Advertisement

Models
Nominal cooling capacity
kW
Nominal heating capacity
Power source
Cooling
Power consumption
kW
Heating
Cooling
Running current
A
Heating
Sound power level
dB(A)
Sound pressure level
dB(A)
Exterior dimensions
mm
Height x Width x Depth
Net weight
kg
Refrigerant equipment
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor
W
Starting method
Air flow(Standard)
m
3
/min
External static pressure
Pa
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Refrigerant
Drain pump
Drain hose
Connectable with VP25 (Standard)
Insulation for piping
Necessary (both Liquid & Gas line)
Accessories
Notes
(1) The data are measured at 33℃DB 28℃WB (68%RH) during cooling and 0℃DB -2.9℃WB (50%RH) during heating (no frost).
(2) Temperature range of outdoor air must be 20 - 40℃DB (32℃WB or less) during cooling and -10℃ - 24 ℃DB during heating.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
(5) The factory E.S.P. setting is set within the range of 10 -120Pa. When SW8-4 is turned to "ON", E.S.P. setting range can be c hanged to 10 -200Pa. (For RC-EX1A and RC-E5 only)
FDU650FKXZE1
9.0
6.5
220-240V 50Hz / 220V 60Hz
220-240V 50Hz / 220V 60Hz
0.24 - 0.25 / 0.24
0.24 - 0.25 / 0.24
1.80 - 1.70 / 1.80
1.80 - 1.70 / 1.80
55
Hi:31
280 × 950 × 635
34
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Electronic expansion valve
Electronic expansion valve
Centrifugal fan × 2
130
Direct line start
Hi:11
200 (at 11 m
3
/min)
Possible
Procure locally
Rubber sleeve (for fan motor)
Rubber sleeve (for fan motor)
Polyurethane form
Remote control switch(Option)
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Wired: RC-EX1A, RC-E5,RCH-E3
Wireless: RCN-KIT3-E
Wireless: RCN-KIT3-E
Thermostat by electronics
Thermostat by electronics
Overload protection for fan motor
Overload protection for fan motor
Frost protection thermostat
Frost protection thermostat
Liquid line: φ9.52 (3/8")
Liquid line: φ9.52 (3/8")
Gas line: φ15.88 (5/8")
Gas line: φ15.88 (5/8")
Flare piping
R410A
Built-in Drain pump
Connectable with VP25 (Standard)
Necessary (both Liquid & Gas line)
Drain hose
FDU1100FKXZE1
FDU1800FKXZE1
14.0
10.5
220-240V 50Hz / 220V 60Hz
0.35 - 0.36 / 0.35
1.16 - 1.20 / 1.16
0.35 - 0.36 / 0.35
1.16 - 1.20 / 1.16
2.30 - 2.20 / 2.30
6.80 - 6.50 / 6.80
2.30 - 2.20 / 2.30
6.80 - 6.50 / 6.80
62
Hi:37
Hi:42
280 × 1,370 × 740
379 × 1,600 × 893
54
Louver fin & inner grooved tubing
Electronic expansion valve
Centrifugal fan × 3
Centrifugal fan × 3
100 + 200
130 + 350
Direct line start
Direct line start
Hi:18
Hi:30
200 (at 18 m
3
/min)
200 (at 30 m
Possible
Possible
Procure locally
Procure locally
Rubber sleeve (for fan motor)
Polyurethane form
Polyurethane form
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Wireless: RCN-KIT3-E
Thermostat by electronics
Overload protection for fan motor
Frost protection thermostat
Liquid line: φ9.52 (3/8")
Gas line: φ19.05 (3/4")
Flare piping
Brazing
R410A
R410A
Built-in Drain pump
Connectable with VP25 (Standard)
Necessary (both Liquid & Gas line)
Drain hose
Drain hose
FDU2400FKXZE1
22.4
28.0
16.0
21.5
220-240V 50Hz / 220V 60Hz
1.16 - 1.20 / 1.16
1.16 - 1.20 / 1.16
6.80 - 6.50 / 6.80
6.80 - 6.50 / 6.80
68
70
Hi:45
379 × 1,600 × 893
89
89
Louver fin & inner grooved tubing
Electronic expansion valve
Centrifugal fan × 3
130 + 350
Direct line start
Hi:40
3
/min)
200 (at 40 m
3
/min)
Possible
Procure locally
Rubber sleeve (for fan motor)
Polyurethane form
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Wireless: RCN-KIT3-E
Thermostat by electronics
Overload protection for fan motor
Frost protection thermostat
Liquid line: φ 9.52 (3/8")
Gas line: φ 22.22 (7/8")
Brazing
R410A
Connectable with VP25 (Standard)
Necessary (both Liquid & Gas line)
Drain hose
Adapted to RoHS directive