5.5 Forced Oil Return
This function is used in recovering the oil level of the compressor through recollecting the accumulated oil
in the pipe.
■ Setting the function
Function
Forced Oil Return
SE 5
■ Option Selection
Setting
oFF
01
■ Detailed information
• This function is used with heat pump and heat recovery.
• Automatically disabled the forced oil return function after finishing oil return function.
· If a compressor is lost and it is unknown if oil is trapped in the pipeline, ask an authorized technician.
5.6 Forced Defrost
This function is used in defrosting of heat exchanger.
■ Setting the function
Function
Forced Defrost
SE 6
■ Option Selection
Setting
oFF
Def
■ Detailed information
• This function is used with heat pump and heat recovery.
• Automatically disabled the forced defrost function after finishing manual defrost.
246
_TROUBLE SHOOTING GUIDE BOOK
Option
01, oFF
Detail of function
Off (Default)
Oil return on
Option
Def, oFF
Detail of function
Off (Default)
Defrost on

5.7 Display Cycle Information

This function is to display the main parameter value displayed by LGMV in real time through the 7-segment
of the master outdoor unit for smooth operation when the LGMV cable is faulty or missing. The 7 segment
is display 26 different cycle data.
■ Setting the function
Function
Display Cycle Information
SE 8
■ Option Selection
step
Tittle
7-seg
op1
Current High Pressure
P1
op2
Current low Pressure
P2
op3
Inv 1 Pulse
h1
op4
Inv 2 Pulse
h2
op5
fan rpm
h3
op6
Subcooling degree
T1
op7
Superheating degree
T2
op8
ODU temp.
T3
op9
Suctino temp.
T4
op10
Comp1 discharge temp.
T5
op11
Comp2 discharge temp.
T6
op12
Liquid pipe temp.
T7
op13
Sc_in
T8
op14
Sc_out
T9
op15
hex_total
T10
op16
hex_hi
T11
op17
hex_low
T12
op18
Inlet pipe temp of IDU
T13
op19
main1 eev
PLS1
op20
main2 eev
PLS2
op21
sc eev
PLS3
op22
oil eev
PLS4
op23
vi eev1
PLS5
op24
vi eev2
PLS6
op25
IDU running capacity
IDU1
op26
Total number of IDU
IDU2
■ Detailed information
• This function is used with heat pump and heat recovery.
Option
op1~op26
example
seg_1
seg_2
seg_3
seg_4
4321 kPa
4
3
2
1
1234 kPa
1
2
3
4
120 Hz
1
2
0
30 Hz
3
0
110 RPM
1
1
0
53℃
5
3
-4.5℃
-
4
5
10℃
1
0
0
43.4℃
4
3
4
150℃
1
5
0
124℃
1
2
4
10℃
1
0
0
10℃
1
0
0
10℃
1
0
0
10℃
1
0
0
10℃
1
0
0
10℃
1
0
0
-10℃
-
1
0
0
1950 pls
1
9
4
0
32 pls
3
2
16 pls
1
6
50 pls
5
0
1350 pls
1
3
5
0
50 pls
8
24 KBtu
2
4
10 EA
1
0
247
_ _

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents