Summary of Contents for Toyotomi GAN-A180VL
Page 5
Installing, starting up, and servicing air conditioner can be Make sure the outdoor unit is installed on a stable, level surface with no accumulation of snow, leaves, or trash hazardous due to system pressure, electrical components, and equipment location, etc. beside.
Page 8
11 0 10 0 Conditions Conditions Indoor:DB27°C WB19°C Indoor:DB20°C Indoor air flo w Supper High Indoor air flo w Supper High Pipe lengt h 5m Pipe lengt h 5m 32 33 34 35 36 37 38 39 40 41 42 43 44 45 Outdoor temp.(°C) Outdoor temp.(°C)
ON/OFF Press it to start or stop operation. Press it to decrease temperaturesetting. Press it to increase temperaturesetting. MODE Press it to select operation mode(AUTO/COOL/DRY/FAN/HEAT). Press it to set fan speed. SWING Press it to set swing angle. I FEEL Press it to set HEALTH or AIR function.
LOCK icon: is displayed by pressing "+" and “-” buttons simultaneously. Press them again to clear the display. SET TIME display: After pressing TIMER button,ON or OFF will blink.This area will show the set time. DIGITAL display: This area will show the set temperature. In SAVE mode,"SE" will be displayed. AIR icon: is displayed when pressing the AIR button.Press this button again to clear the display.
Page 20
SWING: Press this button to set up & down swing angle, which circularly changes as below: This remote controller is universal. If any command is sent out,the unit will carry out the command as indicates the guide louver swings as: I FEEL: Press this button to turn on I FEEL function.
Press “TEMP” and “CLOCK” simultaneously in HEAT mode to start 8℃ Heating Function Nixie tube on the remote controller displays “ ” and a selected temperature of “ 8℃”. (46 if Fahrenheit is adopted). Repeat the operation to quit the function. About Back-lighting Function The unit lights for 4s when energizing for the first time, and 3s for later press.
Page 22
Tamb. Start cooling Tpreset +1 ˚C Original operating status Tpreset –1 ˚C Stop cooling ≥ 6 min. ≥ 3 min. ≥ 6 min. Compressor Outdoor fan Setting fan speed Indoor fan Stop During antifreeze protection Compressor Outdoor fan Indoor fan Preset speed Stop...
Page 23
amb. Cooling preset Dehumidfying preset― Stop min. min. min. Compressor Outdoor fan Indoor fan Low speed Stop Stop heating preset Original operating status preset Start heating min. Compressor Outdoor fan preset wind min. preset wind Indoor fan min. Reversing valve Stop...
Page 28
Space to the ceiling 15cm Above Space to the wall 15cm Above 15cm Above Space to the wall 300cm Above Above Air outlet side Space to the floor The dimensions of the space necessary for proper ● installation of the unit include the minimum permissible distances to adjacent parts.
Page 29
Flooded Wiring Cover GAN-A128VL GAN-A180VL GAN-A240VL GAN-A135VL N(1) N(1) yellow- yellow- orange yellow- orange blue black violet blue black...
Page 30
External connection Gas side piping electric wire Liquid side piping Tailing 2 Gas side piping Tailing 1 Liquid side insulation Piping insulation Finally wrap it Fig.3 Water drainage pipe with tape Left Right Left rear Fig.4 Right rear Fixing hook Mounting plate Mounting...
Page 32
Fig. a Fig. b Air filter Healthy filter Fig. c...
Page 42
(1) Malfunction of temperature sensor Start Is the wiring terminal between temperature sensor and the controller loosened or poor ly contacted? Insert the temperature sensor tightly Malfunction is eliminated. Is there short circuit due to tri-pover of the par ts? Make the parts upright Malfunction is eliminated.
Page 43
(2) PG motor (indoor fan) does not operate (H6) “H6”is displayed on the unit. Stir the fan blade with a hand when the unit is DE - ENERGIZED . Reinstall the motor Does the and the blade to blade rotate make it rotate unsmoothly? smoothly.
Page 44
(3) Jumper cap malfunction (C5) C5 is displayed on the unit. Install a matching Is there jumper cap on the jumper cap . controller? Is the malfunction eliminated? Re-insert the jumper Is the jumper cap inserted incorrectly or improperly? Is the malfunction eliminated? Replace the jumper...
Page 45
Start Normal fluctuation is within 10% of the rated voltage on the Is the supply voltage unstable with big fluctuation? Malfunction is eliminated. nameplate Is the supply voltage too low with overload? Adjust the supply voltage to maintain it within normal range Malfunction is eliminated.