LG ARNH963K2A2 Installation Manual page 49

Hydro kit medium temperature (k2) btu/h 107,500; hydro kit high temperature (k3) btu/h 86,000
Hide thumbs Also See for ARNH963K2A2:
Table of Contents

Advertisement

Indirect Hot Water storage tank Well and sensor (ebG61325701) - continued
7. Apply a generous portion of Thermo-paste to the sensor and in the
well.
• Use enough to fill the air space between the sensor head and the
walls of the sensor well.
8. Push the sensor all the way into the well until it bottoms out.
• Fill any air gaps with Thermo-paste.
9. Slide the keeping nut down the sensor cable and thread it on the
sensor well.
10. Choose a route between the sensor well and the Hydro Kit unit for
the sensor lead where the cable is protected from damage, foot traf-
fic; and extreme weather and temperature conditions.
11. Loosely secure the cable to the structure about every three (3) feet
with cable ties.
12. Avoid damaging the sensor cable, do not pull the ties too tight.
13. Route the sensor cable through the Hydro Kit casing and into the control
panel area.
• Where the cable passes through a hole with sharp edges, install field
supplied protective grommets.
14. Locate socket cN-tH4.
• Before plugging the male connector into the socket, verify unit
power is off.
• Inspect the leads and pins of the sensor cable plug. Look for bent
pins; and loose connections between the wire leads and the metal
pins in the plug.
15. Plug the sensor male plug-end into the cN-tH4 socket.
16. Lastly, verify the connection is secure.
solar Heating system Hot Water storage tank temperature sensor
Well (optional) Included with solar Interface Kit PN #PHlla (K2 Model only)
If optional Solar Heating kit is used, install the sensor well from the
kit in a similar manner used to install the water tank temperature
sensor.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Figure 48: Hot Water Storage Tank Sensor Cable Connection
Be sure to always have powered off before installation of accessories.
Never operate Hydro Kit outside of the operational parameters as out-
lined in this manual and the product specifications.
Never touch wiring or install accessories with wet hands.
fINIsH uP
Accessory Installation
Housing
Sensor Cable
49