Efficiency - Huawei PAC2000S12-B1 PSU Technical Manual

Table of Contents

Advertisement

PAC2000S12-B1 PSU
Parameter
Hot swap
NO TE
● Specifications are subject to change without notice.
● Short-time output power of MV12: V
W, the PSU does not trigger protection within 2 minutes if the output power of the PSU is switched to 2200
W transiently.
● When the PSU output voltage is less than 4 V, ignore the power-off ringback. When the PSU output voltage
ranges from 4 V to 9 V, the power-off ringback is less than 300 mV. When the PSU output voltage is greater
than 9 V, the power-off ringback is less than 400 mV.
● Active current sharing is used for the parallel system.
● Current sharing imbalance applies only to the normal temperature.
● Requirements for switching the output modes between MV12, SV12, and MV6:
PSON12V# is at high level, and the PSU output enters MV6 mode.
PSON12V# is at low level, and the PSU output enters MV12 mode.
When PSON12V# is at low level, the PSU IP PRESENT# works in the following modes:
IP PRESENT# is at high level, and the PSU output maintains MV12 mode.
IP PRESENT# is at low level, and the PSU output enters SV12 mode. The indicator blinks greenat 1
Hz.
IP PRESENT# signal detection validity time is greater than or equal to 25 ms, and the switching
delay time is less than or equal to 200 ms (including the detection time).
● In the parallel system current sharing scenario, fault isolation (except output overvoltage isolation) is
performed. The upper threshold of the 12 V output busbar voltage of the PSU is 12.8 V.
● In a parallel system, the upper threshold of the PSU 12 V output busbar voltage is 12.8 V for PSON12V#
switching.

2.4 Efficiency

Parameter
Output
Output
MV12
efficiency
Technical Manual
Output
Min.
Typ.
MV12
11.4
-
MV6
6.0
-
= 220 V AC, T
in
Min.
Typ.
87
-
Max.
Unit
12.6
V
8.2
V
= 50°C. After the output power of a single PSU is 1100
A
Max.
Unit
Notes & Conditions
-
%
T
= 25°C, V
A
200 W, without a fan
11
2 Electrical Specifications
Notes & Conditions
The system backplane
voltage must not exceed
the dynamic
specification
requirements of the PSU.
During the hot swap of
the MV12/SV12 output,
the bus voltage is lower
than 11.0 V and greater
than or equal to 11.4 V
for less than 100 µs.
= 230 V AC, P
=
in
out