en | System Configuration
Notice!
Only use buttons (no locking element) if you have programmed
inputs as Drill/Evacuate, Silence, or Reset Panel.
Access levels as per EN 54‑2 must be observed.
Notice!
Depending on the panel, there is one input on the FPC‑500‑2
and FPC‑500‑4, and two inputs on the FPC‑500‑8.
4
4.4.1

Input 1

4
1
1
Notice!
You do not have to confirm the input functions on the panel.
Thus use a key switch if possible to activate inputs.
2014.06 | 7.0 | F.01U.172.980
Press zone key 4.
This takes you to the Input Config menu.
Press zone key 4.
This takes you to the Input Config menu.
Press zone key 1.
This takes you to the Input 1 submenu.
Use the zone keys to set the programming for input
7
1.
...
1= Not Used (default setting)
2 Drill/Evacuate
3 Silence
4 Level 2
5 Reset Panel
6 Ext PS Fault
7 Ext Batt Fault
Conventional Fire Panel