Service Manual Part : Technical Information 1. Summary Indoor Unit: ON/OFF Technical Information...
Page 5
Service Manual Outdoor Unit: Remote Controller YB1F2(XFAN) AUTO HEALTH X-FAN HUMIDITY FILTER TURBO HOUR ON/OFF ON/OFF MODE X-FAN TEMP TIMER TURBO SLEEP LIGHT Technical Information...
Page 6
Service Manual 1.GWH09KF-K3DNA6G(LCLH) 2.GWH09KF-K3DNB2G(LCLH) Model 3.GWH09KF-K3DNA5G(LCLH) 4.GWH09KF-K3DNA9G(LCLH) 5.GWH09KF-K3DNB1G(LCLH) 6.GWH09KF-K3DNB4G(LCLH) 1.CB146036201 2.CB409002701 3.CB146037601 4.CB146037001 5.CB146037901 6.CB146038401 Rated Voltage 220-240 Power Cooling Capacity(Min~Max) 2600(450~3230) Heating Capacity(Min~Max) 2800(450~4100) 870(200~1420) 900(200~1550) 1550 2.99 3.11 SEER SCOP Application Area 12-18 Indoor Unit Model 1.CB146N36200 2.CB409N02701 3.CB146N37600 4.CB146N37001...
Page 7
Service Manual CB146W36201 ZHUHAI LANDA COMPRESSOR CO.,LTD. Compressor Model QXA-A091zE190A Compressor Oil RB68EP Compressor Type Rotary Compressor Rated Load Amp (RLA) 1NT11L-6233 °C 16~30 °C -15~43 Range °C -20~24 Range Condenser Form Condenser Pipe Diameter 1-1.4 710X19.05X508 0.36 1600 Climate Type Isolation IP24 dB (A)
Page 8
Service Manual 1.GWH12KF-K3DNA6G(LCLH) 2.GWH12KF-K3DNB2G(LCLH) Model 3.GWH12KF-K3DNA5G(LCLH) 4.GWH12KF-K3DNA9G(LCLH) 5. GWH12KF-K3DNB1G(LCLH) 6.GWH12KF-K3DNB4G(LCLH) 1.CB146036101 2.CB409002401 3.CB146037501 4.CB146037101 5.CB146038001 6.CB146038501 Rated Voltage 220-240 Power Cooling Capacity(Min~Max) 3500(450~3230) Heating Capacity(Min~Max) 3800(450~4100) 1150(200~1420) 1100(200~1550) 1650 3.04 3.45 SEER SCOP Application Area 16-24 Indoor Unit Model 1.CB146N36100 2.CB409N02400 3.CB146N37500 4.CB146N37101 5.CB146N38000 6.CB146N38500 Indoor Unit Fan Type...
Page 9
Service Manual CB146W36101 ZHUHAI LANDA COMPRESSOR CO.,LTD. Compressor Model QXA-A091zE190A Compressor Oil RB68EP Compressor Type Rotary Compressor Rated Load Amp (RLA) 1NT11L-6233 °C 16~30 °C -15~43 Range °C -20~24 Range Condenser Form Condenser Pipe Diameter 2-1.4 710X38.1X506 0.36 1600 Climate Type Isolation IP24 dB (A)
Service Manual 2.4 Cooling and Heating Data Sheet in Rated Frequency Cooling: Rated cooling Fan speed Fan speed connecting indoor Compressor Model of indoor Indoor P (MPa) T1 (°C) T2 (°C) 0.9 to 1.1 12 to 14 75 to 37 0.8 to 1.0 10 to 12 85 to 43...
Service Manual 4. Refrigerant System Diagram Outdoor unit Indoor unit Gas pipe side Valve 4-Way valve Di s charge Heat Accumlator Suction exchanger Compressor (evaporator) Heat exchanger Liquid pipe (condenser) side Valve Strainer Electron Capillary Strainer expansion valve COOLING HEATING Technical Information...
Service Manual 5.2 PCB Printed Diagram Indoor Unit Name Control interface of PG motor indoor fan sensor interface sensor interface 10 Up & down swing 11 Interface of display Technical Information...
Page 19
Service Manual Outdoor Unit Name Compressor Reactor 2 Reactor 1 DC fan Technical Information...
