Caution
- Ensure the foam seal is sealing up
against the front face of the builders
opening.
- The appliance must be fully sealed
to the front of the builders opening.
Failure to do so will result in a spillage
problem.
• If there are any gaps fill them with a
high temperature silicone sealant or
a non-combustible sealant such as fire
cement.
• There must be no gaps between the
Slips and the wall or appliance.
• Looking through the hole in the
top of the appliance and up into
the Chimney, check that there is
no obstruction and that no part of
Chimney is closer than 30mm to the
Debris Shield to ensure the flow of
Combustion Products passes unaf-
fected.
• Connect the debris shield to the flue
spigot by using the self tapping screws
• Screw the flue spigot back in position
using the self-tapping screws.
Caution
The sealing surfaces of the spigot must
be free of debris.
• Screw the cover plate back in posi-
tion using the self-tapping screws.
• Connect the appliance according the
installation manual.
Caution
Do not ignite the appliance until it is
fully installed.
• Replace the glass pane after installing
the wood set according the installa-
tion manual.
INSTRUCTIONS FOR INSTALLATION
Spillage Test
The spillage test is intended to check
the draft in the chimney. The spillage
test can only be
performed if the appliance is fully
installed. Use the User Manual to
ignite the appliance.
Use a pressure meter to ensure ter-
minal draught is sufficient (see table)
Perform the test as follows:
• Close all doors and windows in the
room in which the appliance has
been placed.
• Remove the bolt of the top of the
appliance connection.
• Connect the pressure meter using a
silicon tube to the appliance connec-
tion (see figure 6)
• Ignite the main burner.
• Monitor the pressure from a cold
start of the appliance.
• Make sure the appliance is at its
highest level.
• If the appliance shut down after a
cold start, course by a spillage prob-
lem: Check for a lack of Adequate
Ventilation. A Quick check is to
slightly op en a door or window to
see if this corrects the spillage prob-
lem.
Caution
Disconnect the silicon tube before
the appliance get too hot.
Fitting into a Conventional Class1 Chimney
7