Bild ein. Sie finden die Bilder auf der Referenzseite 14: Buderus Product groups. Anordnung im Rahmen: - Tops - Left sides Logamax plus GB162 Gas condensing boiler Output range from 2.7 kW to 100 kW Heat is our element...
........31 1.1.1 Features Logamax plus GB162 ....5 Logamatic EMS control concept .
Page 3
Logamax plus GB162-45 ....91 freshwater module ......75...
Page 4
Ø 80 mm or Logamax plus GB162 up to 35 kW ..120 Ø 110 mm ......160 Routing flue gas via flexible flues inside a 11.1.2 Components for individual appliances,...
SU160 W, SU200 W and SU300 W (not applicable to GB162-65/80/100) Burner • Highly premixing ceramic linear radiant burner for the cleanest combustion Table 1 Benefits and key features Logamax plus GB162 6 720 645 821 (2010/09) – Logamax plus GB162...
• Simplified commissioning and service through the service menu of the RC35 programming unit; minimum clearances to the side are not required Table 2 Benefits and key features Logamax plus GB162-25 T40S 6 720 645 821 (2010/09) – Logamax plus GB162...
• Booster function for DHW 25 kW appliance with 33 kW DHW output Burner • Highly premixing ceramic linear radiant burner for the cleanest combustion Table 2 Benefits and key features Logamax plus GB162-25 T40S 1.2.2 Logamax plus GB162-25 T40S selection aid...
Technical description Equipment level of the gas condensing boilers 2.1.1 Equipment overview Logamax plus GB162-15, GB162-25, GB162-35 and GB162-45 The wall mounted Logamax plus GB162-15/25/35/45 gas condensing boilers have been tested in compliance with the Gas Appliances Directive 90/396/EEC. The requirements of standards EN 483 and EN 677 were taken into consideration.
GAS AKO VS RS VK RK 6 720 642 463-04.1il Fig. 4 Selected components and assemblies of the Logamax plus GB162-25 T40S (connections not visible fig. 8, page 13) AKO Condensate outlet (not visible) Condensate pan AW DHW outlet (not visible)
Page 11
• Copper-soldered stainless steel plate heat exchanger with 33 kW constant output • Water flow sensor to record the amount of water Control components • Universal burner control unit UBA3.5 • Logamatic BC10 base controller 6 720 645 821 (2010/09) – Logamax plus GB162...
Fig. 7 Function scheme Logamax plus GB162-45 GB162-15/25/35 (key page 14) (key page 14) GB162-25 T40S 6 720 642 463-08.1il Fig. 8 Function scheme Logamax plus GB162-25 T40S (key page 14) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 14
Technical description ETA-plus system in the Logamax plus GB162 GB162-50/65/80/100 The ETA-plus system of the Logamax plus GB162 gas condensing boilers minimises the overall running costs through optimum energy utilisation. Part of the ETA-plus system is a highly effective lamellar tube heat exchanger with ALUplus technology.
A high efficiency UPM 15-70 2W pump In contrast to conventional boilers with electric spark (accessory) can be fitted inside the boiler. The control ignition or a pilot flame, the Logamax plus GB162 gas functions differential pressure-dependent and condensing boilers operate with an incandescent ignition output-dependent control are available.
Ø80/125 1000 VS RS 6 720 642 463-10.1il Fig. 10 Dimensions and connections Logamax plus GB162-15/25/35/45 (dim. in mm) AKO Condensate outlet Ø 30 GAS Gas connection R½ Boiler return Ø 28 (connection, compression fitting R1) DHW cylinder return (connection fitting R¾ ) Boiler flow Ø...
Page 17
Standby heat loss at 70 °C flow 0.68 0.53 temperature Permissible operating pressure, boiler 3 (4) Water content, heat exchanger Pump run-on time, adjustable at the Logamatic BC10 1–60 base controller Table 4 Specification Logamax plus GB162-15/25/35/45 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 18
5) Captured at the flue connector 6) With integral heating circuit pump UPM 15-70 7) Measured in a sound-proof room at a distance of 1 m from the boiler (with concentric flue system) 6 720 645 821 (2010/09) – Logamax plus GB162...
1000 VS RS 6 720 642 463-11.1il Fig. 11 Dimensions and connections Logamax plus GB162-25 T40S (dim. in mm) AKO Condensate outlet Ø 30 AW DHW outlet Ø 15 (connection, compression fitting R½ ) Cold water inlet Ø 15 (connection, compression fitting R½...
Page 20
100 % 10.7 (15.1) 80/60 °C °C 65 (75) 5)6) Flue gas temperature at system temperature (full load) 50/30 °C °C content at full load Table 5 Specification Logamax plus GB162-25 T40S 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 21
5) Factor for sizing the flue system to DIN-EN 13384-1 at 6) Captured at the flue connector 7) Measured in a sound-proof room at a distance of 1 m from the boiler (with concentric flue system) 6 720 645 821 (2010/09) – Logamax plus GB162...
VA/RA GAS A GAS A 6 720 642 463-12.1il Fig. 12 Dimensions and connections Logamax plus GB162-50/65/80/100 (dim. in mm) Condensate outlet; external diameter, fem. connection 24 mm GAS A Gas connection, connection set G1 (fem.) GAS K Gas connection, boiler G1 (fem.) Return connection set G1½...
Page 23
Standby heat loss at 70 °C flow 0.05 0.05 0.05 0.06 temperature Permissible operating pressure, boiler Water content, heat exchanger Pump run-on time, adjustable at the Logamatic BC10 1–60 base controller Table 6 Specification Logamax plus GB162-50/65/80/100 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 24
6) When the output is limited to 50 kW 7) Excluding pump 8) Measured in a sound-proof room at a distance of 1 m from the boiler (with concentric flue system) 6 720 645 821 (2010/09) – Logamax plus GB162...
– 5 231 035 5 231 045 Table 7 Specification Logalux S135 RW and S160 RW combined with Logamax plus GB162 1) Heating water flow temperature/DHW outlet temperature/cold water inlet temperature 2) Height including cylinder cover (accessory), excl. adjustable feet 3) At cylinder temperature 65 °C and room temperature 20 °C...
7747011 041 7 747 003 781 7 747 003 782 7 747 003 783 Table 8 Specifications Logalux S120 W and SU... W combined with Logamax plus GB162 1) Heating water flow temperature/DHW outlet temperature/cold water inlet temperature 2) Minimum room height for the replacement of the magnesium anode 3) For the Logalux S120 W, we recommend the connection of the DHW circulation line in the cold water inlet 4) At cylinder temperature 65 °C and room temperature 20 °C...
ΔT must be output < 25 K Table 12 Operating conditions Logamax plus GB162 1) Heating circuit control with mixer improves the control characteristics; particularly recommended for systems with several heating circuits 6 720 645 821 (2010/09) – Logamax plus GB162...
Programming unit RC35 Programming unit SM10 Solar module UBA3.5 Universal burner control unit VM10 Control module WM10 Low loss header module Number can be selected in accordance with the system configuration 6 720 645 821 (2010/09) – Logamax plus GB162...
6 720 642 463-19.1il Fig. 19 Position of the RC25 or RC35 programming units or the external room temperature sensor in the reference room (dim. in m) Required clearance below the RC25 or RC35 6 720 645 821 (2010/09) – Logamax plus GB162...
19). 6 720 642 463-21.1il Fig. 22 Separate room temperature sensor for external installation as an alternative to the integral room temperature sensor of the RC35 programming unit (dim. in mm) 6 720 645 821 (2010/09) – Logamax plus GB162...
Fig. 24 Back of the Logamatic BC10 base controller which makes further convenient control functions with jumper for limiting the output to 11 kW or available ( fig. 23, pos. 2). 50 kW (for the GB162-65) Jumper 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 35
• “Reset” button for resetting the burner in the event of lockout faults ( fig. 25, pos. 12) • Emergency operation • Limiting the output of the gas condensing boiler and setting system parameters via the software 6 720 645 821 (2010/09) – Logamax plus GB162...
Key with LED for activating once only DHW heating or for selecting the DHW temperature Flap to cover the second control level Key for selecting the heating program Key for adjusting the time and the day of the week 6 720 645 821 (2010/09) – Logamax plus GB162...
For the end user, two control levels are available, divided into standard functions and extended functions. At the service level, contractors can make adjustments, e.g. for the heating circuits or DHW heating. 6 720 645 821 (2010/09) – Logamax plus GB162...
Wall mounting bracket with strain relief for connecting cables 6 720 642 463-26.1il Fig. 28 Quick installation set for heating circuit with high efficiency pump, efficiency category A (with integral EMS module) 6 720 645 821 (2010/09) – Logamax plus GB162...
This High-Flow/Low-Flow operation enables demand-optimised DHW heating. When the system is still cold, the system initially produces DHW quickly from the solar yield for “optimum convenience.” When sufficient 6 720 645 821 (2010/09) – Logamax plus GB162...
4.5.7 Logamatic Easycom telecontrol modem The WM10 low loss header module regulates the In the form of the Logamatic Easycom, Buderus offers an hydraulic separation between the boiler and the affordable telecontrol modem for remote monitoring and consumer circuits. This hydraulic separation can be setting of parameters in small and medium-sized heating achieved with a low loss header or via a heat exchanger.
Input Set flow temperature State of the voltage (gas condensing Combined with the Logamax plus GB162, the EM10 fault boiler) condensing message module provides two standard functions: boiler • Output of a fault indication with a 230 V signal (with potential) (buzzer, signal lamp, max.
Remote configuration Second solenoid valve, e.g. for LPG (VM10 control module) Table 15 Selection aid for the possible equipment 'levels of the Logamax plus GB162 with components of the Logamatic EMS control system 1) As a remote control for heating circuit 1, if the RC35 programming unit is installed inside the appliance or as a remote control for heating circuit 2.
