to be made: •...
Remeha Avanta Plus • Hold a cloth against the bleed nipple, open the nipple with a bleed key and allow air to escape slowly. LTNLPER000017a LTNLPER000018a LT.NL.PER.000.017 + LT.NL.PER.000.018 • Wait until water comes out of the bleed valve (without spluttering) and then close the bleed nipple.
Page 136
• Set the room thermostat to the desired temperature and close the radiator valves in those rooms which do not have to be heated. LTALW7H000212a LTNLPER000025a LT.AL.W7H.000.212 + LT.NL.PER.000.024 + LT.NL.PER.000.025 LTNLPER000024A Draining the central heating system Draining the central heating system may be necessary if the radiators have to be replaced, if there is a serious leak, or if there is a risk of freezing.
Page 137
Remeha Avanta Plus • Connect a drain hose to the lowest drainage valve; place the other end of the hose in a drain or in a place where drained system water will not cause any damage. LTALW7H000216a LT.AL.W7H.000.216 • Open the drainage valve by turning it through a quarter- turn and allow the central heating system to empty.
DISABLING THE BOILER The boiler must be disabled before any maintenance or repairs are carried out. If the central heating system is not used for a long time (during the holidays, for instance, or periods of milder weather) it is advisable to disable the boiler. Boiler with frost protection, during longer periods of non- •...
Remeha Avanta Plus ENABLING THE BOILER • Check the boiler water pressure. If the water pressure is less than 1 bar, the system has to be topped up with water, see par.5.1. 1,5 ... 2 bar LTALW7H000211a LT.AL.W7H.000.211 • Switch on the boiler at the fused spur unit; the boiler will run the start-up program.
TIPS FOR MAINTAINING THE BOILER AND CENTRAL HEATING SYSTEM • Check the water pressure of the central heating system several times a year. If the water pressure is too low, top up with water (see par. 5.2). The optimum pressure is between 1.5 and 2 bar.
Page 141
Remeha Avanta Plus • Clean the outside of the boiler with a damp cloth and mild detergent. LT.AL.W7H.000.221 LTALW7H000221a Cleaning The inside of the boiler may only be cleaned by the installer. Service contract Soiling may reduce the performance of boiler components.
• tips on correctly setting the room thermostat. Tips on saving energy • Ensure that the room in which the Remeha Avanta Plus is fitted is well ventilated. Do not seal up ventilation open- ings. • Place radiator foil on walls behind radiators; this reflects heat which is otherwise wasted.
Remeha Avanta Plus EXPANDING THE CENTRAL HEATING SYSTEM Connecting thermostats A 2-wire on/off thermostat (e.g. the Remeha Celcia 10) or to a modulating thermostat (e.g. the Remeha Celcia 15 or 20) can be connected to the Avanta Plus. Consult the installer about connecting the thermostat you have chosen.
Page 144
APPENDICES 12.1 Remeha factory test Before it leaves the factory, each Remeha Avanta Plus boiler is optimally adjusted and tested for: - electrical safety; - CO2- adjustment; - hot water function; - water tightness; - gas tightness; - automation parameters.
Page 146
Operating instructions for the built in Two Channel Digital electronic time clock Issue No. 1 Date: 8 December 2005...
Page 147
Factory default set times ................. 2 General ......................3 Safety Notes ...................... 3 Timer Features ....................3 Position of Timer in boiler ................4 Description of buttons and display..............4 Initilising Timer ....................6 Setting switching programs for P1 - Heating ..........6 Setting switching programs for P2 - DHW............
Internal time clock for the AVANTA PLUS Boilers Built in Two Channel Timer Kit for System Boiler - Part No S62432 Built in Two Channel Timer Kit for Combi Boiler - Part No S62432C Electronic digital timer with Day/Week programe function enables operation on individual days or groups of days (e.g.
Page 149
Position of Timer in boiler when fitted Description of setting buttons and display...
Page 150
1 to 5 Power and switch connections (cable and plug X2 supplied as std) LCD Display Sliding three position Switches Three position sliding switch to set operating mode Permanently ON (Current time of day must be set before this is active) AUTO Switches ON and OFF in accordance with programmed switch times Permanently OFF Three position sliding switch to set Current time/day and switching times...
Page 151
Initialising Timer On removal from box the display will appear as shown above and MUST be Initialised be- fore it can be used in any of the modes including manual override using switch 7 to I To initialise timer set with the day pointer under M Set program switches 7 to AUTO and 8 to RUN Press HR and MIN buttons together for 3 seconds - display changes to 0:00 Set current time - button HR for the hour and MIN for minutes...
Page 152
10. Checking the Timer settings To check and edit existing times or to add new times ⇒ Set program switches 7 to AUTO and 8 to P1 or P2 - the display will show the first ON time set with the day or group of days it applies to ⇒...
Page 153
Berkshire RG41 2QP Tel : 0118 978 3434 Fax : 0118 978 6977 e Mail : boilers@broag-remeha.com Web Site : www.uk.remeha.com The content in this brochure is based on the latest information available at date of publication and may be subject to revisions.