Service Manual 6. Function and Control 6.1 Remote Controller Introduction Buttons on remote controller ON/OFF Button AUTO HEALTH X-FAN MODE Button HUMIDITY FILTER +/- Button TURBO HOUR ON/OFF FAN Button Button Button ON/OFF MODE HEALTH SAVE Button X-FAN Button TEMP Button TIMER Button X-FAN TEMP...
Page 21
Service Manual 1.ON/OFF button 2.MODE button AUTO COOL DRYF AN HEAT Note: C~30 C(61 F~86 3."+" or "-" button 4.FAN button AUTO Note: button no display position) Note: button no display (swing angle is displayed dynamically) position) Technical Information...
Page 22
Service Manual swing angle is displayed dynamically Note: 7.HEALTH/SAVE button SAVE function: 8.X-FAN button Note: 9.TEMP button no display Note: 10.TIMER button Note: 11.TURBO button disappeared on remote controller. 12.SLEEP button 13.LIGHT button Technical Information...
Page 23
Service Manual Function introduction for combination buttons Child lock function Switchover function for temperature display C and °F. Operation guide MODE Replacement of batteries in remote controller direction. signal sender battery NOTICE reinstall remove Cover of battery box Technical Information...
Service Manual 6.2 Brief Description of Modes and Functions 1.Temperature Parameters 2. Basic Functions (1)COOL mode (2) Dehumidifying mode speed. (3) HEAT mode Installation and Maintenance...
Page 25
Service Manual Note:T total total total total (4) Fan Mode will stop. (5) AUTO Mode (6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes seconds. Installation and Maintenance...
Page 26
Service Manual 3. Other Controls (1) ON/OFF (2) Mode Selection (3) Temperature Setting Option Button (4) Time Switch (5) SLEEP State Control Cooling mode Heating mode: (6) Indoor Fan Control (7) Buzzer Control (8) Auto button (9) Up-and-Down Swinging Control O(0 ) Location L, Location A, Location B, Location C, Location D, Location L to Location D, stop at any Installation and Maintenance...
Page 27
Service Manual (10) Display Operation pattern and mode pattern display (11) Protection function and failure display after defrosted) (12) Drying Function (13) Power-failure memory function memory. (14) Refrigerant recycling function (applicable when changing installation location or in maintenance) mode. (15) Compulsive Defrosting Function Installation and Maintenance...
Service Manual Part : Installation and Maintenance 7. Notes for Installation and Maintenance Safety Precautions: 10. If the power cord or connection wire is not long enough, please get the specialized power cord or connection wire Important! from the manufacture or distributor. Prohibit prolong the wire by yourself.
Page 29
Service Manual Main Tools for Installation and Maintenance 1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill 4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner hexagon spanner 7. Electronic leakage detector 8.
Service Manual Installation procedures Start installation Preparation before installation Read the requirements select installation Prepare tools for electric connection location Select indoor unit Select outdoor unit installation location installation location Install the support of outdoor unit Install wall-mounting (select it according to the actual situation) frame, drill wall holes Connect pipes of indoor Fix outdoor unit...
Service Manual 8.2 Installation Parts-checking 8.4 Electric Connection Requirement Name Name 1. Safety Precaution Wrapping tape Connection pipe Drainage pipe Fixing screw frame Connecting remote controller conditioner. Wall pipe Air-conditioner Note: 8.3 Selection of Installation Location 1. Basic Requirement: 2. Grounding Requirement: 2.
Page 33
Service Manual 5. Connect the Pipe of Indoor Unit in Fig.5) 3. Install Wall-mounting Frame Wall Wall Mark in the middle of it Level meter Space Space to the to the Open-end wrench wall wall above above Union nut 150mm 150mm Pipe Pipe joint...
Page 34
Service Manual 7. Connect Wire of Indoor Unit 8. Bind up Pipe Panel Screw Fig.11 Wiring cover Indoor and outdoor power cord Indoor unit pipe Liquid Fig.14 pipe Band Drain hose Cable-cross hole Drain hose Connection pipe Band Power connection wire Fig.12 Fig.15...
Service Manual 8.6 Installation of Outdoor Unit . m) 1. Fix the Support of Outdoor Unit(Select it according to the actual installation situation) 15~20 30~40 45~55 60~65 expansion screws. 70~75 Note: 5. Connect Outdoor Electric Wire N(1) screws are needed. yellow- blue brown...