Fig. 35 Logamatic 4121 control unit with standard CM431 controller 'module equipment level MEC2 programming unit Control unit ON/OFF switch ZM424 central module Fuse CM431 controller 'module MEC2 programming unit Control unit ON/OFF switch Fuse 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 44
1) When using the FM445 function module, DHW heating through the ZM424 central module will be disabled. The modules of the Logamatic EMS cannot be controlled via the Logamatic 4000 control system. 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 45
Fig. 38 Position of the wall mounting bracket for the For further details, see the technical guide MEC2 programming unit in the reference room concerning the “modular Logamatic 4000 (dim. in mm) control system”. Required clearance below the MEC2 6 720 645 821 (2010/09) – Logamax plus GB162...
Table 17 Decision-making aids for the selection of integral or separate DHW heating 1) In the case of adequate room height, recommended with the Logalux S120 W DHW cylinder (below) Recommended Limited recommendation – Not recommended 6 720 645 821 (2010/09) – Logamax plus GB162...
At a total hardness of the potable water of 15° dH to 20° dH, we recommend that the cylinder temperature is The use of the Logamax plus GB162 gas condensing set to ≤ 55 °C. As an alternative, a water treatment system boilers for DHW heating with cylinder primary system can also be used.
DHW heating Separate DHW heating via a 3-way diverter valve for the Logamax plus GB162-45, GB162-50, GB162-65, GB162-80 and GB162-100 DHW priority circuit When fitting the valve, ensure the correct The universal burner control unit UBA3.5 of the Logamax position is maintained. The motor must not plus GB162 gas condensing boilers features a DHW hang down.
Page 49
DHW heating DHW heating via pump assembly with integral 3-way diverter valve for the Logamax plus GB162-50 and GB162-65 The 3-way diverter valve can only be fitted to the l.h. side plus GB162-50 and GB162-65, and cannot be used for of the pump connection assembly.
Suitable for both boiler output ranges DHW cylinders are recommended. Recommendation according to example Condition: DHW cylinder is heated to 60 °C. Table 20 Explanation of the colour coding in table 19 6 720 645 821 (2010/09) – Logamax plus GB162...
Cold water inlet to DIN 1988-2 DHW circulation inlet Check valve DHW circulation pump Logalux S120 W 6 720 642 463-31.1il Fig. 43 Version of a DHW circulation line for the Logalux S120 W DHW cylinder 6 720 645 821 (2010/09) – Logamax plus GB162...
Heat source pump Cylinder primary pump Solar circuit pump DHW circulation pump RC.. Programming unit Differential pressure controller Heating system return Boiler return DHW cylinder return Table 21 Overview of frequently used abbreviations 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 53
4121 2x0,6 A / B 6 720 642 463-33.1il Fig. 46 Sample circuit diagram for the hydraulics and control of all systems that include the Logamax plus GB162 (design information tab. 22, page 54) Reference room The boiler does not include a safety valve...
Page 54
Page 37 A low water indicator is not required when installing the Logamax plus GB162 gas condensing boiler as an attic heating centre. The function of a thermostatically controlled low water indicator is safeguarded with a minimum Page 9 ff.
Page 55
For open flue operation of the Logamax plus GB162 gas condensing boiler, the IP rating is IP 40. For balanced flue operation of the Logamax plus GB162, the IP rating is IP X4 D. The Logamax plus GB162 is equipped with a plug-in strip that includes a suitable plug for the power cable.
≤ 10 μS/cm Below the curves, fill with untreated tap water that meets the requirements of the Drinking Water Ordinance [Germany] Water hardness Water volume over the service life of the boiler 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 57
65 f.). When installing pipes that are permeable to oxygen, e.g. in underfloor heating systems, allow for system separation by means of a heat exchanger ( fig. 51, page 59). 6 720 645 821 (2010/09) – Logamax plus GB162...
Logamax plus Maximum transferable output at high efficiency pump. A high efficiency pump is available 10 K temperature differential as an accessory for the Logamax plus GB162-45, and can be installed inside the boiler. 150 mbar 200 mbar The pumps for the Logamax plus GB162 gas condensing...
Page 59
Additional RC25 programming unit feasible as a remote control if the RC35 programming unit has been clipped into the gas condensing boiler WM10 low loss header module may, alternatively, be plugged into the gas condensing boiler SMF recommended 6 720 645 821 (2010/09) – Logamax plus GB162...
Maximum modulation in output-dependent operation A high efficiency pump is available as an accessory for the with setting 0 at the RC35 programming unit Logamax plus GB162-45 and can be installed inside the tab. 25, page 64) boiler ( fig. 55).
Page 61
The RC35 programming unit of the Energy Management System (EMS) enables the heating circuit pump of the Logamax plus GB162-45 Logamax plus GB162 up to 45 kW to be adjusted in line with the system, so that it can be operated with different Δp [mbar ] residual heads Δp = constant or output-dependent...
Page 62
Low load Full load Resulting pump pressure 4 m Δp Residual head Resulting pump pressure 3 m Δp Flow rate Residual head GB162-65 with pump assembly incl. 3-way diverter valve Flow rate 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 63
6 720 642 463-46.1il Fig. 62 Pressure drop curve GB162-45 of the heat Fig. 63 Pressure drop curve GB162-50/65/80/100 of exchanger the heat exchanger Δp Δp Pressure drop Pressure drop Flow rate Flow rate 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 64
Particularly with low system design temperatures, such as 40/30 °C in underfloor heating systems, the internal heating circuit pump of the Logamax plus GB162 gas condensing boilers may prove inadequate. In this case allow for a circuit via a low loss header with secondary pump ( fig.
Average total system water content Example 1 Given • System output Q = 18 kW • Panel radiators Checked • Total system water content = 175 l fig. 64, curve d) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 66
1360 1942 3107 1.00 1200 1714 2742 1.25 1000 1428 2284 1.50 1142 1827 Table 27 Maximum permissible system volume subject to the flow temperature and the required MAG pre-charge pressure 6 720 645 821 (2010/09) – Logamax plus GB162...
System examples Hydraulic boiler schemes for appliances with integral 3-way diverter valve 6.3.1 System example for a single boiler system, Logamax plus GB162-15/25/35 with RC25 or RC35 programming unit for one heating circuit with separate DHW heating 2x0,6 Logamatic 3x1,5...
System examples 6.3.2 System example for a single boiler system, Logamax plus GB162-25 T40S with RC25 or RC35 programming unit for one heating circuit with integral DHW heating 2x0,6 Logamatic 3x1,5 RC25 Netz RC35 2x0,6 THV/SA THV/SA THV/SA THV/SA 6 720 642 463-51.1il Fig.
System examples 6.3.3 System example for single boiler system, Logamax plus GB162-15/25 and GB162-25 T40S with RC35 programming unit for one heating circuit without mixer and one heating circuit with mixer with the same time channel (as option with system separation)
System examples 6.3.4 System example for the Logamax plus GB162-15/25 with low loss header, one heating circuit without mixer, one underfloor heating circuit with mixer and separate DHW heating via 3-way diverter valve RC35 RC25 2x0,6 (RC25) (RC35) 2x0,6 2x0,6...
System examples 6.3.5 System example for the Logamax plus GB162-15/25/35 with low loss header, one heating circuit without mixer, one underfloor heating circuit with mixer and DHW heating via cylinder primary pump (maximum equipment level with the RC35 and RC25 programming units)
System examples 6.3.6 System example for the Logamax plus GB162-15/25/35 with one heating circuit without mixer directly downstream, solar DHW heating and DHW reheating via 3-way diverter valve RC35 (RC25) 2x0,6 ÜS 2x0,6 Logasol SKN3.0 SM10 SKS4.0 CPC6 Logasol BC10...
System examples 6.3.7 System example for the Logamax plus GB162-15/25/35 with solar central heating backup and one heating circuit with mixer Logamatic 4121 FM443 2x0,6 ZV (THV) ÜS Logasol 3x1,5 SKN3.0 SKS4.0 230 V AC CPC6 Logasol 50 Hz 2x0,6...
System examples 6.3.8 System example for the Logamax plus GB162-15/25/35/45 with Logamatic 4121, solid fuel boiler and one heating circuit with mixer Logamatic 4121 2x0,6 ZV (THV) 3x1,5 3x1,5 2x0,6 BC10 2x0,6 KR PS G-KS 4x1,5 (HSM…) (HKV 2/…) Logamatic 2114 Logalux PR...
System examples 6.3.9 System example for the Logamax plus GB162-15/25/35 with solar DHW heating and central heating backup, solid fuel boiler and one heating circuit with mixer, buffer cylinder/Thermosiphon buffer cylinder and freshwater module Logasol KS01... Logalux FS-Z Logamatic 2114...
System examples Hydraulic boiler schemes for appliances without 3-way diverter valve 6.4.1 System example for Logamax plus GB162-45 with internal pump, RC35 programming unit, 3-way diverter valve and direct heating circuit without mixer RC35 2x0,6 BC10 G-SU 6 720 642 463-58.1il Fig.
System examples 6.4.2 System example for Logamax plus GB162-45 with low loss header, maximum version for the installation with EMS module inside the boiler and with RC35 or RC25 programming unit RC35 RC25 ZV (THV) 2x0,6 BC10 MM10 3x1,5 2...
System examples 6.4.3 System example for Logamax plus GB162-50/65 with DHW heating via a 3-way valve kit, RC35 programming unit and direct heating circuit without mixer RC35 2x0,6 2 BC10 G-SU 6 720 642 463-60.1il Fig. 76 Circuit diagram for the system example (index of abbreviations...
System examples 6.4.4 System example for the Logamax plus GB162-50/65/80/100 with DHW heating via a 3-way diverter valve, RC35 programming unit and direct heating circuit without mixer RC35 2x0,6 2 BC10 G-SU 6 720 642 463-61.1il Fig. 77 Circuit diagram for the system example (index of abbreviations page 52) •...
System examples 6.4.5 System example for the Logamax plus GB162-65/80/100 with low loss header and RC35 programming unit, one heating circuit without mixer, two heating circuits with mixers and DHW heating via a cylinder primary pump RC35 2x0,6 2 BC10...
System examples 6.4.6 System example for the Logamax plus GB162-45 and GB162-50/65/80/100 with Logamatic 4121, maximum standard equipment level with two heating circuits with mixer Logamatic 4121 2x0,6 2 2x0,6 2 3x1,5 2 2x0,6 2 4x1,5 2 2x0,6 2 3x1,5 2...
System examples 6.4.7 System example for the Logamax plus GB162-50/65/80/100 in a 2-boiler cascade, one heating circuit with mixer and one without, DHW heating via cylinder primary pump and use of a pump assembly 2x0,6 2 Logamatic 4121 mit FM456...
System examples 6.4.8 System example for the Logamax plus GB162-50/65/80/100 in a 2-boiler cascade, one heating circuit with mixer and one without, DHW heating via cylinder primary pump and use of a pump assembly 2x0,6 2 Logamatic 4323 mit FM441, FM458...
System examples 6.4.9 System example for the Logamax plus GB162-50/65 and GB162-50/65/80/100 in a 2-boiler cascade with two heating circuits with mixer 2x0,6 2 Logamatic 4121 mit FM456 Logamax plus 2x0,6 2 GB162-65 4x1,5 2 3x1,5 2 2x0,6 2 BC10...
≥ 80 ≥ 8 Table 29 Conditions for adequate admixing of condensate with domestic waste water 1) Maximum values at a system temperature 40/30 °C and 2000 hours run 2) Combustion output 6 720 645 821 (2010/09) – Logamax plus GB162...
3° 6 720 641 280-33.1il Fig. 83 Condensate hose from the gas condensing boiler and a flue via the neutralising system Neutralising system 6 720 645 821 (2010/09) – Logamax plus GB162...
– – – Table 30 Selection aid for connection accessories Logamax plus GB162-15/25/35 and GB162-25 T40S 1) Determine the required diaphragm expansion vessel to suit the specific system 2) Installation on the side towards the back 3) For retrofitting in the S-Flex, if the building is not equipped with a pressure reducer...
Page 88
Installation Connection accessories for the Logamax plus GB162-15/25/35 and GB162-25 T40S Designation Description Accessories; heating circuit and gas connection • 2 service ball valves Rp1 • Tee with cap for connecting an external MAG • Tee with drain & fill valve Heating circuit connection set •...
Page 89
Installation Connection accessories for the Logamax plus GB162-15/25/35 and GB162-25 T40S Designation Description Accessories for external DHW cylinders • DHW temperature sensor Ø 6 mm for DHW heating, with plug for connection to the terminal strip inside the gas condensing boiler •...
Page 90
Installation Connection accessories for the Logamax plus GB162-15/25/35 and GB162-25 T40S Designation Description DHW cylinder accessories for the sanitary side for S120 W, S135 RW and S160 RW • For DHW cylinders S120 W, S135 RW and S160 RW • Flexible corrugated hoses with thermal insulation and...
5 991 387 – – Table 32 Selection aid for connection accessories Logamax plus GB162-45 1) Cylinder primary pump sized for reduced flow rate 2) Alternative for UPM 15-70 2 W; installed outside the appliance 3) Alternative for Wilo Stratos ECO 25/1-5, installed outside the appliance...
NE 1.1 – Neutralising system with lifting pump 8 133 352 Table 34 Selection aid for connection accessories Logamax plus GB162-50/65/80/100 1) Available pump pressure for the heating circuit at 4000 l/h = 150–170 mbar 2) G-SU 1¼ ", pressure drop at 4000 l/h = 50 mbar, K...
Page 95
GA-BS • R1 Straight-through gas tap 1" • Straight-through form • Installation on finished walls • With integral fire safety valve Table 35 Connection accessories Logamax plus GB162-50/65/80/100 (assignment tab. 34) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 96
Line and measuring valve • DN32, K = 6.3; Rp1¼ ASV-M • DN40, K = 10; Rp1½ (only in combination with ASV-PV) Table 35 Connection accessories Logamax plus GB162-50/65/80/100 (assignment tab. 34) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 97
• To increase the head to approx. 4.5 m for NE 2.0 Neutralising agent • 10 kg bucket, sufficient for the NE 0.1, NE 1.1 and NE 2.0 Table 35 Connection accessories Logamax plus GB162-50/65/80/100 (assignment tab. 34) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 101
HSM 32 E plus, white, EMS inside 8 718 577 395 • For 1 heating circuit with mixer DN32, high efficiency pump, permanent magnet motor • MM10 mixer module, integral Table 38 Accessories 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 102
HSM 20 E plus = 6.3 m /h to 40 kW HSM 25 E plus = 8.0 m /h to 45 kW HSM 32 E plus = 18.0 m /h to 55 kW 6 720 645 821 (2010/09) – Logamax plus GB162...
