Toshiba G8000 SERIES Installation And Operation Manual page 59

480/208 v 100/150 kw
Hide thumbs Also See for G8000 SERIES:
Table of Contents

Advertisement

Step 4-5 continues the procedure to start the UpS.
LED Key
- LED Off
- LED On
- LED Flash
BYPASS
MOVE 72B TO 'ON' POSITION
AC INPUT
CONVERTER
FLOAT CHARGE
EQUAL CHARGE
BATTERIES
DISCHARGE
BYPASS INPUT
UPS SUPPLY
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
BATTERIES
DISCHARGE
BYPASS INPUT
G8000 Series with Isolated output Installation and operation manual
UPS
INVERTER
AC
SWITCH
BYPASS
AC - Vo 208 V
AC - Io 50%
UPS
INVERTER
AC
SWITCH
BYPASS
STEP 4
Turn on the DC Input breaker (72b) on the
external battery cabinet.
bATTerIeS leD is "on".
AC OUTPUT
STEP 5
*press the "UpS" button for at least 0.5
seconds. This completes UpS startup
procedure
bypASS leD is "oFF".
UpS leD is "on".
AC OUTPUT
NOTE
*
If the AC switch does not function, contact
Toshiba or authorized representatives.
If the bypass power source is out of
specification, this operation will be inhibited.
In order to switch manually, press the "UpS"
button for 5 seconds or more.