Page 2
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm Like all solid state electronic devices, this system may operate erratically or can control panel.
Page 4
Table of Contents FIGURE 3-1: Programmer Keypad .....................30 3.1.2: Programmer Display .........................31 3.2: Real Time Clock Mode..........................32 3.3: Program Mode .............................33 3.3.1: DACT Programming .........................34 TABLE 3-1: Ademco Contact ID Format - Primary ................36 TABLE 3-2: 4+2 Standard and 4+2 Express Formats - Primary ............37 TABLE 3-3: All 3+1, 4+1 and 4+2 Expanded Formats - Primary ............38 TABLE 3-4: Ademco Contact ID Format - Secondary ...............41 TABLE 3-5: 4+2 Standard and 4+2 Express Formats - Secondary .............42...
Page 5
This digital communicator/transmitter has been designed to comply with standards set forth by the following regulatory agencies: • Underwriters Laboratories Standard • NFPA 72 National Fire Alarm Code • CAN/ULC - S527-M87 Standard for Control Units for Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents.
Page 6
NAC B+ NAC B- +12 VDC Resettable - Resettable (common) Zone 1 B+ Relay 2
Zone 1 B- Common Zone 2 B+ NC Contact Zone 2 B- NO Contact Zone 3 B+ Zone 3 A+ Relay 1 Zone 3 A- Common...
Product Description Product Description CHAPTER 1 The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines. The four inputs use conventional input devices. The 411UDAC accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. The unit also supervises AC voltage, telephone line input voltage/current and battery level.
Page 8
Product Features • Industry first 20-digit central station and service terminal telephone numbers • NAC coding per ANSI S-3.41 (Temporal Coding) • Surface mount technology • Separate external keypad and display provides means of programming 411UDAC in program mode provides means of testing input/output circuits (including telephone connections) in Troubleshoot Mode •...
Circuits Circuits The 411UDAC circuit board utilizes surface mount technology and contains a MicroController Unit (MCU), dual modular phone line jacks, piezo sounder, two sockets for optional programmable relays and connectors for input, out- put and power wiring. A piezo silence switch and reset switch are provided on the membrane panel which plugs into connector J7 on the main circuit board.
Controls and Indicators Controls and Indicators 411UDAC Controls and Indicators FIGURE 1-3:
Front Panel Switch • Reset Switch - to reset 411UDAC circuits • Acknowledge/System Silence Switch press once to acknowledge alarm or trouble (silence local 411UDAC piezo sounder and change all flashing LEDs to steady on) press a second time and hold for minimum of two seconds to perform a System Signal Silence (silence...
Components and Accessories Components and Accessories Main Circuit Board The main circuit board contains the system’s MCU (microcontroller unit), power supply, other primary components and wiring interface connectors. The main circuit board is shipped in the same carton as the cabinet but is not mounted in the cabinet.
Panel Configuration Panel Configuration The 411UDAC can be configured, through programming, for the following modes of operation: • Stand-alone Mode With Communicator Enabled - the 411UDAC functions as a latching digital alarm commu- nicator in which all input circuit activations latch (except those programmed as autoresettable) and are restored only by pressing the local reset switch.
Telephone Requirements and Warnings Telephone Requirements and Warnings 1.9.1 Telephone Circuitry - PH1 & PH2 AC Ringer Equivalence Number (REN) = 1.2B DC Ringer Equivalence Number (REN) = 0.0B Mates with RJ31X Male Connector Supervision Threshold: less than 4.0 volts for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line.
Telephone Requirements and Warnings 1.9.4 For Canadian Applications The following is excerpted from CP-01 Issue 5: “NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appro- priate Terminal Equipment Technical Requirements document(s).
Installation Installation CHAPTER 2 Mounting Options The cabinet may be either semi-flush or surface mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots and two additional 0.25" diameter holes located in the backbox.
Page 17
Mounting Cabinet Dimensions and Knockout Locations FIGURE 2-2: Top (back) Top (front) Knockouts ...
Operating Power Operating Power CAUTION: Several different sources of power can be connected to the 411UDAC. Disconnect all sources of power before servicing this unit. The communicator and associated equipment may be damaged by removing and/or insert- ing modules or cables with power applied. Primary Power Source (AC) and Earth Ground Connections AC power connections are made inside the 411UDAC cabinet.
Page 20
Operating Power Secondary Power Source (batteries) Observe polarity while connecting the battery. When installing one 12 volt battery for up to 7 Amp Hour applica- tions, connect the supplied battery cable (P/N 75516) by sliding the connector attached to the long red wire onto the positive (+) battery terminal and the connector attached to the long black wire onto the negative (-) battery terminal.
Input Channels Input Channels The 411UDAC has four channel inputs. Channel/input field wiring is supervised for opens (trouble), shorts (alarm) and ground faults by the 411UDAC. All conditions are visually and audibly annunciated and, if programmed, com- municated to a Central Station. Each channel is a Style B (Class B) Initiating Device Circuit with the exception of channel/input 3 which can be con- figured for Style B or Style D (Class A).
Page 22
Input Channels Fire•Lite MS-9200 Connection to 411UDAC FIGURE 2-6: Note: The M300 monitor module input, Program the 411UDAC as follows: which is being used to monitor the Channel 1 - Normally Open Contact Device (alarm) 411UDAC Relay Output programmed for Channel 2 - Host Panel Trouble DACT Trouble (requires optional 411RK Channel 3 - Supervisory...
Page 23
Input Channels Notifier AFP-200 Connection to 411UDAC FIGURE 2-7: Program the 411UDAC as follows: Note: The MMX-2 monitor module input, Channel 1 - Normally Open Contact Device (alarm) which is being used to monitor the Channel 2 - Host Panel Trouble 411UDAC Relay Output programmed for Channel 3 - Supervisory DACT Trouble (requires optional 411RK...
Output Circuits Output Circuits Notification Appliance Circuit The 411UDAC provides one Style Y (Class B) NAC (Notification Appliance Circuit). The NAC is supervised and power-limited and is capable of 1.0 amp of current. Note that when coding is selected, the NAC output is not power-limited.
Page 25
Output Circuits Relays Installation: The 411UDAC provides sockets for two optional Form-C relays (P/N:411RK) rated for 2.0 amps @ 30 VDC (resistive). Relay 1 must be installed in the main circuit board socket labeled K6 and Relay 2 must be installed in the socket labeled K5.
Telephone Circuits Telephone Circuits Provision to connect two independent telephone lines is available via two telephone jacks labeled PH1 (Primary) and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an RJ31X style interconnection. (RJ31X jacks must be ordered separately). CAUTION: It is critical that the 411UDAC be located as the first device on the incoming telephone circuit to properly function.
Optional Programmer Optional Programmer The Fire-Watch 411 Series DACT Programmer (Model PRO-411) is used to: switch between the digital alarm communicator's five Modes of operation set the digital alarm communicator's 24 hour internal clock in Real-Time Clock Mode program the 411UDAC digital alarm communicator in Program Mode test the status of input and output circuits (including telephone lines) in Troubleshoot Mode return all digital alarm communicator programming to the factory default settings in Default Mode To use the PRO-411 Programmer:...
UL Power-limited Wiring Requirements UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the 411UDAC is shown below.
Modes of Operation Modes of Operation CHAPTER 3 The 411UDAC has five operational modes: • Normal Mode • Real Time Clock Mode • Program Mode • Troubleshoot Mode • Default Mode The operational mode for the 411UDAC is Normal Mode. The operator is able to switch between any modes of oper- ation provided no alarm events are active in the system.
Normal Mode The 411UDAC meets NFPA 72 requirements for Remote Station Protective Signaling Service and Central Station Signaling Service reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. See “Central Station Communications” on page 52, for additional information. The 411UDAC can be switched from Normal Mode to any other Mode, provided no channel programmed for fire alarm or fire supervisory is active, that is, in alarm (shorted).
Normal Mode LAMP TEST KEY Pressing the Lamp Test key on the Programmer, while the digital communicator is in Normal Mode, will cause the front panel LEDs and all segments of the four 7-segment display on the 411UDAC to light. A Lamp Test can only be performed in Normal Mode.
Real Time Clock Mode Real Time Clock Mode Real Time Clock Mode is entered by pressing the MODE key followed by the 4-digit entry code 2525 and pressing the [ENTER/STORE] key. ® 2525 spells CLCK on a Touch-Tone phone. If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as information is entered into the 411UDAC, the digits will scroll across the Programmer display from right to left.
Program Mode Enter the second minute digit (0 in this example) and press the [ENTER/STORE] key. The number '0' will appear as the digit fourth from the left. Following the entry of the fourth and final digit, the operating mode will immediately switch to Normal Mode, indicating that programming of the time is now completed.