200 mbar pressure drop: HS 25/4 E plus 8.5 kW HS 25/6 E plus 15 kW HSM15 E plus 7 kW HSM 20 E plus 15 kW HSM 25 E plus 15 kW 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 104
Install the MAG on site ÜS1 Adaptor set G1¼ to G1½ (product Height of the heating circuit quick installation sets no. 63 012 350), on-site pump HSM 32(-E) and HS 32(-E) 6 720 645 821 (2010/09) – Logamax plus GB162...
6 720 641 280-43.1il HKS DN32 on the WMZ – Fig. 94 Dimensions of the heat meter set with heating circuit distributor (dim. in mm) Table 40 Accessories for different combinations 6 720 645 821 (2010/09) – Logamax plus GB162...
Installation Cascade units Logamax plus GB162-50, GB162-65, GB162-80 and GB162-100 ≥80 6 720 642 463-72.1il Fig. 95 Cascade unit dimensions (dim. in mm) In-line installation Installation at the back Mounting support Cascade header GB162-50/65/80/100 Pump connection assembly (on-site connection of the MAG, connection ½...
9.1.2 System certification In accordance with the [German] Technical Rules for Gas The flues of the Buderus sets GA, ÜB-Flex with GA, GA-X Installations DVGW-TRGI 2008, the contracted installer with GA-K, ÜB-Flex with GA-X and GA-K, the sets of the...
– The gas condensing boilers are located in rooms where their operational reliability cannot be put at risk from the operation of open fireplaces. – The open combustion equipment has its own combustion air supply. 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 110
) must be No particular installation room is required for operating installed in rooms that feature a vent leading to the outside the Logamax plus GB162 gas condensing boilers with an of at least 150 cm or two vents of 75 cm each;...
Buderus sets equipment with a total rated output in excess of 100 kW The flue that is part of the Buderus set is made from requires a specific installation room. Observe relevant plastic. It is installed as a complete pipe system or as a national or regional combustion ordinances.
Page 112
– L0 for non-flammable casing system on site when connecting to a moisture-resistant – L1 for flammable casing flue system with the Buderus sets GN or GA-X with – L for designs without casing LAS-K (LAS multiple connection). In flue cascades, the condensate flows from the vertical...
Page 113
• The solar lines including their thermal insulation must correspond to the requirements of the flue where their temperature resistance is concerned. 6 720 645 821 (2010/09) – Logamax plus GB162...
98 and fig. 99). Position of the lower inspection aperture • Upstream and downstream of every diversion in excess • When connecting the Logamax plus GB162 to a flue, of 30°, an additional inspection bend is required. allow for a lower inspection aperture: •...
Page 115
≤ 0,3 6 720 641 280-47.1il Fig. 100 Example with the inspection apertures (P) located in a horizontal flue with diversions in the installation room - top view (dim. in m) 6 720 645 821 (2010/09) – Logamax plus GB162...
Flue systems for open flue operation Flue gas routed through a flue inside a shaft with GA set and secondary ventilation for the Logamax plus GB162 up to 45 kW Appliance type B (formerly B Observe the general information on page 108 ff.
Page 117
Flue gas routed through a flue inside a shaft with GA set and secondary ventilation Product no. Details Standard GA set for Logamax plus GB162 up to 45 kW 87 094 034 GA, PP plastic, Ø 80 mmWith stainless steel shaft cover and terminal pipe fig.
Flue systems for open flue operation Flue gas routed through a flue inside a shaft with GA set and secondary ventilation for the Logamax plus GB162-50, GB162-65, GB162-80 and GB162-100 Appliance type B (formerly B Observe the general information on page 108 ff.
Page 119
Spacer (4 pce) 87 090 421 – Stainless steel shaft cover and terminal pipe 87 090 150 – Table 48 Components of the GA set 1) Not in connection with ÜB-Flex 6 720 645 821 (2010/09) – Logamax plus GB162...
Interconnected combustion air supply to TRGI or vent to the outside 1 × 150 cm or 2 × 75 cm Air/flue gas concentric The manufacturer of the LAS will calculate and supply the required cross-section. 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 121
Components for the air/flue gas line inside the installation room and for flues in shafts with secondary ventilation: The additional equipment to supplement the standard GA-K set is listed for the Logamax plus GB162 up – Table 72, page 149 to 45 kW.
Routing flue gas via flexible flues inside a shaft with ÜB-Flex set in conjunction with the GA set or with the GA-X and GA-K sets For the Logamax plus GB162 the ÜB-Flex set is only 120 × 120 140 × 140 ∅...
Page 123
Standard ÜB-Flex set 25 m With flexible plastic flue PP, 25 m long 87 094 038 87 090 038 fig. 112 For operation of the Logamax plus GB162, the standard ÜB-Flex set is only permissible in conjunction with standard GA set. – To combine the ÜB-Flex set with the standard GA set:...
110). Atmospheric pressure Reduction of positive pressure Chimney connection Chimney manufacturer Even when connecting the Logamax plus GB162 to a Flue gas Ventilation air moisture-resistant special chimney, only a flue approved Flue pipe together with the gas condensing boiler that is suitable for Connection piece supplied by the manufacturer of the positive pressure (e.g.
Page 125
87 090 296 87° inspection bend 87 094 537 87 090 875 – Pipe with inspection aperture 77 190 015 33 87 090 236 – Table 55 Components of the GN set 6 720 645 821 (2010/09) – Logamax plus GB162...
• Positive pressure operation when all gas condensing flue is always required. The required condensate drain boilers operate at full load. with siphon is part of the Buderus flue cascade sets. • Negative pressure operation as soon as one gas Flue cascade set condensing boiler is shut down.
Page 128
Shaft set for flue cascade fig. 117 and Flue cascade shaft, plastic PP table 60, page 130 f. Table 58 Components of the flue cascade set (cont. tab. 60, page 130 f.) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 129
≈ 430 + D/2 6 720 642 463-80.1il Fig. 117 Plastic components of the flue cascade shaft set with Logamax plus GB162 plus one example of a 4-boiler cascade with Logamax plus GB162-50/65/80/100 gas condensing boilers (dim. in mm) I Shaft set for flue cascade:...
Page 130
87 090 416 500 mm 87 090 417 1000 mm 87 090 418 2000 mm 87 090 419 Table 60 Components of the flue cascade set (cont. from tab. 58, page 128) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 131
Ø 110 mm 7 747 202 158 – e.g. TR3/TR5 if the TR4 or TR6 set is used. Table 60 Components of the flue cascade set (cont. from tab. 58, page 128) 6 720 645 821 (2010/09) – Logamax plus GB162...
All maintenance can be carried out from the 10.1.2 System certification front. The air/flue gas lines of the Buderus sets DO, DO-S, Prohibited installation areas GA-K, ÜB-Flex with GA-K, GAF-K, GAL-K and LAS-K Never install gas appliances in essential stairwells (e.g.
Buderus sets In balanced flue operation, the fan draws in the required combustion air from the outside into the gas condensing boiler. The air/flue gas line of the Buderus sets is a concentric pipe or a pipe-in-pipe system made of plastic/steel.
Page 134
– L for designs without casing The flue system must be identified as system-certified following installation. For this purpose, an ID label is supplied with each standard set to provide system certification ( fig. 119). 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 135
Generally, a chimney sweep should clean the chimney Shafts for flues must not be used for any prior to installing a flue system with the Buderus GA-K or other purpose. ÜB-Flex set in conjunction with GA-K if one or more of the following applies: •...
Page 136
• The solar lines including their thermal insulation must correspond to the requirements of the flue where their temperature resistance is concerned. 6 720 645 821 (2010/09) – Logamax plus GB162...
DIN 18160-5 in front of the lower inspection aperture. ≤ 0,3 6 720 641 280-59.1il Fig. 121 Example with the inspection apertures (P) located in a flue with diversions in the installation room - top view (dim. in m) 6 720 645 821 (2010/09) – Logamax plus GB162...
137). On the roof, maintain minimum Logamax plus Dimension A clearances towards windows ( fig. 125). [mm] ≈ 70 GB162-15/25/35/45 ≈ 85 GB162-50 Table 62 Installation dimensions of the concentric boiler flue connection ( fig. 123) 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 139
7 747 009 801-79.1il Fig. 125 Minimum clearances towards windows with the DO set (dim. in m) (examples in accordance with the Muster-Feuerungsverordnung [Germany]; regulations page 132) No special clearance required 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 140
Vertical, concentric air/flue gas routing above the roof with the DO set Product no. Details Standard DO set for the Logamax plus GB162 up to 50 kW DO with plastic roof outlet PP/PE, steel inside, painted white, black exterior 77 190 036 60 fig.
Flue systems for balanced flue operation 10.3 Vertical, concentric air/flue gas routing above the roof with the DO set (DN110/160) for Logamax plus GB162-45, GB162-50, GB162-65, GB162-80 and GB162-100 Appliance type C DO set The Logamax plus GB162-50/65/80/100 requires a...
Page 142
DO set (order separately; dim. in mm) For flat roof For pitched roof Adhesive flat roof flange Universal roof tile Tiles for alternative roof slopes available on request. 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 143
130, 77 472 085 70 barrier pos. 13 Concentric expansion piece, from DN80/125 to DN110/160 87 090 868 – Table 66 Components of the DO set for boilers from 45 kW 6 720 645 821 (2010/09) – Logamax plus GB162...
Minimum dimensions and inspection apertures Allow for inspection apertures in accordance with regulations ( page 137). 6 720 641 280-65.1il Fig. 133 Installation version (dim. in mm) Flue gas Ventilation air Air/flue gas concentric 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 145
Air/flue gas routing via concentric pipe through a shaft with DO-S set Product no. Details Standard DO-S set for Logamax plus GB162 up to 45 kW DO-S in PP plastic/zinc-plated steel, painted white, Ø 80/125 mm 77 472 153 68 fig.
Flue systems for balanced flue operation 10.5 Concentric air/flue gas routing through a flue and shaft with GA-K set (DN80/125) for the Logamax plus GB162 up to 45 kW Appliance type C (formerly C order [Germany]). Where this cannot be ensured, design the flue using non-combustible materials (e.g.
Page 147
Concentric air/flue gas routing through a flue and shaft with GA-K set Product no. Details DN80 and Standard GA-K set for Logamax plus GB162 up to 45 kW DN110 DN80/125 GA-K in PP plastic/zinc-plated steel (painted white), 77 472 153 65 87 094 344 fig.
(according to the state combustion order [Germany]). Where this cannot be ensured, design the flue using non-combustible materials (e.g. stainless steel fig. 139) and route it inside the shaft used for the condensing boiler. 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 149
Fig. 141 Plastic components of the standard GA-K set Concentric air/flue gas routing through a flue and shaft with GA-K set Product no. Details Standard GA-K set for Logamax plus GB162 from 50 kW DN110/160 GA-K in PP plastic/zinc-plated steel (painted white), 87 094 054 fig.
10.7 Concentric air/flue gas routing through a flexible flue and shaft with ÜB-Flex set in conjunction with the GA-K set For the Logamax plus GB162 the ÜB-Flex set is only Minimum dimensions and inspection apertures permissible in conjunction with the GA-K ( fig.
Page 151
72, page 149 Table 74 Components of the ÜB-Flex set in conjunction with the GA-K set for, but not in connection with stainless steel shaft cover and terminal pipe 6 720 645 821 (2010/09) – Logamax plus GB162...
146). This requires the concentric roof outlet and either an adhesive flat roof flange or a universal roof tile with rain cap as auxiliary equipment ( fig. 147, roof outlet). 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 153
Concentric air/flue gas routing on an external wall with GAF-K set Product no. Details Standard GAF-K set for the Logamax plus GB162 up to 45 kW Plastic GAF-K in plastic PP/zinc-plated steel (painted white) inside the installation room and 77 472 153 69 fig.
Flue gas Ventilation air 400 mm sufficient if the output is restricted to 50 kW Alternative Ventilation air: ≥ at 30 cm (observe the height of snow deposits!) Stainless steel 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 155
Concentric air/flue gas routing on an exterior wall with GAF-K set Product no. Details internal and external Standard GAF-K set for the Logamax plus GB162 from 50 kW DN110/160 GAF-K in plastic PP/zinc-plated steel (painted white) inside the installation room 87 094 056 fig.
10.10 Concentric air/flue gas routing via a separate combustion air line inside the installation room and via a flue with secondary ventilation in a shaft with GAL-K set For the Logamax plus GB162 the Buderus GAL-K set is 120 × 120 140 ×...
Page 157
GAL-K, Ø 100/160 mm for GB162 (from 50 kW) 87 094 058 For the operation of the Logamax plus GB162, the GAL-K extension set is only permissible in conjunction with standard GA-K set. To combine the GAL-K extension set with the standard GA-K set (PP plastic/zinc-plated steel (painted white)): fig.
Practice G 636 “Gas appliances for connection to an air/flue gas system operating with negative pressure (standardised procedure).” Inspection apertures Allow for inspection apertures in accordance with regulations ( page 137). 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 159
(Ø 80 mm, 500 mm long; Ø 125 mm, 300 mm long Concentric air/flue gas routing via an air/flue gas system Product no. Details Standard LAS-K set for Logamax plus GB162 gas condensing DN80/125 DN110/160 boilers, PP plastic/zinc-plated steel (painted white)
DHW circulation line ..............Integral ..............Separate ........– Diaphragm expansion vessel DO set (45 to 100 kW) ..........– Components ......... Maximum total flue length ...... Minimum clearances towards windows 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 168
Set GA (up to 45 kW) ........– ......... Connection accessories Maximum total flue length .............. Dimensions Set GAF-K (50 to 100 kW) ......................Equipment overview Components ....................Function principle Maximum total flue length 6 720 645 821 (2010/09) – Logamax plus GB162...
Page 169
ÜB-Flex set with GA-X und GA-K (up to 35 kW) ......... Maximum total flue length ......– – Underfloor heating system ....... Universal burner control unit UBA3.5 ......– 3-way diverter valve 6 720 645 821 (2010/09) – Logamax plus GB162...