Remote Indicators - Bosch AVENAR FAP-425 Operation Manual

Detector 4000
Table of Contents

Advertisement

AVENAR detector 4000
MH 400 Detector Heating Element
The MH 400 Detector Heating Element is required if the
detector is used in an environment where water
condensation can occur, such as in a warehouse that must
frequently be opened briefly for delivery vehicles.
The detector heating element is connected to the + V/0 V
terminals in the detector base.
Operating voltage: 24 V DC
Resistance: 1 kΩ
Power consumption: 3 W.
The heating is supplied with power either by the fed-
through supply voltage via the central unit or by a separate
power pack.
With supply via the central unit, the number of detector
heating elements depends on the cable diameter and line
length used.
2.5.1

Remote Indicators

A remote indicator is required if the detector is not directly visible or has been mounted in
false ceilings or floors. The remote indicator should be installed in corridors or access
pathways to the corresponding building sections or rooms.
Installation of the FAA-420-RI Remote Indicator
Warning!
Malfunction and Damage
!
If maximum current consumption of the connected detector is larger than 20 mA, it can result
in malfunction and damage to the remote indicator.
Before assembly remove the cap from the base plate
1.
2.
3.
Bosch Sicherheitssysteme GmbH
Unlock the snap‑fit hook by pressing on it with a flat object and lift the cap carefully
Remove the connection board for easy access.
Mount the base plate directly on a dry, level surface with two or four screws.
Operation Guide
System Overview | en
9
2014.11 | 1.1 | F.01U.283.550

Hide quick links: