Download Print this page

Kenmore 2671532 Use & Care Manual page 25

Gas laundry center
Hide thumbs Also See for 2671532:

Advertisement

Available languages

Available languages

RECOMMENDED
MAXIMUM LENGTH
Exhaust Hood
Types
No. of 90 ° Elbows
0
1
2
3
EXHAUST SYSTEM CHECK LIST
Recommended
-I 4
Rigid Metal
56 Feet
46 Feet
34 Feet
32 Feet
Use only for
short
run installations
4" dia,
2-1/2"
Rigid Metal
42 Feet
36 Feet
28 Feet
18 Feet
HOOD
OR WALL CAP
• Terminate
in a manner to prevent
back drafts or entry of
birds or other wildlife.
• Termination
should present minimal
resistance
to the ex-
haust air flow and should require
little or no maintenance
to
prevent clogging.
• Never install a screen in or over the exhaust duct. This
could cause lint build up.
• Wall
caps must be installed
at least 12 in. above ground
level or any other obstruction
with the opening
pointed
down.
SEPARATION
OF TURNS
For best performance,
separate
all turns by at least 4 ft. of
straight
duct, including
distance
between
last turn and ex-
haust hood.
TURNS OTHER THAN 90 °
• One turn of 45 ° or less may be ignored.
• Two 45 ° turns should be treated
as one 90 ° turn.
• Each turn over 45 ° should be treated
as one 90 ° turn.
SEALING
OF JOINTS
• All joints should be tight to avoid leaks. The male end of
each section of duct must point away from the dryer.
• Do not assemble the ductwork
with fasteners that extend
into the duct. They will serve as a collection
point for lint.
• Duct joints can be made air and moisture-tight
by wrap-
ping the overlapped
joints with duct tape.
• Horizontal
runs should slope down toward
the outdoors
1/2
inch per foot.
INSULATION
Duct work that runs through
an unheated
area or is near air
conditioning
should be insulated
to reduce condensation
and
lint build-up.
Z IExhraust connection
TO REDUCE THE RISK OF FIRE OR PERSONAL
IN-
JURY:
• This appliance
must be exhausted
to the outdoors.
• Use only 4" rigid metal ducting
for the home exhaust duct.
• Use only 4" rigid metal or UL-listed
flexible
metal
(semi-
rigid or foil-type)
duct to connect the dryer to the home ex-
haust duct. It must be installed
in accordance
with the in-
structions
found in the section "Connecting
The Dryer To
House Vent" on this Use & Care Guide.
• Do not terminate
exhaust
in a chimney,
a wall, a ceiling,
gas vent, crawl space, attic, under an enclosed floor, or in
any other concealed
space of a building.
The accumulated
lint could create
a potential
fire hazard.
• Never terminate
the exhaust into a common
duct with a
kitchen exhaust system. A combination
of grease and lint
creates a potential
fire hazard.
• Do not use duct longer than specified
in the exhaust length
table.
Longer ducts can accumulate
lint, creating
a poten-
tial fire hazard.
• Never install a screen in or over the exhaust duct. This will
cause lint to accumulate,
creating
a potential
fire hazard.
• Do not assemble
ductwork
with any fasteners
that extend
into the duct. These fasteners
can accumulate
lint, creating
a potential
fire hazard.
• Do not obstruct
incoming
or exhausted
air.
• Provide an access for inspection
and cleaning
of the ex-
haust system, especially
at turns and joints. Exhaust system
shall be inspected
and cleaned
at least once a year.
THIS DRYER COMES
READY
FOR REAR EXHAUSTING.
IF SPACE IS LIMITED,
USE THE INSTRUCTIONS
IN SEC-
TION
9 TO EXHAUST
DIRECTLY
FROM
THE SIDES OR
BOTTOM
OF THE CABINET.
STANDARD
REAR EXHAUST
CSA (AGA)
approved
For straight
line installation,
new flexible
gas
connect
the dryer
exhaust
to the
line connector
external
exhaust
hood
using
duct
tape
or clamp.
Gas inlet
External
pipe
duct
\
Duct
tape
or
duct
clamp
4" Metal
duct
cut
to proper
lenght
Duct tape
or
duct
clamp
25

Advertisement

loading