Type; Indoor Unit Capacity System Address Indoor Unit Address Group Address - Toshiba RAV-SM564UTP-E Service Manual

Hide thumbs Also See for RAV-SM564UTP-E:
Table of Contents

Advertisement

DN
01
Filter sign lighting time
02
Filter pollution leve
03
Central control address
06
Heating suction temperature shift
OF
Cooling only
10

Type

11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
19
Louver type (wind direction adjustment)
Temperature range of cooling/heating
1E
automatic SW control point
28
Power failure automatic recovery
2A
Option/Abnormal input (CN70) SW
2b
Thermo output SW (T10
31
Ventilation fan (standalone)
32
Sensor SW (Selection of static pressure)
40
Humidifier control (+ drain pump control)
5d
High ceiling SW
60
Timer setting (wired remote controller)
Demand setting
C2
(outdoor unit current demand)
d0
Remote controller operation save function
d3
Rotation number of the self-clean operation
d1
Frost protection function
F0
Swing mode
F1
Louver fixing position (Flap No. 1)
F2
Louver fixing position (Flap No. 2)
F3
Louver fixing position (Flap No. 3)
F4
Louver fixing position (Flap No. 4)
Table 2. Type: CODE No. 10
Setting data
*1 * 2
0001
4-way Cassette Type
∗1 EEPROM initial value on the P .C. board for indoor unit servicing
∗2
CAUTION
<Model Name: RAV-SM∗∗∗UTP∗>
For the above models, set the CODE No. to "
data 0000 (initial) to "0001".
Table 1. Setting data (CODE No. table (example))
Item
)
Type
" and the setting
Setting data
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
Depending on Type.
0003: 3 deg (Ts ± 1.5)
0000: None
0002: Humidifier
0000: Thermo ON
0000: Not available
0000: Body sensor
0003: Humidifier ON + Pump OFF
0000: Standard
0000: Available
0075: 75 %
0001: Enable
0001: 210ypm(at self-clean operation)
0000: None
0001: Standard
0000: Not fixed
0000: Not fixed
0000: Not fixed
0000: Not fixed
Indoor unit capacity: CODE No. 11
Type name abb.
RAV-SM∗∗∗UTP∗
∗ EEPROM initial value on the P .C. board
for indoor unit servicing.
– 64 –
FILE NO. SVM-13010
Factory-set value
Table 3.
Setting data
Type
0000∗
Disable
0006
0007
0009
0012
0015
0017
0018
40
45
56
80
110
140
160

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents