Second Water Temperature Setting - Hitachi RCUE40AG2 Service Manual

Air cooled water chillers, cooling only and heat pump, cooling capacity 106/112 kw - 585/556/1030 kw
Table of Contents

Advertisement

Control System
Second water temperature
setting:
pag. 58
2. Forced capacity control
a) Contents
Compressor operation capacity is set forcedly through customer wiring terminals.
Order signal pattern and compressor operation capacity are shown as below.
HOLD
Xa
ON
Xb
ON
b) Wiring method (customer wiring terminal)

4.9. Second water temperature setting

According to the day run / night run or classifi cation of load application, temperature
setting can be changed remotely.
Thanks to the two setting temperatures and the two control procedures for water
temperature (capacity control and full load or energy storage) these can be combined to
have the following possibilities.
1) Air-conditioning (capacity control ) + Air-conditioning (capacity control)
2) Air-conditioning (capacity control) + Heat storage operation (100-0%)
3) Heat storage operation (100-0%) + Heat storage operation (100-0%)
Air-conditioning temperature is set by rotary switch on operation PCB and heat storage
temperature is set by using "▲or▼" switch on indication PCB (7 segment).
Operation mode and setting
Water temp
Operation mode
Air-conditioning
Air-conditioning
Capacity control
Capacity control
1)
Air-conditioning
Air-conditioning
Capacity control
Capacity control
Air-conditioning
Air-conditioning
Capacity control
Capacity control External Thermo Air-conditioning
2)
Heat storage
Heat storage
100-0%
Heat storage
Heat storage
100-0%
3)
Heat storage
Heat storage
100-0%
SMGB0003 rev.0-01/2007
Compressor forced operation capacity
LOAD DOWN
ON
OFF
Switch: Air-
Dip Switch
conditioning/
control
setting
heat storage
-
Air-conditioning
Air-conditioning
-
heat storage
heat storage
Air-conditioning
External Thermo
heat storage
heat storage
External Thermo Air-conditioning
Air-conditioning
External Thermo
heat storage
heat storage
Normal operation
LOAD UP
OFF
OFF
ON
OFF
Setting water
Operation signal
temp
Rotary Switch
Rotary Switch
Local / remote
Segment
Segment
Local / remote
Rotary Switch
Rotary Switch
Local / remote
Segment
Segment
External Thermo
Rotary Switch
Rotary Switch
External Thermo
Segment
Segment
External Thermo