Rack cabling reference guide
Hide thumbs Also See for D7171A - NetServer - LPr:
Table of Contents

Advertisement

Chapter 3
Table 3-2. 208 VAC Components
1
Component
PDU
HP NetServer LH 6000r
Pentium III Xeon,
550/512K
Pentium III Xeon,
550/1MB
Pentium III Xeon,
550/2MB
HP NetServer
Mass Storage Unit
HP Console Switch
Note 1.
More ratings are listed in Table 2-8. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2.
Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 208 VAC Configuration
Figure 3-6 shows a UPS connected to the power mains through a captive cord
terminated with an L6-20P plug. The UPS has five receptacles for use in the
rack: two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and
one L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a
detachable cord with an L6-20P plug. This cord connects to the PDU with an IEC
320 C-19 plug. The 208 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13
receptacles. A second PDU (E7670A) is available, which can be daisy-chained to
the 16-amp unit, providing ten more C-13 receptacles.
44
Procedure for Connecting and Routing Cables to the LH 6000r
Model
E7675A
D9104A
D9108A
D9112A
Rack Storage/12
is D5989A
Rack Storage/
12FC is D5991A
J1497B
Power
Power
Current
(VA)
(W)
(A)
N/A
N/A
max 16
1120
1099
5.3
541
530
4.5
42
29
0.2
2