Example Of A Group Operation System With 2 Or More Outdoor Units And A M-Net Remote Controller - Mitsubishi Electric PUMY-P200YKM Technical & Service Manual

Hide thumbs Also See for PUMY-P200YKM:
Table of Contents

Advertisement

B. Example of a group operation system with 2 or more outdoor units and a M-NET remote controller.
(Address settings are necessary.)
L
2
L
6
A : Group
B : Group
C : Group
D : Shielded Wire
E : Sub Remote Controller
( ): Address example
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well
for all OC-OC, and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable block of the indoor unit
(IC).
c. Connect terminals M1 and M2 on the transmission cable terminal block of the indoor unit (IC) that has the most
recent address within the same group to the terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for centralized control (TB7) for the outdoor
unit (OC).
e. DO NOT change the jumper connector CN41 on MULTI controller circuit board.
f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi-
nal S on the power supply unit with the earth.
g. Set the address setting switch as follows.
Unit
IC (Main)
IC (Sub)
Outdoor Unit
Main Remote Controller
Sub Remote Controller
MA Remote Controller
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical
power has been turned on.
OCH575
OC
(51)
TB3
TB7
M1 M2 S M1 M2 S
D
L
3
OC
(53)
NO
TB7
TB3
M1 M2 S
M1 M2
S
Power Supply
Unit
M1 M2 S
D
System
controller
M1 M2 S
Range
01 to 00
Use the smallest address within the same group of indoor units.
Use an address, other than the IC (Main) in the same group of indoor units.
01 to 50
This must be in sequence with the IC (Main).
Use the smallest address of all the indoor units plus 50.
51 to 100
The address automatically becomes "100" if it is set as "01–50".
101 to 150
Set at an IC (Main) address within the same group plus 100.
151 to 200
Set at an IC (Main) address within the same group plus 150.
Address setting is not necessary. (Main/ sub setting is necessary.)
L
1
A
IC
IC
(01)
(02)
TB5
TB5
M1 M2 S
M1 M2 S
A B
(101)
RC
L
4
IC
IC
(04)
(03)
TB5
TB5
M1 M2 S
M1 M2 S
A B
(104)
RC
B
Setting Method
21
C
IC
IC
(05)
(06)
TB5
TB5
M1 M2 S
M1 M2 S
r
3
A B
A B
(105)
(155)
RC
RC
E
IC
(07)
TB5
M1 M2 S

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pumy-p200ykm-bs

Table of Contents