Program Mode While in Program Mode, the first three locations on the left of the Programmer display represent the memory address and the last location (farthest right) represents the contents of the memory address. The first address displayed is shown below: 00_F (address)(data) Certain program items will be locked from editing if the communicator is active (dialing, transmitting, etc.).
Page 35
Program Mode Primary Central Station Number Communication Format (20) One location is needed to select the Communication Format to the primary phone number. Address 20 is used for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE].
Page 36
Program Mode Ademco Contact ID Format Primary Central Station Event Codes If 'E' is entered for address 20, the following data is automatically programmed for the Primary Central Station phone number event codes. Enter '000' for the Setting to disable the report to the Central Station. The Channel # is not programmable.
Page 37
Program Mode 4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes If ‘1, A or C’ is entered for address 20, the following data is automatically programmed for the Primary Central Station phone number event codes. Enter '00' for the Setting to disable the report to the Central Station. 4+2 Standard and 4+2 Express Formats - Primary TABLE 3-2: Address...
Page 38
Program Mode All 3+1, 4+1 and 4+2 Expanded Formats Primary Central Station Event Codes If ‘0, 2, 3, 4, 5, 6, 7, 8 ,9, B or D’ is entered for address 20, the following data is automatically programmed for the Primary Central Station phone number event codes.
Page 39
Program Mode Primary Central Station Number Account Code (21 - 24) The four locations at addresses 21 - 24 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 20, enter three digits (one digit each in locations 21, 22 and 23 - location 24 is ignored).
Page 40
Program Mode Secondary Central Station Number Communication Format (50) One location is needed to select the Communication Format to the secondary phone number. Address 50 is used for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE].
Page 41
Program Mode Ademco Contact ID Format Secondary Central Station Event Codes If ‘E’ is entered for address 50, the following data is automatically programmed for the Secondary Central Station phone number event codes. Enter '000' for the Setting to disable the report to the Central Station. Ademco Contact ID Format - Secondary TABLE 3-4: Channel/...
Page 42
Program Mode 4+2 Standard and 4+2 Express Formats Secondary Central Station Event Codes If 1, A or C is entered for address 50, the following data is automatically programmed for the Secondary Central Sta- tion phone number event codes. Enter '00' for the Setting to disable the report to the Central Station. 4+2 Standard and 4+2 Express Formats - Secondary TABLE 3-5: Address...
Page 43
Program Mode All 3+1, 4+1 and 4+2 Expanded Formats Secondary Central Station Event Codes If 0, 2, 3, 4, 5, 6, 7, 8 ,9, B or D is entered for address 50, the following data is automatically programmed for the Secondary Central Station phone number event codes.
Page 44
Program Mode Secondary Central Station Number Account Code (51 - 54) The four locations at addresses 51 - 54 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 50, enter three digits (one digit each in locations 51, 52 and 53 - location 54 is ignored).
Page 45
Program Mode Input Channel 1 Function Selection (65) Factory default for Channel 1 is '0' for activation on fire alarm (2-wire smoke). Enter '1' for pull station; '2' for normally open contact device; '3' for host panel trouble; '4' for fire supervisory; '5' for fire supervisory autoresetta- ble;...
Page 46
Program Mode Input Channel 4 Delay Timer (78 - 80) The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel is activated. Input Channel 4 Delay Timer is factory set to '000' seconds for no delay. The timer may be pro- grammed for a delay of from 0 to 179 seconds.
Page 47
Program Mode Alarm Verification Enable (91) Alarm verification works only on zones programmed as 2-wire smoke detector zones (i.e. zones 1 and 3). After detecting an alarm, the panel removes power from two-wire smoke zones for 6 seconds, resetting all 2-wire smoke detectors.
Page 48
Program Mode The input circuit must be physically clear of an input short upon completion of the reset period. If, and only if, the input circuit is normal (clear of an input short) after the reset period will the communicator transmit a Restoral Event to the Central Station.
Page 49
Program Mode Trouble Call Limit - Dialer Runaway Prevention (96) Factory default setting of '0' in address 89, allows the digital communicator to call the Central Station each time any DACT trouble and any active Channel programmed for host panel trouble is detected by the 411UDAC. Pro- gramming a '1' in this address enables the Trouble Call Limit feature, which limits the number of 411UDAC and Input Channel Trouble calls to the Central Station to 10 calls for each unique trouble event within a 24 hour period.
Default Mode Default Mode To return all program entries, including the upload/download secret password and time, to their factory original set- tings, perform the following steps only when the system is idle (i.e. the communicator is not active) and there are no active fire alarms or fire supervisories in the system: Press the MODE key followed by the 4-digit code 3337 and press the [ENTER/STORE] key.
Page 51
Troubleshoot Mode Battery Pressing B followed by the [ENTER/STORE] key will display the battery voltage. Note that the battery voltage display does not automatically update with a change in battery voltage. The [ENTER/STORE] key must be pressed each time a display update is desired. Shown below are the critical battery threshold conditions: Battery Voltage Normal Low Battery...
Central Station Communications Central Station Communications CHAPTER 4 The 411UDAC transmits system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made to interface the communicator to the telephone lines. Two 7-foot telephone cords P/N MCBL-7 may be used for this purpose (not supplied - order separately).
Page 53
Central Station Communications The digital communicator is capable of reporting detailed messages depending upon the Format in use. Table 4-1 shows the data reporting structure for each of the pulsed formats as well as the Ademco Express Formats. Ademco Express Formats allow a typical data message to be transmitted to the Central Station in under 5 seconds. Pulsed for- mats typically require 15 to 20 seconds in comparison.
Page 54
Central Station Communications Format Selection Address Explanation TABLE 4-2: Where: SSS or SSSS = Subscriber ID = Fire Alarm (1st digit) = Fire Alarm (2nd digit) = Channel/Input Number = Fire Alarm Restore (1st digit) RFA2 = Fire Alarm Restore (2nd digit) = Zone Trouble (1st digit) = Zone Trouble (2nd digit) = Zone Trouble Restore (1st digit)
Central Station Communications 4.0.1 Transmittal Priorities The digital communicator transmits highest priority events first. Events in terms of priority are listed below in descending order: Fire Alarm (highest priority level) Fire Supervisory System Troubles Host Panel Trouble (active input programmed for trouble) AC Fail (after delay) Channel/Input faults Telephone line fault...
Central Station Communications 4.0.2 Ademco Contact ID Format Event Code Description This section describes the various Event Codes and their messages which are available for the Ademco Contact ID Format. The reporting structure for the Ademco Contact ID Format is as follows: SSSS 18 QXYZ GG CCC Where: SSSS...
Page 57
Central Station Communications The following table contains UL listed receivers compatible with the 411UDAC’s onboard DACT. Compatible UL Listed Receivers TABLE 4-3: Format # (Addresses 20 and 50) 4+1 Ademco Express 4+2 Ademco Express (5, 6) 3+1/Standard/1800/2300 3+1/Expanded/1800/2300 3+1/Standard/1900/1400 3+1/Expanded/1900/1400 4+1/Standard/1800/2300 4+1/Expanded/1800/2300 4+1/Standard/1900/1400...
Remote Site Upload/Download Remote Site Upload/Download CHAPTER 5 The 411UDAC may be programmed off site via the public switched telephone network. Any personal computer with ® ® Windows 3.1 or greater or Windows 95, with a 1200 Baud Hayes compatible modem and Upload/Download soft- ware P/N PK-411UD, may serve as a Service Terminal.
General With program address location 64 set to '1' in Program Mode, anytime a contact with callback is initiated, the commu- nicator will first either contact the primary Central Station or contact both the primary and secondary Central Stations or contact the first available Central Station phone number to report a 'request for upload/download' message (depending upon the program entry in address location 137).
Downloading to the Communicator Central Station Acknowledge There is an option whereby the communicator will report to one or both Central Stations that a request for upload- ing or downloading has been received prior to processing the call. This is called the 'callback' option. If the Cen- tral Station(s) does not acknowledge receipt of this request, uploading or downloading is prohibited.
Simultaneous Data Transfers All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be in a standby state with no new information waiting to be transmitted to a Central Station. Once an incoming call is accepted/answered by the communicator, the 411UDAC will: Establish basic modem connection Verify secret code Verify callback vs.
Battery Calculations Battery Calculations CHAPTER 6 Use the Total Standby and Alarm Load Currents calculated in Table 6-2, “Load in Standby,” on page 63, and Table 6- 3, “Load in Alarm,” on page 63, for the following battery calculations. Battery Calculations TABLE 6-1: Standby Load Required Standby Time in Hours...
411UDAC Power Supply 411UDAC Power Supply The 411UDAC provides filtered power for operating the digital communicator, external devices and the battery charger. The power for operating external devices is limited. Use Table 6-2 (standby or nonalarm) and Table 6-3 (alarm) to determine if external loading is within the capabilities of the power supply. Load in Standby TABLE 6-2: Current...
Programming Sheets Programming Sheets Appendix A A.1 Digital Communicator Options Program Sheets --To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key. Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number. Primary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
Page 65
Programming Sheets Input Channel 4 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsi- lenceable; '8' for process monitoring; '9' for process monitoring autoresettable. Input Channel 1 Delay Timer.
Page 66
Programming Sheets Addresses 101 to 120 store the Service Terminal 1 Phone Number. Valid entries are 0 - 9 and A - E. 'F' designates the end of the phone number. Ring Count on Primary Phone Line. Enter number of rings prior to panel answering call. Valid entries are 00 to 25 (00 = no answer).
Programming Sheets A.2 Digital Communicator Options Program Sheet (Factory Defaults) --To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key. Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number. Primary Central Station Communication Format: 'E' for A demco Contact ID Format.
Page 68
Programming Sheets Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing. Make/Break Ratio for Secondary Phone. '0' for 67/33 ratio. Output Relay #1 Enable. '0' to enable relay. Output Relay #1 Function Selection. '0' for activation on fire alarm (2-wire smoke). Output Relay #2 Enable.
Event Codes/Transmission Format Programming Sheets Event Codes/Transmission Format Appendix B Programming Sheets --To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key. B.1 4+2 Standard & 4+2 Express Formats Primary Central Station B.2 4+2 Standard & 4+2 Express Formats Secondary Central Station Document #51073 Rev.
Event Codes/Transmission Format Programming Sheets --To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key. B.3 4+2 Standard & 4+2 Express Formats Primary Central Station B.4 4+2 Standard & 4+2 Express Formats Secondary Central Station Document #51073 Rev.A 1/19/99 P/N 51073:A...
Event Codes/Transmission Format Programming Sheets --To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key. B.5 All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central Station B.6 All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary Central Station B.7 All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central Station (Factory Defaults)
Event Codes/Transmission Format Programming Sheets --To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key. B.9 Ademco Contact ID Format Primary Central Station B.10 Ademco Contact ID Format Secondary Central Station Document #51073 Rev.A 1/19/99 P/N 51073:A...
Event Codes/Transmission Format Programming Sheets B.11 Ademco Contact ID Format Primary Central Station (Factory Defaults) B.12 Ademco Contact ID Format Secondary Central Station (Factory Defaults) Document #51073 Rev. A 1/19/99 P/N 51073:A...
Ademco Contact ID Format Event Code Description Ademco Contact ID Format Event Appendix C Code Description EVENT CODE CLASSIFICATIONS ALARMS SUPERVISORY TROUBLES DISABLES/ OPEN/CLOSE TEST/ BYPASSES REMOTE ACCESS MISC. Medical Fire System Open/Close System Test Fire Sounder/Relay Remote Access Sounder/Relay Panic System Peripheral Access Control...
Page 75
Ademco Contact ID Format Event Code Description EVENT MESSAGE General Alarms - 140 140 General Alarm ALARM - General Alarm - # 141 Polling loop open ALARM - Polling Loop Open - # 142 Polling loop short ALARM - Polling Loop Short - # 143 Expansion module failure ALARM - Exp.
Page 76
Ademco Contact ID Format Event Code Description EVENT MESSAGE System Peripheral Troubles - 330 and 340 330 System peripheral TROUBLE - Sys. Peripheral - # 331 Polling loop open TROUBLE - Polling Loop Open 332 Polling loop short TROUBLE - Polling Loop Short 333 Expansion module failure TROUBLE - Exp.
Events and Default Event Codes Events and Default Event Codes Appendix D Note: The character ‘x’ in the following table refers to the input circuit number (1 - 4). 411UDAC Events Format Group 1 Format Group 2 Ademco Contact ID Active and Input Circuit Functions Active...
Operational Modes Operational Modes Appendix E CODE ACTIVITY NOTES 6676 (NORM) Returns to normal operation Fire protection is on. Program digital communicator time. 2525 (CLCK) Enters Real-Time Clock Mode Fire protection is off. Allows programming of digital communicator. 7764 (PROG) Enters Program Mode Fire protection is off.
Page 83
Notes Document #51073 Rev. A 1/19/99 P/N 51073:A...
Page 84
Limited Limited W W W W W arr Limited anty anty Limited Limited arranty anty anty ® ® ® ® ® Fire-Lite Fire-Lite Fire-Lite Fire-Lite Fire-Lite warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture.