Installation and User's Guide
Submenu
In/Out settings
Output voltage
Output frequency
Output mode
Input volt hysteresis
High Efficiency mode
Bypass transfer
Interrupt time
Overload prealarm
Redundancy mode
Available settings
Default settings
[200V] [208V] [220V]
[208V]
[230V] [240V]
Can be changed only
in Standby mode
[Disabled]
Frequency converter:
[Enabled] [Disabled]
Frequency settable in
frequency converter
mode
[Network]
[Industrial]
[Network]
Set UPS behavior
regarding transfer on
Bypass
[10V]
Sets input voltage
hysteresis from 1 to
10V
[Disabled]
[Enabled] [Disabled]
Power the output
from Bypass for high
efficiency
[Disabled]
[Transfer if BP AC
NOK]
[Enabled] [Disabled]
Allow transfer on
Bypass out of
tolerance
If Bypass transfer is
[10ms]
enabled, Interrupt
time: [10ms] [20ms]
Define break
duration when
transfer on Bypass
[10%] ... [102%]
[102%]
Load % when
overload alarm
occurs
[Unitary UPS] [Hot
[Unitary UPS]
Standby]
Force slew rate value
to 0.5Hz/s