9.4 Sensor Module Cabinet-Mounted SMC10
9.4.3

Connection example

Figure 9-4
9.4.4

Meaning of the LED

Table 9-5
Meaning of the LEDs on the Sensor Module Cabinet-Mounted SMC10
LED
Color
RDY
-
Off
READY
Green
Continuous
light
Orange
Continuous
light
Red
Continuous
light
Green/re
Flashing
d
light 0.5 Hz
Flashing
light 2 Hz
Green/
Flashing
orange
light
2 Hz
or
Red/
orange
238
Connection of an encoder system via a Sensor Module Cabinet-Mounted (SMC) for a motor
without a DRIVE-CLiQ interface
Status
The electronics power supply is missing or outside the per‐
missible tolerance range.
The component is ready for operation. Cyclic DRIVE-CLiQ com‐
munication is taking place.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated irrespective of whether the correspond‐
ing messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. The system waits for POWER
ON.
Component recognition via LED is activated (p0144=1).
Note:
Whether the LED flashes green/orange or red/orange depends
on the status the LED had during activation (setting of param‐
eter p0144 to "1").
Description, cause
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
Remedy
Remove and acknowl‐
edge the fault.
Carry out a POWER ON.