Page 1
NOTE: The settings in this manual are for retrofit applications. If this burner is being installed on a packaged unit (burner comes with the boiler or furnace), then follow the settings on the OEM page, as settings may differ. Burner is set for a single line system. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
EXPLODED SPARE PARTS LIST................18 SPARE PARTS LIST ...................... 19 PACKAGE LIST Your Riello 40 burner should include the following parts. Please check to make sure all parts are present before beginning the installation. QTY. DESCRIPTION (parts bag) QTY. DESCRIPTION (carton)
20. Mounting flange with gasket SERIAL NUMBER IDENTIFICATION The Riello 15 character serial number, example, 99 A 8511111 00025, is identified as follows: 99 = last two digits of the year of manufacture; A = BI-week of manufacture; 8511111 = burner product code;...
1) Universal flange bolted to Boiler/Furnace unit. 2) Semi-flange collar bolted to Boiler/Furnace unit. 3) Universal flange mounted to optional Pedestal mount, where flange mounting direct to appliance is not possible. Pedestal kit must be ordered separately. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
NOTE: A suggested method for creating mounting bolt holes in the mounting gasket: Hold the gasket against the appliance mounting bolts using the mounting flange for proper positioning. Lightly tap the flange with a hammer to form the holes. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
WARNING: DO NOT activate burner until proper oil line connections have been made, or failure of the pump shaft seal may occur. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
120Vac to the connection terminal. The maximum allowable current draw on this terminal (4) is 1 Amp. WARNING: If a neutral or ground lead is attached to this terminal, the CONTROL BOX on the burner will be damaged should lockout occur. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
Model F5). D) Loosen SCREW (2), and then slide the complete drawer assembly out of the combustion head as shown. E) To insert drawer assembly, reverse the procedure in items A to D above. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
All pump port threads are British Parallel Thread design. Direct connection of NPT threads to the pump will damage the pump body. Riello manometers and vacuum gauges do not require any adapters, and can be safely connected to the pump ports. An NPT (metric) adapter must be used when connecting other gauge models.
Be sure there are no air leaks or blockages in the piping system. Any obstructions in the return line will cause failure of the pump shaft seal. Do not exceed the pipe lengths indicated in the tables above. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
8) Reinstall the air tube cover and nozzle line The burner can now be started normally WARNING: Omitting steps 2 and 3 will result in a collection of unburned oil in the combustion chamber creating a hazardous situation upon burner startup. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
NOTE: Variations in flue gas, smoke, CO and temperature readings may be experienced when burner cover is put in place. Therefore, the burner cover must be in place when making final combustion instrument readings, to ensure proper test results. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
BTU/hr. or US gph input rating of the appliance. COMBUSTION CHAMBER Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropriate installation codes (e.g. CSA B139 or NFPA #31). C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
The amulet has been sized to fit Riello Model 40 sizes F3 and F5 plus the Riello Model R35. When installing this amulet, handle it carefully. Do not exert undue pressure when pushing the amulet over the combustion tube.
In most localities, a number 14 wire should be used inside a metal conduit. The system should be grounded. A service switch should be placed close to the burner on a fireproof wall in an easily accessible location. C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
RIELLO SPARE PARTS LIST F3 & F5 • Indicates applicable model for each part. CODE F3 F5 DESCRIPTION CODE F3 F5 DESCRIPTION 3007232 • Burner Back Cover 26 C7001029 • • Primary Control 3007233 • Burner Back Cover 27 3005854 •...
Page 20
Please complete this form, fax it or mail it at the address/fax above, or send an e- mail with the information listed below to: techservices@riellocanada.com C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
Page 21
35 Pond Park Road 2165 Meadowpine Blvd Hingham, MA 02043 Mississauga, ON L5N 6H6 Phone 781-749-8292 Phone 905-542-0303 Toll Free 800-992-7637 Toll Free 800-387-3898 Fax 781-740-2069 Fax 905-542-1525 www.riellousa.com www.riellocanada.com Technical Support Hotline 1-800-4-RIELLO 1-800-474-3556 C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006...
Need help?
Do you have a question about the F3 and is the answer not in the manual?
Questions and answers