80
en | Specifications
17
Specifications
Dimensions
(H x W x D)
Weight
D6100IPv6 Power Input
Current Required
Standby Power
Telephone
2012.11 | 08 | 4998122704
D6600
Rack mount (4U)
Standalone
D6100IPv6
Rack mount (2U)
Standalone
D6600
8.7 kg (19 lb)
D6100IPv6
3 kg (7 lb)
AC Nominal Operating
Range
AC Maximum Operating
Range
Power Cord
Replaceable Fuse
AC Nominal Operating
Range
D6600 with one line card
installed
For each additional line card
or terminal card pair
For network
communications card
D6100IPv6
The receiver includes an external battery connection and battery harness. Use 12 V
rechargeable sealed lead-acid batteries.
Standby power supply (UPS or battery) requirements: 24-hour minimum for UL Fire
applications (UL864); 4‑hour minimum for UL Burglary applications (UL1610).
Refer to Connecting External Batteries, page 27 for battery size.
RJ11C modular jacks, with 26 AWG or larger wire diameter.
Installation and Operation Guide
18 cm x 48.3 cm x 49.5 cm
(7.0 in x 19.0 in x 19.5 in)
18 cm x 45.0 cm x 49.5 cm
(7.0 in x 17.75 i. x 19.5 in)
9.0 cm. x 37.5 cm. x 25.5 cm
(3.5 in x 19 in x 10 in)
9.0 cm. x 30.5 cm. x 25.5 cm
(3.5 in x 12.0 in x 10 in)
120 V or 230 V
100 VAC to 120 VAC, 220 VAC to 240 VAC, 50 - 60 Hz
2.5 A maximum
IEC 60320 C13 type
2.5A F250V fast blow 5x20mm
18VAC (see specific Installation Supplement supplied
with your product for your application for supplied
transformer specifics)
Required battery current
Required UPS AC standby current
Required additional battery current
Required additional UPS AC
standby current
Required additional battery current
Required additional UPS AC
standby current
Required battery current
Required UPS AC standby current
Conettix Communications Receiver/
Gateway
800 mA
350 mA
210 mA
35 mA
10 mA
10 mA
330 mA
250 mA
Bosch Security Systems, Inc.