Service Manual 8.8 Check after Installation and Test Operation The drain hose can't be fluctuant 1. Check after Installation The water outlet installation. can't be placed in water The drain hose can't be fluctuant The water Fig.27 outlet can't be fluctuant emit noise.
Service Manual 9. Maintenance 9.1 Flashing LED of Indoor/Outdoor Unit and Primary Judgement Unit Name 0.5s) Code 0.5s Display Operation Cool Heating Yellow Green Indicator Indicator Indicator Indicator Indicator Indicator operation, except indoor fan operates, all loads stop protection of operation.
Page 38
Service Manual Unit Name 0.5s) Code 0.5s Display Operation Cool Heating Yellow Green Indicator Indicator Indicator Indicator Indicator Indicator Nominal cooling mode refrigerant Indoor sensor is operation. Indoor AC stops operation once Indoor fall internal fan motor stops sensor is stop operation OFF 3S operating, compressor stops...
Page 39
Service Manual Unit Name 0.5s) Code 0.5s Display Operation Cool Heating Yellow Green Indicator Indicator Indicator Indicator Indicator Indicator Decrease All loads operate normally, OFF 3S twice compressor is decreased OFF 3S decrease All loads operate normally, speed is too low compressor is decreased 4 times antifreezing...
Page 40
Service Manual Unit Name 0.5s) Code 0.5s Display Operation Cool Heating Yellow Green Indicator Indicator Indicator Indicator Indicator Indicator Compressor intermediate test state operation, compressor will stop protection of analysis (IPM protection, loss compressor operation. operation, compressor will stop of capacitor operation, compressor will stop protection AP1.
Page 41
Service Manual Unit Name 0.5s) Code 0.5s Display Operation Cool Heating Yellow Green Indicator Indicator Indicator Indicator Indicator Indicator 1. Bad contact of DC motor Internal fan motor, external fan 2. Bad contact of DC motor Internal motor motor, compressor and electric control end.
Page 42
Service Manual Unit Name 0.5s) Code 0.5s Display Operation Cool Heating Yellow Green Indicator Indicator Indicator Indicator Indicator Indicator operation, compressor will stop detection compressor operation, compressor will stop dropping for of complete detection control panel AP1. operation. 2.Wiring terminal 4V is loosened or operation.
Page 43
Service Manual If malfunction occurs,corresponding code will display and the unit will resume normal until protection or malfunction disappears. Installation and Maintenance...
Page 44
Service Manual Analysis or processing of some of the malfunction display: 1. Compressor discharge protection 2. Low voltage overcurrent protection 3. Communication malfunction 4. Sensor open or short circuit 5. Compressor over load protection 6. System malfunction 7. IPM module protection Installation and Maintenance...
Page 45
Service Manual 9.2 Procedure of Troubleshooting (1) Malfunction of Temperature Sensor Main detection points: Start eliminated eliminated eliminated Installation and Maintenance...
Page 46
Service Manual (2) Malfunction of Blocked Protection of IDU Fan Motor Main detection points: Start eliminated eliminated and motor correctly eliminated control terminal for PG motor is Replace PG motor eliminated Installation and Maintenance...
Page 47
Service Manual (3) Malfunction of Protection of Jumper Cap Main detection points: Start eliminated eliminated eliminated Installation and Maintenance...
Page 48
Service Manual (4) Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor Main detection points: Start U8 is still displayed Installation and Maintenance...
Page 49
Service Manual Communication Malfunction Troubleshooting for E6 malfunction Disconnect power and check if the connection wire of indoor and outdoor units and the built-in wire of electric box are correctly connected. Connect the wire properly according Is malfunction Correct connection? to the wiring eliminated? diagram.
Page 50
Service Manual Outdoot Unit (1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel) Turn on the unit and wait 1 minute Use DC voltmeter to measure the voltage on the two ends of electrolytic capacitor Fault with the voltage Replace the control...
Page 51
Service Manual (2) IPM Protection, Out-of-step Fault, Compressor Phase Overcurrent (AP1 below refers to the outdoor control panel) Installation and Maintenance...
Page 52
Service Manual Energize and switch on Use AC voltmeter If the voltage Check the supply to measure the IPM protection between terminal L voltage and voltage between occurs after the and N on wiring machine has run for terminal L and N restore it to board XT is within a period of time?
