6.5.3.4 Setting Communications Parameters (SNMP Protocol)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
Figure 6-15 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
Step 3 Set Read Community and Write Community.
1.
2.
Step 4 Add a SNMPv3 user.
1.
2.
Issue 04 (2022-12-15)
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you connect
a unit to a network management system (NMS).
One unit supports concurrent access of up to 6 NMSs through SNMP.
When SNMP Version is set to ALL or SNMPv1&v2c, you can set Read
Community and Write Community.
When SNMP Version is set to ALL or SNMPv3, you can add an SNMPv3 user.
CA UTION
SNMPv1&SNMPv2c are insecure protocols. SNMPv3 is recommended.
Tap the text box next to Read Community, set the read community
parameter based on the actual plan, and tap Submit.
Tap the text box next to Write Community, set the write community
parameter based on the actual plan, and tap Submit.
Tap Add under SNMP V3.
Set User Name, Auth Protocol, and Prop Protocol based on the actual plan.