Controlling the Monitor with a PC (RS-232C)

You can control this monitor from a PC via RS-232C (COM
port) on the PC.
TIPS
• To control the monitor via RS-232C, set RS-232C/LAN
SELECT to RS-232C.
• When POWER SAVE MODE is set to ON, control is not
possible in standby mode.
• You cannot use RS-232C and LAN control simultaneously.

PC connection

Connect the RS-232C conversion cable (supplied) to the RS-
232C input terminal on the monitor. Connect the RS-232C
conversion cable (supplied) to the COM port (RS-232C port)
on your computer with an RS-232 cable (straight).
Computer
To COM port
RS-232 straight cable
(commercially available)
42
E

Communication conditions

Set the RS-232C communication settings on the PC to match
the monitor's communication settings as follows:
* Set to the same baud rate as the BAUD RATE setting of

Communication procedure

nCommand format
When a command is sent from the PC to the monitor, the
monitor operates according to the received command and
RS-232C input terminal
sends a response message to the PC.
RS-232C conversion
cable (supplied)
* Be sure to input 4 characters for the parameter. Pad with
When inputting a negative value, specify a numerical value in
three digits.
Do not use spaces for MPOS, DATE, and SC01 through
SC08. Specify parameters using a specified number of
characters.
If a command has "R" listed for "DIRECTION" in the
"RS-232C command table" on page 45, the current value can
be returned by using "?" as the parameter.
Baud rate
*
Data length
8 bits
Parity bit
None
SETUP menu. (Initial setting: 38400 bps)
C1
C2
C3
C4
P1
Command field
(4 prescribed
alphanumerical characters)
Example: VOLM0030
VOLM
30
spaces (" ") if necessary.
("
" is a return code (0D
Wrong : VOLM30
Right
: VOLM
30
Example: AUTR-005
Example: MPOS010097
Example:
VOLM ? ? ? ?
30
Stop bit
1 bit
Flow control
None
Return code
P2
P3
P4
Parameter field
(4 character string comprised of:
0-9, +, -, space, ?)
, 0A
or 0D
))
H
H
H
From PC to monitor (How much
is current volume setting?).
From monitor to PC (Current
volume setting: 30).