Page 53
Service Manual (3) High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor unit) Mainly detect: Overheat and high temperature protection Normal protection, please operate it after the outdoor ambient temp- Is outdoor ambient temperature higher than 53? erature is normalized.
Page 54
Service Manual (4) Start-up failure (following AP1 for outdoor unit control board) Mainly detect: Power on the unit Restart it up after Is stop time of the compressor 3 minutes longer than 3 minutes? Does startup fail? Connect the wires as Are the wires for the compressor connected per the connection correctly? Is connection sequence right?
Page 55
Service Manual (5) Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit) Mainly detect: Out of step occurs in Out of step occurs once the operation unit is powered on. Check if the fan terminal Is stop time of the Replace the fan Is the outdoor fan working...
Page 56
Service Manual (6) Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board) Mainly detect: 20 minutes after the complete unit is powered off Is the terminal FA for the Connect the electronic expansion valve wires correctly connected correctly? Resistances between the first four pins close to the terminal hole and the fifth...
Page 57
Service Manual (7) Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the outdoor unit) Mainly detect: Start Check wiring of the reactor (L) of the outdoor unit and the PFC capacitor Replace it as per the Whether there is any...
Page 58
Service Manual (8) Communication malfunction: (following AP1 for outdoor unit control board) Mainly detect: Start Did the equipment operate normally before the failure occurs? Check the wiring of the indoor and outdoor units with reference to the wiring diagram Check wiring inside of the indoor and outdoor Is the connection right? units...
Page 59
Service Manual (9) Malfunction of Overcurrent Protection Main detection points: Start eliminated eliminated eliminated eliminated model eliminated eliminated opened completely) eliminated Installation and Maintenance...
Service Manual 9.3 Maintenance Method for Normal Malfunction 1. Air Conditioner Can't be Started Up connected well. or poor connection for wiring terminals correctly once improper Repair or replace remote controller 2. Poor Cooling (Heating) for Air Conditioner motor is set too low conditioner Add refrigerant.
Page 61
Service Manual 4. ODU Fan Motor Can't Operate Connect wires according to wiring diagram to Wrong wire connection, or poor connection diagram damaged fan capacitor. 5. Compressor Can't Operate Connect wires according to wiring diagram to Wrong wire connection, or poor connection diagram Capacity of compressor is...
Service Manual 11. Removal Procedure Caution: discharge the refrigerant completely before removal. 11.1 Removal Procedure of Indoor Unit Steps Procedure Points 1. External features If ON/OFF button is kept pushing for 5 seconds, aforced cooling op- eration willbe carried out for approx.
Page 75
Service Manual Steps Procedure Points 3. Remove panel Support the front panel by one hand, while remove the rotation Pull down horizontal blade axis at the upper center by the by pulling forward. other hand. And pull out the front panel forward to remove.
Page 76
Service Manual Steps Procedure Points 4. Remove electric box cover screws Remove a electric box cover mounting screw. Open electric box cover upward. electric box cover A switch for field setting is not provided in particular. screws 5. Remove front case Remove the 3 screws, in the right and the left, Screw stoppers inside the...
Page 77
Service Manual Steps Procedure Points 6. Remove the vertical blade Hooks Unfasten the hooks at the upper 2 positions. A set of vertical blade has 6 fins as on ASSY. (It is impossible to replace only one fin.) The set of vertical blades is not marked for difference between right and left.
Page 78
Service Manual Steps Procedure Points 7. Remove electrical box Disconnect the c able clamp Pay attention to the direction of the retainer of the thermistor so that the retainer will not touch the harness (same as the existing models.) Terminal board Disconnect the connection wires.
Page 79
Service Manual Steps Procedure Points Remove fan motor Signal fan motor Signal Wire Wire Remove a screw on the electrical box. Bottom frame Pull up the electrical box forward to remove. Hook Installation and Maintenance...
Page 80
Service Manual Steps Procedure Points 8. Remove the shield plate and control PCB Hooks Unfasten the hooks at the upper 2 positions of the shield plate. Remove the electrical box according to the “Removal of Electrical Box”. shield plate (1) Unfasten the hook at the lower position, and remove the shield plate...
Page 81
Service Manual Steps Procedure Points Take off wiring terminal Display PCB ASSY Remove display PCB sub-Assy. Remove swing motor. Swing motor Installation and Maintenance...
Page 82
Service Manual Steps Procedure Points The control PCB is To remove the control integrated with the power PCB, unfasten the 2 hooks at the upper part supply PCB. from the rear side. Lift up the upper part of the control PCB, and remove it.
Page 83
Service Manual Steps Procedure Points 9. Remove the refrigerant piping CAUTION If gas leaks, repair the spot of Lift the indoor unit by a leaking, then collect all wooden base. refrigerant from the unit. After conducting vacuum drying, recharge proper amount of refrigerant.
Page 84
Service Manual Steps Procedure Points 10. Remove evaporator assy When the pipings are disconnected, protect the Remove the indoor unit both openings from entering from the installation moisture. plate. Liquid piping Gas piping Auxiliary piping Piping fixture Release the hook of the piping fixture on the back of the unit.
Page 85
Service Manual Steps Procedure Points Loosen the 2 screws, in the right and the left, which fix the evaporator assy. Screws Auxiliary piping Widen the auxiliary piping to the extent of 10°~20°. evaporator Pull the evaporator assy to the front side to undo the hooks completely, and then lift it.
Page 86
Service Manual Steps Procedure Points 11. Remove cross flow fan and fan motor Cross flow fan Remove cross flow fan and Fan motor fan motor. Bearing Remove the rubber cushion of the bearing. Remove the screws at the joint of the cross flow blade and the motor.
Page 87
Service Manual Steps Procedure Points Take down the motor sub-assy. Remove fan motor. Installation and Maintenance...
Service Manual 11.2 Removal Procedure of Outdoor Unit Warning: Be sure to wait for a minimum of 20 minutes after turning off all power supplies and discharge the refrigerant completely before removal. Steps 1.Remove big handle Before disassamble. Remove 1 connection screw fixing big handleand then removethe big handle.
Page 89
Service Manual Steps 3.Remove grille and front panel Remove connection screws between the front grille and the front panel. Then remove the front grille. Remove connection screws connecting the front panel with the chassis and the motor support, and then remove the front panel. Grille Panel 4.Remove axial flow blade...
Page 90
Service Manual Steps 6.Remove electric box assy Electric box assy Remove the 2 screws fixing the cover of elec- tric box. Lift to remove the cover. Loosen the wire and disconnect the terminal. Lift to re- move the electric box assy. 7.Remove 4-way valve assy Unscrew the fastening nut of the 4-way Valve 4-way Valve Assy...
Page 91
Service Manual Steps 9.Remove motor and motor support Motor support Remove the 4 tapping screws fixing the motor. Pull out the lead-out wire and remove the Motor motor. Remove the 2 tapping screws fixing the motor support. Lift motor support to re- move it.
Page 92
Service Manual Steps 11.Remove Compressor Remove the 2 screws fixing the gas valve. Unsolder the welding spot connecting gas valve and air return pipe and remove the gas valve. (Note: it is necessary to warp the gas valve when unsoldering the welding spot.) Remove the 2 Liquid valve screws fixing liquid valve.
Service Manual Appendix: Appendix 1: Reference Sheet of Celsius and Fahrenheit Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32 Set temperature display display display 60.8 69.8 78.8 62.6 71.6 80.6 64.4 73.4 82.4 66.2 75.2 84.2 Ambient temperature display display display 55.4...
Service Manual Appendix 3: Pipe Expanding Method Pipe Note: Pipe cutter Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps: Leaning Uneven Burr Pipe Shaper Downwards Union pipe Pipe Hard mold Note: Expander A(mm)
Page 95
Service Manual Appendix 4: List of Resistance for Temperature Sensor Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor (15K) Temp( Temp( Temp( Temp( 138.1 18.75 3.848 1.071 128.6 17.93 3.711 1.039 121.6 17.14 3.579 1.009 16.39 3.454 0.98 108.7 15.68 3.333...
Page 96
Service Manual Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K) Temp( Temp( Temp( Temp( 181.4 25.01 5.13 1.427 171.4 23.9 4.948 1.386 162.1 22.85 4.773 1.346 153.3 21.85 4.605 1.307 20.9 4.443 1.269 137.2 4.289 1.233 129.9 19.14 4.14 1.198...